Fire Sprinkler Tech
Fire Sprinkler Tech
  • 77
  • 204 567
Replacing Sprinkler Heads
Replacing a few standard response sprinkler heads that are over 50 years old. It's cheaper to replace than test. NFPA 25 requires standard response heads to be sample tested or replaced after 50 years.
Tired of dealing with stacks of paperwork or fillable PDF forms after every inspection? Yeah, me too. That's why I'm partnering with Inspect Point to show you how it's making my job much easier - less paperwork, better reporting, and staying compliant is a breeze now. Book your demo here: engage.inspectpoint.com/firesprinklertech
Переглядів: 350

Відео

Relocating a CPVC Fire Sprinkler Pipe
Переглядів 7643 місяці тому
Had to move a couple heads on CPVC.
Replacing Sprinkler Head and the Drop Came Out
Переглядів 5653 місяці тому
Sometimes the entire drop will come out when you are replacing a head. This one was easy but sometimes the drop is long and the system is trapped with water making a big mess.
Replacing a Circulation Relief Valve
Переглядів 6384 місяці тому
I replaced a CRV that was not working correctly.
Follow up on the Service Call for a Tripped Dry System. (Part 2)
Переглядів 5864 місяці тому
This is part 2 of the "Walk With Me On A Service Call" video. I unclog the ITV and flush part of the system.
Hard to find leak on a dry system.
Переглядів 5764 місяці тому
This attic is not an easy one to climb around in. This system is 17 years old and has just started developing leaks. The cheapest route in the long run is to replace the sch.10 pipe with sch. 40. If the customer choses not to replace it, they will pay far more for repairs spread over time.
Walk with me on a service call for a dry valve tripped. (Part 1)
Переглядів 4374 місяці тому
Thought I would show you what we do on a service call.
Replacing a Clapper Gasket on a Reliable D Dry Valve
Переглядів 4834 місяці тому
In my opinion the Reliable Model D dry valve was the best dry valve ever made. They are typically easy to work on and have a simple design. Unfortunately on the earlier models, the clapper pin could be difficult to remove. Later they added a hole on the back with a plug so you could drive the pin out.
Main Drain Test Fail
Переглядів 8584 місяці тому
Three separate system had water supply issues found during the inspection.
Water Pipes Freeze
Переглядів 4394 місяці тому
Here are a few of the freeze ups for the winter of 2023
Replacing an air compressor in a tight space
Переглядів 3304 місяці тому
Replacing an air compressor in a tight space
Searching for air leaks using Accutrak Ultrasonic Leak Detector
Переглядів 3975 місяців тому
Searching for air leaks using Accutrak Ultrasonic Leak Detector
Nitrogen Generator Troubleshooting
Переглядів 9616 місяців тому
Nitrogen Generator Troubleshooting
AccuTrak Ultrasonic Leak Detector to find air leaks
Переглядів 1,2 тис.6 місяців тому
AccuTrak Ultrasonic Leak Detector to find air leaks
Replacing Alarm Line Trim on a Reliable Model D Dry Valve
Переглядів 8086 місяців тому
Replacing Alarm Line Trim on a Reliable Model D Dry Valve
Partial Trip Test Victaulic 768 Dry Fire Sprinkler Valve
Переглядів 2,1 тис.6 місяців тому
Partial Trip Test Victaulic 768 Dry Fire Sprinkler Valve
Repairing 8" Cast Iron Underground Pipe
Переглядів 1,5 тис.6 місяців тому
Repairing 8" Cast Iron Underground Pipe
False Alarms Caused by Ames 4000 SS Vertical RPZ Backflow Preventer
Переглядів 4397 місяців тому
False Alarms Caused by Ames 4000 SS Vertical RPZ Backflow Preventer
Fire Department Connection Hydrostatic Test
Переглядів 3,2 тис.7 місяців тому
Fire Department Connection Hydrostatic Test
NFPA 25 Internal Pipe Assessment
Переглядів 1,1 тис.7 місяців тому
NFPA 25 Internal Pipe Assessment
NFPA 13R Water Tank and Fire Pump Setup
Переглядів 1,2 тис.7 місяців тому
NFPA 13R Water Tank and Fire Pump Setup
Replacing Leaking Sch 40 pipe
Переглядів 8 тис.7 місяців тому
Replacing Leaking Sch 40 pipe
Troubleshooting an air compressor not working on a pre-action system
Переглядів 1,3 тис.7 місяців тому
Troubleshooting an air compressor not working on a pre-action system
Adding a 2' Fire Hydrant Extension
Переглядів 2,3 тис.7 місяців тому
Adding a 2' Fire Hydrant Extension
Replacing a Fire Hydrant
Переглядів 6 тис.7 місяців тому
Replacing a Fire Hydrant
Installing a General Air Riser Mount Air Compressor and Replacing a Control Valve
Переглядів 7178 місяців тому
Installing a General Air Riser Mount Air Compressor and Replacing a Control Valve
Fire Department Connection Full of Debris.
Переглядів 1,9 тис.8 місяців тому
Fire Department Connection Full of Debris.
Aircraft Hanger High Expansion Foam System Test
Переглядів 9458 місяців тому
Aircraft Hanger High Expansion Foam System Test
Troubleshooting Victaulic 756 Dry Fire Sprinkler Valve
Переглядів 1,9 тис.8 місяців тому
Troubleshooting Victaulic 756 Dry Fire Sprinkler Valve
Using Ridged 915 Groover on 4" Fire Sprinkler Pipe
Переглядів 1,1 тис.8 місяців тому
Using Ridged 915 Groover on 4" Fire Sprinkler Pipe

КОМЕНТАРІ

  • @luisva._to114
    @luisva._to114 16 годин тому

    Un curso porfavor

  • @sammydavis3796
    @sammydavis3796 День тому

    I thought your supposed to flip the check valve and test against the check valve

  • @jameschuke4104
    @jameschuke4104 3 дні тому

    Obviously your unit is about wore out hi amps n capacitor all old the generator people should of put that on there when installed

  • @luisva._to114
    @luisva._to114 5 днів тому

    Puedes!! subtitularlo en español

  • @brettlaplaunte9028
    @brettlaplaunte9028 6 днів тому

    is that the proper head wrench ;)

  • @FireSprinklerTech
    @FireSprinklerTech 6 днів тому

    I put a link in the description if you want to learn more about Inspect Point. Thanks for watching!

  • @JohnSebeny
    @JohnSebeny 6 днів тому

    Nice video Doc!

  • @InspectPoint
    @InspectPoint 6 днів тому

    That's some intuitive software you're using 😏

    • @quinkelley1134
      @quinkelley1134 6 днів тому

      Can't wait for my company to make the switch, pen and paper is getting old!

    • @InspectPoint
      @InspectPoint 5 днів тому

      @@quinkelley1134 Hang in there, we feel your pain. Tell your company we're ready when they are 💪

  • @dannyspiker1549
    @dannyspiker1549 6 днів тому

    😊👍🏻

  • @mohieldeen9140
    @mohieldeen9140 17 днів тому

    good

  • @dianenelson5179
    @dianenelson5179 18 днів тому

    Absolutely love your content...keep up the good work, learning a bunch..

  • @sabianfirst
    @sabianfirst 20 днів тому

    Good install. I've had one for a couple years that I installed on a 4-ton Goodman. Installation instructions were very straightforward. Tested with my Duromax 13000 EH (10,500) portable generator and it works very well. Using a portable for whole-house is another topic. Micro-Aire does have excellent customer support through Hutch Mountain if you have any questions regarding install for your particular unit, and although the app seems limited (connection and live data only accessible during call for cooling), if you send diagnostic data they are right on it. I also enjoyed the screw drop response; happens to the best of us. You did everything right (for a fire sprinkler tech haha. Don't be so hard on yourself). Good call with the cap discharge and terminal cleaning. For everyone reading, you need to purchase a replacement capacitor. I have replaced mine (and a backup) and it is very easy, cheap, and they DO fail (probably the first component to fail). If you are doing this install, just go ahead and replace your Start/Run cap at the same time. I noticed that you have an outdoor home surface that prevents this, but as a side note if some of you have siding/framework to attach the EasyStart to on the house, this might be better for at least three reasons: 1. vibration from the condenser unit 2. if you need to replace your condenser, this EasyStart is not attached to it (OOPS! forgot about that soft-start). Just need to run some seal-tite and possibly extra conductors from the condenser panel to the wall where the unit is attached. For me, the included cord was run through seal-tite and the conductors were plenty long enough. 3. you can view the indicator lights on the unit in case of fault through the clear plastic cover that is attached to the wall, rather than hidden. This may be helpful for some in case there is an issue. This case is waterproof (do not open), and it really will not be better protected whilst trying to fit it into the electrical enclosure for your condenser. And that can be a pain in the butt all by itself. Not necessary to fit this large unit on the condenser itself, as long as you ensure waterproof conductor installation. Another side note for those with older condenser compressors with suspect terminals at the pecker (S, R, C), I used a kit that works very well for this purpose, and I recommend it. Also requires good cleaning of what's left of your terminals if they are degraded. Hope this helps some: www.amazon.com/gp/product/B07TFK4587/ref=ppx_yo_dt_b_search_asin_title?ie=UTF8&psc=1 Also, always clean your condenser coils by shield disassembly and regular hose pressure from inside out once a year!

  • @jeremyg8568
    @jeremyg8568 27 днів тому

    Likely the highest area for a potential fire so you don't flood the whole building in the event of a more likely fire.

  • @VirtualAdvocate
    @VirtualAdvocate 28 днів тому

    isn't that a redundant system? If the other sprinklers fail this will still work?

  • @redstonebrain40
    @redstonebrain40 28 днів тому

    Nows time to run a hose off that, overhead gerbal feeder water tube

  • @chrismehl1607
    @chrismehl1607 28 днів тому

    Wires touching the metal pipe wouldn't pass in my area.

  • @vseanw
    @vseanw 28 днів тому

    Probably has to do with whats directly under it and them initially not wanting it wet unless the building is hit by a plane

  • @tartredarrow
    @tartredarrow 28 днів тому

    They were under strict instructions not to bring back extra material.

  • @BlackMercFPS
    @BlackMercFPS 28 днів тому

    Past Chemical shower area?

    • @gunnerschwieterman6383
      @gunnerschwieterman6383 28 днів тому

      Yeah in a post office you know when they have to handle those nasty boxes😂😂

  • @DuckEDeluxe
    @DuckEDeluxe 28 днів тому

    Thank you for making this 💯

  • @Fredengle
    @Fredengle Місяць тому

    Hi I got a question maybe you can answer as you know anti freeze is frowned upon in newi stallion and instead the advice given is dry pipe my question to you is I. Know a hose can be attached to a sprinkler system I was wondering do you know if it's ever been done to connect a fire hose to a dry pipe sprinkler or pre action riser?

    • @FireSprinklerTech
      @FireSprinklerTech Місяць тому

      Yes, some standpipes are supplied by a dry pipe valve.

    • @Fredengle
      @Fredengle 29 днів тому

      ​@@FireSprinklerTechthank you my new question is could it some how be connected to to a pre-action system ?

    • @FireSprinklerTech
      @FireSprinklerTech 29 днів тому

      @@Fredengle Sorry, can’t help you there. I am a sprinkler fitter and we don’t do alarm work.

  • @fitter5423
    @fitter5423 Місяць тому

    Sound like they maybe had some issues with potentially breaking that head in the past. No flow switch or drain lol. Not considered a system. If you had to shut one head off you’re getting very wet.

  • @barrymurray8264
    @barrymurray8264 Місяць тому

    Thanks ! Helped a lot !

  • @alexduffy8723
    @alexduffy8723 Місяць тому

    Or the sprinkler main pipe to building is completely filled with sediment. Can cause water to slowly fill the system but it won't fill quickly. Seen once.

  • @hlhl5962
    @hlhl5962 Місяць тому

    very very detailed, practical and helpful video.

  • @Elitecataphract
    @Elitecataphract Місяць тому

    As a civil engineer, I love these videos with detailed explanations and real-world examples of how this stuff comes together. Too many of us are stuck looking at drawings and specifications, but everything makes much more sense when you can see it actually come together.

  • @JohnSebeny
    @JohnSebeny Місяць тому

    This looks familiar :)

  • @TheCLOGDAWGPlumbing
    @TheCLOGDAWGPlumbing Місяць тому

    with 2 men how long would you say it takes to complete one?

    • @FireSprinklerTech
      @FireSprinklerTech Місяць тому

      It all depends on the situation. If you have a good operator doing the excavating and you’re not too deep, don’t have anything in your way, you can do it in about 4 hours. However, I would never plan on that. You could get in a situation where you have to pour a thrust block back. Now you’re talking all day and a return trip after the concrete sets. I would figure all day and exclude pouring a thrust block if you are giving them a price.

    • @TheCLOGDAWGPlumbing
      @TheCLOGDAWGPlumbing Місяць тому

      @@FireSprinklerTech what would you quote one at?

    • @FireSprinklerTech
      @FireSprinklerTech Місяць тому

      @@TheCLOGDAWGPlumbing I don’t do the quotes, don’t really know the cost.

  • @KennyMFJones
    @KennyMFJones 2 місяці тому

    How would you pump against a storz cap? Or pump into a storz cap. I have to hydro test an FDC that has a storz. I wanted to disconnect the pipe from the FDC check valve WITHOUT draining the system. Then put a drain cap on the pipe and pump against the storz cap. Will the storz cap hold pressure or does it leak?

    • @KennyMFJones
      @KennyMFJones 2 місяці тому

      Reason for not wanting to drain the system. It’s at a mall with anti freeze loops everywhere and there is a total of 15 FDC’s to test.

    • @FireSprinklerTech
      @FireSprinklerTech 2 місяці тому

      I have tested against the cap. Some don’t seal. I have a storz x 2.5” hose connection I use.

  • @richardashworth400
    @richardashworth400 2 місяці тому

    Great video. Nice simple explanation on how the valve works. A question if I may? I'm trying to troubleshoot a false "system charged" water flow alarm that occured on a 769 NXT valve.What could be the possible reasons that the water flow alarm would trip when the system itself has not tripped? Air pressure in the system is above 20 psi, all valves are in the correct positions etc. I did notice a tiny water leak on the low pressure actuator via the vent valve, but unsure if this could be the cause. I've charged the system with the test valve, and then discharged again afterwards via the PRV under the alarm pressure switch, but can't get the alarm to clear. Driving me nuts. I've visibly aged in the last 24 hours.

    • @FireSprinklerTech
      @FireSprinklerTech 2 місяці тому

      Is this a pre-action system? I ask because the I think the 769 is designed for pre-action or deluge. Just want to make sure you didn't mean 768 NXT

    • @FireSprinklerTech
      @FireSprinklerTech 2 місяці тому

      When you say discharged via the PRV, are you referring to the manual ball drip also called a velocity check? If you don't have any water pressure on the velocity check and it is still in alarm, I would slowly remove the velocity check to confirm it isn't stuck or plugged. If the trim is clear and you are still in alarm then open the pressure switch and check the state of the switch. If the switch is active indicating a water flow then you might have a bad switch. If the switch is not active then it's an alarm system issue.

  • @sharonzelikovich4381
    @sharonzelikovich4381 2 місяці тому

    Its call obstruction investigation my friend.

  • @sharonzelikovich4381
    @sharonzelikovich4381 2 місяці тому

    When the pump on zero flow shut down the primary source of the power does not activate the secondary power source / generator? why did you need to get inside the settings of the transfer switch?

  • @jonathanlee6444
    @jonathanlee6444 2 місяці тому

    are there any downsides to using this micro air soft start?

  • @ronfranz7578
    @ronfranz7578 2 місяці тому

    Nice video.. with doing the five (5) year there could be many different scenarios as to accessibility to get at the check. Also what type of check valve. Learned in this business you have to CYA and also take pictures. In the fire protection industry many people don't want to spend money on something that they can't see. Then you also have contractors out there that are pipe bangers or do their inspections in the car yet there are still some honest people out there. From experience its always advisable to keep extra new couplings, a spare check, 2.5" rubber gaskets for the ones that are rotted out on the FDC.

  • @fattysgarage1754
    @fattysgarage1754 3 місяці тому

    Best thing I ever installed. I installed right before hurricane Ian in 2022 and was able to run whole house 3 ton unit. My advice would be to change capacitor and contactor while you are in there and you will be good for many years. This saves your unit from pre mature failures and the A/C companies hate it. Nice video!

    • @jdwilson-ig7uj
      @jdwilson-ig7uj 21 день тому

      This is exactly what I did this past weekend. The HVAC system is about 12 years old and I also have a backup generator. Having tested the A/C on generator last year, the current draw is w/in limits of the gen set, but you can hear the RPM is pulled down on startup. Ordered the soft-start and also updated the contactor (per AS/Trane). Replaced the capacitor with the appropriate size one from AmRad (through an Amazon market place dealer). Installed the replacement parts first to make sure it's all running then installed the soft start kit. In-rush current dropped (after initialization process) from ~81A to ~24A. Runs very quiet too. Also while I had it opened up, washed down the coils. It's expensive, but I think it will really pay off in the long-run with the life of the compressor and when on backup power.

  • @juanesquivel5990
    @juanesquivel5990 3 місяці тому

    Learned a lot, thank you very much Sir.

  • @ryangardner9683
    @ryangardner9683 3 місяці тому

    U need a helper

  • @jaygdad
    @jaygdad 3 місяці тому

    Thanks from Boston. I need this in my arsenal.

  • @nathanielchavez2978
    @nathanielchavez2978 3 місяці тому

    One thing I’m not understanding is I know a main control valve shuts water to either sections or the entire standpipe system. What I’m not understanding is sometimes I will go past normal control valves that have a tamper and a flow switch and a inspectors test, but sometimes they will have “main control” by the tamper. I don’t get how a tamper could be a main control to shit off water to standpipe? Is there something in missing? (This is for a dry system by the way)

  • @blkinvestor
    @blkinvestor 3 місяці тому

    What tool can I buy to remove it and what’s the best brand to replace white in color ?

    • @FireSprinklerTech
      @FireSprinklerTech 3 місяці тому

      You need to contact a fire sprinkler contractor. Sprinkler heads come in different sizes, temperatures, spray patterns, orientations, K-factors, etc… This channel is not intended to be a DIY channel. It is to help other sprinkler fitters. It’s not uncommon for us to come in and find critical problems because someone tried to work on their fire sprinkler system. Often times costing them a lot to repair.

  • @PaulAdame-jq3uv
    @PaulAdame-jq3uv 3 місяці тому

    How frequently should the compressor be going off? We have a compressor on our system that has started to run every 30 minutes for about 30-60 seconds in one building.

    • @FireSprinklerTech
      @FireSprinklerTech 3 місяці тому

      More than likely you have a small leak starting to develop. They can be very difficult to find when they are small like that.

  • @alanmiller6061
    @alanmiller6061 3 місяці тому

    What’s the average price you would charge for a new hydrant installation? And I’m in Illinois basically Chicago. We also put auxiliary valves with every hydrant.

  • @fitter5423
    @fitter5423 3 місяці тому

    I remember when them torque safe reducers were brand new. We did a brand new 14 story building using those. The painters, finishers and carpenters damaged about 900 pendants and sidewalls by either painting the head, covered the head in mud or damaged the head with the drywall. We went back to change them I’d say about 10% of the heads wouldn’t come out. They just kept spinning inside that brass piece in the fitting. We had to cut holes in the walls and ceilings to be able to hold back to get the head out.

    • @FireSprinklerTech
      @FireSprinklerTech 3 місяці тому

      That's interesting, I haven't ran into that. They make a wrench to use as a hold back. Extremely overpriced, but it would save you from cutting out the ceiling. parts.spearsmfg.com/sourcebook/FLAMEGUARD_FG-1_SHRK.pdf

  • @FireSprinklerTech
    @FireSprinklerTech 3 місяці тому

    Please like and subscribe to help the channel grow. Feel free to leave a comment. I would like your input so I can improve the channel. Thanks for watching!

  • @gallihyde
    @gallihyde 3 місяці тому

    Lmao i always make my guys stuff a hoodie in the barrel so they dont drop the pjn like you did hahahaa

  • @kpj9028
    @kpj9028 3 місяці тому

    Well that amd in the case that they water mains do fail. At least you aren't finding out in an emergency.

  • @erikbrantner4295
    @erikbrantner4295 3 місяці тому

    Are the all-thread rodes stainless steel composition? Otherwise would rust out over time creating a stress point up against the TEE joint

    • @FireSprinklerTech
      @FireSprinklerTech 3 місяці тому

      Zink coated ATR and we spray them with a protective coating.

    • @erikbrantner4295
      @erikbrantner4295 3 місяці тому

      @@FireSprinklerTech 👍👍 Looks like back in the day on those old hydrants certainly wasn't the case!

  • @erikbrantner4295
    @erikbrantner4295 3 місяці тому

    Weep hole looks to be only 1/8"to 1/4"... Why isn't it larger to allow water to escape from the barrel faster???

    • @FireSprinklerTech
      @FireSprinklerTech 3 місяці тому

      That's a pretty standard size. I believe NFPA requires it to drain within 60 minutes.

    • @erikbrantner4295
      @erikbrantner4295 3 місяці тому

      @@FireSprinklerTech gotcha 👍👍