How to Rebuild HONEYWELL ZONE VALVE
How to repair Honeywell Zone Valve - Part number: V8043E1012 + V8043E1061
Honeywell Zone Valve Rebuild Kit: amzn.to/2LlDYVA
Honeywell Zone Valve: amzn.to/2Lk1ylP
NEST Thermostat - amzn.to/2Szw28y
NEST Carbon Monoxide + Smoke Alarm - amzn.to/37vdgmX
Fuel Pump Strainer: amzn.to/2QwkxiI
Wool Filter: 1A-30 : amzn.to/2EwFzYg
4 Pack Fuel FILTERS: amzn.to/2UNWfPR
Burner Coupling: amzn.to/2CgoIXl
Burner Suntec Fuel Pump: amzn.to/2Lj6ozx
Beckett Cleancut Fuel Pump: amzn.to/2BjieFo
Pipe Dope to seal fuel oil lines: amzn.to/2Gk28RG
Threaded Fuel line check valve: amzn.to/2Exy9Uy
Flared fuel line check valve: amzn.to/2EvMyk5
option #2 : Fuel oil Check Valve: amzn.to/2GtpwvU
Boiler Safety
3/4" NPT Male x Female: amzn.to/2UOJPaz
Boiler Safety
3/4" NPT Female: amzn.to/2QUF2oF
Loctite Anti Seize: amzn.to/2Bm1f5i
Pipe Dope to seal fuel oil lines: amzn.to/2QxZEDL
High Temp RTV: amzn.to/2CeZfNM
KO Wool Blanket: amzn.to/2S4N37M
1/2" Boiler Rope Gasket: amzn.to/2UOLPQ7
3/8" Boiler Rope Gasket: amzn.to/2BjisMK
Blower Motor: amzn.to/2UKvvQp
Burner Coupling: amzn.to/2UN4agh
Beckett AFG Electrodes + Transformer Kit: amzn.to/2S4ybGD
Burner Suntec Fuel Pump: amzn.to/2QXBli5
Beckett Cleancut Fuel Pump: amzn.to/2Bq0J6a
Fuel Pump Strainer: amzn.to/2Gg7T2z
Wool Filter: 1A-30 : amzn.to/2Ey0vhl
4 Pack Fuel FILTERS: amzn.to/2S2SAfi
Tools:
11 in 1 Screwdriver: amzn.to/2BnAvl3
Pump Rotation Tester: amzn.to/2UNWA55
Milwaukee Head Lamp: amzn.to/2LjmiKs
5 Gal Shop Vac: amzn.to/2Lj6JlN
5 Gal Soot Vacuum Bags: amzn.to/2ExyBlI
Small Wire Brush: amzn.to/2BlS6K6
Milwaukee 2462-20 M12 1/4 Hex Impact Driver: amzn.to/2S4Pg3p
Greenlee PVC Cutter: amzn.to/2LqSfkd
Boiler Brush: amzn.to/2UOBdAr
Basic - Caulking Gun: amzn.to/2QS0Hhv
Soot Saw: amzn.to/2Bxhi0r
((( Post your questions in the comments and remember to subscribe! )))
"WARNING" - Do not attempt to work on or disassemble any part of your HVAC System if you're not a Skilled Technician. You assume any and all responsibility. Working on HVAC Systems can be VERY DANGEROUS and should only be performed by Highly Trained Technicians.
Thank you for your watching our videos.
Переглядів: 11 951

Відео

Service Call - Troubleshooting TOO COLD in HOUSE
Переглядів 5783 роки тому
All Zone valve calling for heat and No power to circulation pump AquaSmart Control: amzn.to/3aXcJPI Alpha Circ Pump: amzn.to/3stXQKB ((( Post your questions in the comments and remember to subscribe! ))) "WARNING" - Do not attempt to work on or disassemble any part of your HVAC System if you're not a Skilled Technician. You assume any and all responsibility. Working on HVAC Systems can be VERY ...
How to replace Boiler Circ Pump
Переглядів 2,6 тис.3 роки тому
Step by step video to change out a BAD BOILER Circ PUMP. Alpha Pump: amzn.to/3stXQKB Turn off boiler power Drain boiler Unhook power to pump Remove bad pump Clean flanges Install new pump Hook up power to pump Refill system Remove Air from system Turn on boiler power and continue bleeding air and testing for good fluid flow ((( Post your questions in the comments and remember to subscribe! ))) ...
How to FIX Baseboard Leak
Переглядів 12 тис.3 роки тому
Fire Extinguisher leak in baseboard heater including Tools and supplies used in the repair process. TOOLS Milwaukee Copper Cutter: amzn.to/3ung16J Milwaukee Drill: amzn.to/37JeKNl Milwaukee Pen Light: amzn.to/3qVUD6s Bernzomatic Torch:amzn.to/2NASTRl Wire brush for drill: amzn.to/3qJWomZ Tape Measure: amzn.to/3kf7UEw Sheet metal cutter: amzn.to/2Nq3uid Reamer: amzn.to/2OYtHEM Needle nose pliers...
Installing T4 Pro Honeywell Thermostat
Переглядів 66 тис.3 роки тому
New Tstat install on 4x4 box. THERMOSTATS CO DETECTORS T4 Pro Thermostat: amzn.to/3k0RgIC NEST Thermostat - amzn.to/2Szw28y NEST Carbon Monoxide Smoke Alarm - amzn.to/37vdgmX BURNER PARTS Blower Motor: amzn.to/2UKvvQp Burner Coupling: amzn.to/2UN4agh Burner FUEL PUMP Suntec Fuel Pump: amzn.to/2Lj6ozx Burner FUEL PUMP Beckett Cleancut Fuel Pump: amzn.to/2BjieFo Beckett AFG Electrodes Transformer...
BAD BURNER FUEL PUMP
Переглядів 21 тис.3 роки тому
Step by step video showing how to replace a burner fuel pump. INTRO: 0:01 REPLACING BURNER COUPLING: 2:08 REPLACING FUEL PUMP: 3:13 INSTALLING BYPASS PLUG: 4:57 CHECKING FUEL PRESSURE: 7:55 HOW TO RESET BURNER: 8:45 RECAP: 9:17 BURNER FUEL PUMP: amzn.to/2Lj6ozx BURNER COUPLING: amzn.to/2UN4agh PIPE DOPE: amzn.to/2QxZEDL BURNER PARTS Blower Motor: amzn.to/2UKvvQp Burner FUEL PUMP Beckett Cleancu...
ABOVE GROUND FUEL TANK - HOOK UP
Переглядів 2,5 тис.3 роки тому
Setting up ABOVE GROUND Fuel Tank SPACE HEATER: amzn.to/37buUPm Pipe Dope to seal fuel oil lines: amzn.to/2QxZEDL Complete GOLDENROD FILTER: amzn.to/3d8BLNn GOLDENROD Spin on filter with water blocker: amzn.to/2ZgkBFy TOOLS RIDGID PIPE WRENCH: amzn.to/3jNJEsM Quick Reamer: amzn.to/3ajjHy7 Honeywell Zone Valve Repair Kit: amzn.to/2LlDYVA Honeywell Zone Valve: amzn.to/2Lk1ylP NEST Thermostat - am...
Zone Valve Troubleshooting - Honeywell V8043E1012 + V8043E1061
Переглядів 24 тис.3 роки тому
Found bad Honeywell Zone Valve Part number: V8043E1012 V8043E1061 Honeywell Zone Valve Repair Kit: amzn.to/2LlDYVA Honeywell Zone Valve: amzn.to/2Lk1ylP NEST Thermostat - amzn.to/2Szw28y NEST Carbon Monoxide Smoke Alarm - amzn.to/37vdgmX Fuel Pump Strainer: amzn.to/2QwkxiI Wool Filter: 1A-30 : amzn.to/2EwFzYg 4 Pack Fuel FILTERS: amzn.to/2UNWfPR Burner Coupling: amzn.to/2CgoIXl Burner Suntec Fu...
Boiler not firing - Burner Tripping OFF
Переглядів 2,7 тис.3 роки тому
Troubleshooting blower motor. Burner control tripping. BURNER PARTS Blower Motor: amzn.to/2UKvvQp Burner Coupling: amzn.to/2UN4agh Burner FUEL PUMP Suntec Fuel Pump: amzn.to/2Lj6ozx Burner FUEL PUMP Beckett Cleancut Fuel Pump: amzn.to/2BjieFo Beckett AFG Electrodes Transformer Kit: amzn.to/2S4ybGD Burner Coupling: amzn.to/2CgoIXl Beckett AFG Electrodes: amzn.to/3oZBqyM Z gauge: amzn.to/36YxGaD ...
Water in Fuel Filter
Переглядів 1703 роки тому
Close up look at water in the fuel system FUEL FILTERS: Wool Filter: 1A-30 : amzn.to/2EwFzYg 4 Pack Fuel FILTERS: amzn.to/2UNWfPR Fuel Pump Strainer: amzn.to/2QwkxiI BOILER TUNEUP SUPPLIES High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": amzn.to/3jq6J4s Loctite Anti Seize: amzn.to/2Bm1f5i...
BOILER CLEANING - FAST MOTION
Переглядів 5533 роки тому
I tried to waste no time showing you how to clean an oil fired boiler system. Hope it helps! BOILER TUNEUP SUPPLIES High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": amzn.to/3jq6J4s Loctite Anti Seize: amzn.to/2Bm1f5i Pipe Dope to seal fuel oil lines: amzn.to/2QxZEDL KO WOOL HIGH TEMP Blan...
How to change BURNER Fuel Filter
Переглядів 8163 роки тому
Replacing burner fuel filter FUEL FILTERS: Wool Filter: 1A-30 : amzn.to/2EwFzYg 4 Pack Fuel FILTERS: amzn.to/2UNWfPR Fuel Pump Strainer: amzn.to/2QwkxiI BOILER TUNEUP SUPPLIES High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": amzn.to/3jq6J4s Loctite Anti Seize: amzn.to/2Bm1f5i Pipe Dope to...
How to replace burner electrodes
Переглядів 14 тис.3 роки тому
Installing new burner electrodes in AFG Beckett Burner Beckett AFG Electrodes: amzn.to/3oZBqyM Z gauge: amzn.to/36YxGaD Electrode setting tool : AFG Burners with - F Heads: amzn.to/36Ko5UK Universal Electrode Setting Tool: amzn.to/2YTpVy5 High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": a...
How to replace a pellet stove control board
Переглядів 2,7 тис.3 роки тому
Replacing bad control board on a pellet and Start Up. PELLET STOVE Parts: amzn.to/3p14bLj Rope Gasket Kits: amzn.to/3rsOTAF HVAC TOOLS Magnetic Flashlights: amzn.to/2YUQyml 11 in 1 Screwdriver: amzn.to/2BnAvl3 Milwaukee Headlamp: amzn.to/2LjmiKs 5 Gal Shop Vac: amzn.to/2Lj6JlN 5 Gal Soot Vacuum Bags: amzn.to/2ExyBlI Small Wire Brush: amzn.to/2BlS6K6 Milwaukee 2462-20 M12 1/4 Hex Impact Driver: ...
How to CLEAN a BURNHAM BOILER
Переглядів 20 тис.3 роки тому
High speed boiler cleaning BOILER TUNEUP SUPPLIES High Temp RTV: amzn.to/3oVLTeH 1/2" Rope Gasket: amzn.to/3aErSnJ 3/8" Rope Gasket: amzn.to/2YNgccM KO WOOL High TEMP Strips Blanket, 2200F 1" x 1/2" x 300": amzn.to/3jq6J4s Loctite Anti Seize: amzn.to/2Bm1f5i Pipe Dope to seal fuel oil lines: amzn.to/2QxZEDL KO WOOL HIGH TEMP Blanket: amzn.to/2S4N37M BOILER PARTS Blower Motor: amzn.to/2UKvvQp Bu...
HOW TO Replace BURNER NOZZLE - Beckett AFG Burner
Переглядів 4 тис.3 роки тому
HOW TO Replace BURNER NOZZLE - Beckett AFG Burner
-15 degrees (below zero) Troubleshooting Furnace
Переглядів 1,1 тис.3 роки тому
-15 degrees (below zero) Troubleshooting Furnace
20,000 VOLT BURNER IGNITION VS 10,000 VOLT BURNER IGNITION
Переглядів 13 тис.4 роки тому
20,000 VOLT BURNER IGNITION VS 10,000 VOLT BURNER IGNITION
How to fix a Honeywell Zone Valve. Part number: V8043E1012 + V8043E1061
Переглядів 145 тис.4 роки тому
How to fix a Honeywell Zone Valve. Part number: V8043E1012 V8043E1061
How to CHANGE FUEL FILTER on your BOILER or FURNACE
Переглядів 4,7 тис.4 роки тому
How to CHANGE FUEL FILTER on your BOILER or FURNACE
AFG Beckett Burner
Переглядів 28 тис.4 роки тому
AFG Beckett Burner
DANGER - SLOW MOTION Boiler Ignition
Переглядів 6924 роки тому
DANGER - SLOW MOTION Boiler Ignition
Boiler Safety Valve
Переглядів 4994 роки тому
Boiler Safety Valve
What's Inside a Fuel Oil Line Check Valve
Переглядів 6 тис.4 роки тому
What's Inside a Fuel Oil Line Check Valve
What's inside a burner nozzle!!
Переглядів 6724 роки тому
What's inside a burner nozzle!!
GOT SOOT? Check out this Dirty Boiler!
Переглядів 7816 років тому
GOT SOOT? Check out this Dirty Boiler!
Tigerloop in Action - Video #15
Переглядів 7 тис.6 років тому
Tigerloop in Action - Video #15
Suntec B2VA-8216 - BURNER FUEL PUMP
Переглядів 95 тис.6 років тому
Suntec B2VA-8216 - BURNER FUEL PUMP
How to Clean a Boiler Heat Exchanger - Video #9
Переглядів 50 тис.6 років тому
How to Clean a Boiler Heat Exchanger - Video #9
What's Inside a circulator Pump - Video #6
Переглядів 2,7 тис.6 років тому
What's Inside a circulator Pump - Video #6

КОМЕНТАРІ

  • @MrRixsy
    @MrRixsy 26 днів тому

    If I change the motherboard does it need programming ?

  • @bradc7254
    @bradc7254 2 місяці тому

    I have the same attachment foe my ash vac i use on my pellet stove except the bristles are a wire brush instead of plastic. Should work mint for doing my furnace. Isn't there a few other things like adjusting the fuel ratio and checking the co2 being released or something? And also ik you gotta use Chimney Sealant stuff, kinda like mortar around where the exhaust flue meets the actual chimney, also how frequently do i need to clean my actual chimney for my furnace? Idk if ive ever seen my plumber do that, he has however cleaned the exhaust flue that goes from the furnace to the chimney. And last question, also how do you adjust the oxygen ratio and air intake vent? Is there anything you even have to do there and if so how frequently?

  • @Dave-wz8nv
    @Dave-wz8nv 2 місяці тому

    3 years later. What an excellent informative video. Thanks from the UK.

  • @user-vw8nh4dw2o
    @user-vw8nh4dw2o 3 місяці тому

    This a great video for that 'headache' thing. Thank you.

  • @johnmitchell3719
    @johnmitchell3719 4 місяці тому

    Hi what type of screws holds the motorized valve to the frame i tried a philips but i cannot get really tight.

  • @4Fox59
    @4Fox59 4 місяці тому

    What happened to the programming link?

  • @Rysdad1
    @Rysdad1 5 місяців тому

    What is the large piece that you are working on that it's connected to called? Just called an oil burner?

    • @furnacetech2581
      @furnacetech2581 5 місяців тому

      The burner housing is the metal body that the fuel pump mounts to. The whole thing is the burner!

  • @ncooty
    @ncooty 5 місяців тому

    2 questions: 1. Why not use the common wire? 2. Why not mount the metal box cover to the box first, then the thermostat?

    • @furnacetech2581
      @furnacetech2581 5 місяців тому

      Thank you for watching and leaving your feedback! Most of our systems use only two wire setups. You can definitely use the common wire! I am sure there are many ways to mount a thermostat. This is just the way I did it for this project!

  • @tomclose6643
    @tomclose6643 5 місяців тому

    can i just leave zone valve head off and open up with that little handle so its getting hot water all the time when the other two zones call for heat?

    • @furnacetech2581
      @furnacetech2581 5 місяців тому

      Yes! It will heat if you manually open the valve!

  • @anthonyrosario7841
    @anthonyrosario7841 5 місяців тому

    Hi I got a question for you I have smoke coming out of the oil burner and I have oil leaking under de oil burner as well is that has to be with the oil pump or I will have to replace the entire oil burner.

    • @furnacetech2581
      @furnacetech2581 5 місяців тому

      You may have a fuel leak on the nozzle assembly or fuel line! Be careful it does not start a fire.

  • @GreenEarth140
    @GreenEarth140 6 місяців тому

    TRULY , a fantastic explanation about a zone valve. Excellent.

  • @dgmenace73
    @dgmenace73 6 місяців тому

    Thanks for the detailed video.....I just purchased some Beckett electrodes and they along with the old set have what looks like a butt connector to attach the length electrodes ends to match the others. The instructions don't say to crimp them or anything

    • @furnacetech2581
      @furnacetech2581 6 місяців тому

      I am not sure exactly what you are referring too. I know the electrodes come in many different designs. Most of the ones I run into, I cut to length or screw them together and then cut off excess. Some I am able to get the exact lengths. I know there is one type that I have come across that pushes together. I am sorry my reply is not much help!

    • @dgmenace73
      @dgmenace73 6 місяців тому

      @furnacetech2581 no apology necessary. I appreciate any advice. These electrodes have two lengths of rods that have a metal "coupler" that does push on but its very loose. I figure you're supposed to crimp them to make tighter? The old & new set both have the same "coupler". If this helps any, let me know your thoughts. Thanks

  • @akeyrecords5517
    @akeyrecords5517 6 місяців тому

    What spray were you using to clean it ?

    • @furnacetech2581
      @furnacetech2581 6 місяців тому

      Carburetor Cleaner works great to clean electrodes!

  • @christinemao9986
    @christinemao9986 6 місяців тому

    Thanks for this video! My problem is I cant not move that level freely and it seems like stuck in the middle while I can still feel the motor is hot. What do you think could cause the problem? Do I have to call the strata to replace the whole thing? Thanks

    • @furnacetech2581
      @furnacetech2581 6 місяців тому

      I would remove the powerhead off the valve body and check if the valve is stuck. If it’s stuck, then the internal valve parts need to be replaced. They sell rebuild kits. You can check this video’s description for a parts link if you have the ability to do it yourself!

    • @christinemao9986
      @christinemao9986 6 місяців тому

      Thanks!@@furnacetech2581

  • @TroyD-vo1bz
    @TroyD-vo1bz 6 місяців тому

    A question for you about bearing noise. I have a two-year-old furnace, and I'm hearing some pretty bad-bearing noise coming from around the fuel pump. At this point it's intermittent. I thought originally it was coming from the blower motor but upon closer examination, it's coming from around the Motor or the fuel pump. I'm assuming there are several bearings in and around the motor and fuel pump. Which do you think would be most likely to fail after just a couple of years? I've actually had furnaces 10 plus years old and never had bearing issues before, but this noise Is fairly loud and can be heard from 10 feet away.

    • @furnacetech2581
      @furnacetech2581 6 місяців тому

      I would remove the coupling between the blower and the fuel pump and test the blower motor. See if the noise goes away or not.

  • @watr77222
    @watr77222 6 місяців тому

    Hi, how would you suggest detecting location of heating pipe for baseboard water heater behind wall? Former owners severed the pipe in the boiler room for the basement. Thanks!

    • @furnacetech2581
      @furnacetech2581 6 місяців тому

      That’s a tough one! My best suggestion would be to start where the end of the baseboard run is located and work from there. You can cut small inspection holes to limit damages. I hope this helps

  • @michaelkatzenbach9478
    @michaelkatzenbach9478 6 місяців тому

    Are you adding a fill gauge

    • @furnacetech2581
      @furnacetech2581 6 місяців тому

      No, just fill cap, vent and supply line!

    • @michaelkatzenbach9478
      @michaelkatzenbach9478 6 місяців тому

      @@furnacetech2581I don’t understand the customer won’t know how much fuel is in the tank to order more fuel plus this tank is set on snow when the snow melts the tank will be off pitch. And don’t they have to dig that broken tank up and clean the spill. Are they filling that tank with kerosene or #1 fuel with temperature that low and lower. And with a bottom draw aren’t you going to draw moisture and sludge and possibly plugging the filter

  • @paulallen-01
    @paulallen-01 7 місяців тому

    I don’t miss these times of having to wear a mask in customer homes even though I always took mine off on e the customer left me alone in their boiler room. Anyway I stopped using pipe dope and know use Blue Monster anti-seize that’s rated for solvents and all fuels and I’ve had great success with it.

  • @bigpardner
    @bigpardner 7 місяців тому

    Does the higher voltage of the igniter improve combustion? Does it tax the ceramic insulation of the electrodes?

    • @furnacetech2581
      @furnacetech2581 7 місяців тому

      Stronger spark which help to ignite. The combustion is improved by adjust the fuel and air mixture using combustion tuning equipment. As for the electrodes, not 100% sure and every system is different because the controller may or may not turn off the spark after ignition had been established! I hope this helps!

  • @larchman4327
    @larchman4327 7 місяців тому

    My furnace quit today tried new filter. Ended up taking off b2va suntec pump and the pump shaft just came out of the pump thats not supposed to happen right. Any input appreciated.

    • @furnacetech2581
      @furnacetech2581 7 місяців тому

      Replace the pump and coupling together and you should be good to go!

    • @larchman4327
      @larchman4327 7 місяців тому

      @@furnacetech2581 OK will do. Gotta stay warm because fairbanks is a little cold in the winter.

  • @joecardenas8723
    @joecardenas8723 7 місяців тому

    Hi Mister Great video. I like to know what cause bleeding every 3 days? I replaced my single stage. Thank you

    • @furnacetech2581
      @furnacetech2581 7 місяців тому

      If you have a leak in the fuel line, it can cause the system to need bleeding after extended periods off time.

    • @joecardenas8723
      @joecardenas8723 7 місяців тому

      @furnacetech2581 I'll be check. Thank you so much

  • @minimule1
    @minimule1 8 місяців тому

    Hi there great video . I have a question because it getting cold and my furnace is not working. I have air comming out of the inlet filter on the side of the blow motor . Does this mean the motor is running backwards? The air is comming out of the filter where you adjust the air flow going into the burner head it that makes sense . My burner is a Beckett . I furnace runs but not well . I have changed everything from the control unit , nozzle,new igniter box. I thought the air was supposed to go into the burner head from the side where the adjuster ring goes. Should I change the direction of the blower motor ?

    • @furnacetech2581
      @furnacetech2581 8 місяців тому

      I have never seen one spin backwards. I wish I was there to see what you were talking about.

  • @kyledc6402
    @kyledc6402 8 місяців тому

    I'm curious if have 5 zones everything in 4 work fine the 5th is my garage it is always calling for heat even when the tstat is off. If the zone valve is set to auto but I'm curious if it is somehow stuck to open would that be why the zone is always calling for heat?

    • @furnacetech2581
      @furnacetech2581 8 місяців тому

      Yes, it could be stuck open for sure! If there is no power going to the zone valve, you can remove the powerhead and check it. The valve body stem could be stuck too so try rotating the stem too!

  • @willrise3980
    @willrise3980 8 місяців тому

    hi, is this installation is for heater only

    • @furnacetech2581
      @furnacetech2581 8 місяців тому

      yes, if you would like to hook up cooling or a fan, you would need to connect the (Y) & (G) wires to the tstat as well. I was only needing heating when i created this video.

    • @willrise3980
      @willrise3980 8 місяців тому

      @@furnacetech2581 can u make a video on how to connect heater and air conditionin

  • @TheDrewflav
    @TheDrewflav 8 місяців тому

    Did you have to drain whole boiler system line prior to cutting copper radiator??

    • @furnacetech2581
      @furnacetech2581 8 місяців тому

      No, I have isolation valves in each heating loop.

  • @jamesg5700
    @jamesg5700 8 місяців тому

    Very helpful video, thank you! Like another viewer, I now think I can fix my defective valve myself. ✅☺️

  • @joshfinkler6516
    @joshfinkler6516 8 місяців тому

    this video was PERFECT for helping me troubleshoot my honeywell zone valve problem, also gave me the confidence to do it myself. just got everything put together and tested and back to normal operations in plenty of time for winter. thanks for making this video!

  • @bigpardner
    @bigpardner 9 місяців тому

    It's been a couple years since I did this, but it would have been nice if they had put a note/warning with the pump that it was full of oil. Made a bit of a mess. I also had to put the pump in a vise and use a breaker bar to get the plug out for the fuel line. Made in France I recall. Has run like silk since putting the CleanCut pump with solenoid to replace the previous.

  • @Stacks2031
    @Stacks2031 9 місяців тому

    Great job if you don’t mind me asking how long did it take you to disassemble , clean and reassemble?

    • @furnacetech2581
      @furnacetech2581 9 місяців тому

      It varies based on how dirty the boiler is! Plus if you have all the supplies/parts organized while doing the service. Normally takes between 2hrs and 3.5hrs for me.

  • @andersonandrew112
    @andersonandrew112 9 місяців тому

    Are you in Anchorage? I have six of these at my apartment building, and I've had to have 14 motors replaced in 2 years. Either failure to open or failure to close. The plumber only hooks up the two yellow wires, leaves the red ones disconnected. Could that cause problems?

    • @furnacetech2581
      @furnacetech2581 6 місяців тому

      The red wires are used if the controls need to know when the valve is calling. I would check the valve body if it’s moving freely because if not, the motor may be working too hard and failing. I hope this helps! I am located in Fairbanks and North Pole!

  • @asiakevin
    @asiakevin 9 місяців тому

    Thank you

  • @jeffreyjohn2037
    @jeffreyjohn2037 9 місяців тому

    How many years of training does it take to be certified?

  • @elizabethabar2011
    @elizabethabar2011 9 місяців тому

    I need help with mine that looks like this! I’m so sick of hearing I need a whole new boiler system because no one can find this pump

    • @furnacetech2581
      @furnacetech2581 9 місяців тому

      Pumps are not too hard to find! Even a new system will need the correct sized pump. Do you have the pump model?

  • @HonestDiner-cz4op
    @HonestDiner-cz4op 10 місяців тому

    Could you have done that repair with a ProPress?

    • @furnacetech2581
      @furnacetech2581 10 місяців тому

      I don't see why not. I just don't use ProPress personally.

  • @JS-go1gu
    @JS-go1gu 10 місяців тому

    Satisfying!

  • @user-wf9cm1cb1p
    @user-wf9cm1cb1p Рік тому

    Why is it just for hot water could we not put this on a cold water system??

  • @zoots15
    @zoots15 Рік тому

    Does isolating the valve by turning off supply and return eliminate the system pressure when you pull off the old plate? Thanks for the video

    • @furnacetech2581
      @furnacetech2581 Рік тому

      Yes, if you isolate the supply and return lines, you can slowly loosen the old plate. Place a bag or something to catch the fluid. Take your time because it can have a bit of fluid trapped in the lines.

    • @zoots15
      @zoots15 Рік тому

      @@furnacetech2581 Much appreciated 👍

  • @iwktwom
    @iwktwom Рік тому

    As soon as I turn on the boiler there is a call for heat, even though the heating is off at the program box. The hot water works normally just the heating is messed up. Do u think just replacing the metal box would work to fix the heat so it could be called when needed?

    • @furnacetech2581
      @furnacetech2581 Рік тому

      The first thing I would check is the end switch. If the end switch is closed, then the boiler will get a signal to run the pump. Some boilers will turn on just to maintain minimum temp.

  • @gerardcianci582
    @gerardcianci582 Рік тому

    Is there a way I can get a stuck open valve manually closed until I get a new one?

    • @furnacetech2581
      @furnacetech2581 Рік тому

      Yes, there are a couple ways. Turn the thermostat off in that space, then remove the zone valve cover and take a screwdriver to see if you can move the linkage to free it. The spring should drive it closed. The other way is to turn off the thermostat in that zone and then close off one of the valves on that zone. I hope this helps!

  • @pulseharborwellness
    @pulseharborwellness Рік тому

    Great! very helpful

  • @johnc6157
    @johnc6157 Рік тому

    Very informative. Thank you.

  • @rene5313
    @rene5313 Рік тому

    Ive been having trouble with my bekett burner. Ive trouble shooted everything i could think of and cant figure out the issue. My blower fan is not kicking on when i turn on the heat switch. It will kinda of turn on but get stuck then it trips my breaker. Do you think it could possibly be the fuel pump? Or something electrical? When i trouble shoot the motor blower alone without being assembled it works normal but when i place it into the shaft it looks like it gets stuck. Id appreciate the help. Thanks!

    • @furnacetech2581
      @furnacetech2581 Рік тому

      You should be able to spin the fuel pump by hand. If you can, the blower motor may be going bad! That’s where I would start. I hope this helps!

    • @rene5313
      @rene5313 Рік тому

      @@furnacetech2581 figured out the problem the next day. It was the fuel pump. The shaft inside the fuel pump was stuck causing my motor blower to get stuck. I changed out the fuel pump and it started working like a champ! I appreciate your videos I've learned so much. Thanks

    • @furnacetech2581
      @furnacetech2581 Рік тому

      @@rene5313 That's Great news!

    • @anthonyrosario7841
      @anthonyrosario7841 5 місяців тому

      Hi I’m having issues with my oil burner. I keep getting smoke coming from the oil burner and the oil burner is leaking under. If you can give me an advise I will be so appreciate.

  • @rwpeter12
    @rwpeter12 Рік тому

    I have just replaced my Honeywell motor head. I must have an older style as there are no screws holding it to the valve body. It is only held on with a wire clip. The issue I’m having is that when the thermostat calls for heat the motor head comes disengaged and does not open the valve. If i put pressure on the motor head towards the valve body it will engage properly.

    • @furnacetech2581
      @furnacetech2581 Рік тому

      I am sorry for the late response. I would probably replace the zone valve unless you find another solution

  • @cahjavra
    @cahjavra Рік тому

    thank you !

  • @brett6328
    @brett6328 Рік тому

    Thank you! Sounds like I am having very similar symptoms. Only getting hot water when our other zone is running, so I guess it is stuck open and the manual switch is pretty loose. The boiler is not firing with this zone. The zone valve case seems warm too, not sure if that is normal. You mention the end switch originally but at the end you say it is the power head. What specifically did you end up replacing? Did you just go with the "Honeywell Zone Valve Repair Kit" that you linked to? And not the end switch or the motor?

    • @furnacetech2581
      @furnacetech2581 Рік тому

      I replaced the powerhead which includes the motor and end switch all in one.

    • @furnacetech2581
      @furnacetech2581 Рік тому

      Thank you for watching!

    • @brett6328
      @brett6328 Рік тому

      @@furnacetech2581 Thanks. Do you happen to have a link to what specifically you ordered?

  • @njboesman
    @njboesman Рік тому

    Very informative, getting the new unit seated with moving the lever was KEY....Thank You !

  • @alexnunez4019
    @alexnunez4019 Рік тому

    Great video. Thank you

  • @johnrmce
    @johnrmce Рік тому

    can i just remove and replace the whole pump or do i have to take it apart like a jigsaw puzzle ?

  • @spacefencer
    @spacefencer Рік тому

    Excellent! Real professional! Thank You! You work clean and orderly. Not many in the trade do.👍 Thanks again!

  • @dennissheese9378
    @dennissheese9378 Рік тому

    My furnace leaks at the end of the chip out there and making a mess what is your suggestion to fix it I have a Parkway furnace with the end of the ship that leaks Beckett furnace that leaks out by the chip I've replaced the tip and it's no good to it leaks

    • @furnacetech2581
      @furnacetech2581 Рік тому

      Did you get it fixed? If you are getting air into the fuel line, this can happen. Is the burner down stairs? I would check the fuel pressure going into the burner when it’s not running!