Carrier RTU No Heat Internal Control Fault

Поділитися
Вставка
  • Опубліковано 6 бер 2021
  • Carrier RTU No Heat Internal Control Fault. simple and easy service call on a cold day. Hit SUBSCRIBE!
    hughesmanhvac@gmail.com
  • Навчання та стиль

КОМЕНТАРІ • 41

  • @zekenzy6486
    @zekenzy6486 2 місяці тому

    Great Video. Thank you for sharing

  • @NewEnglandReptile
    @NewEnglandReptile Рік тому

    Thank you !!!

  • @gregbowman3598
    @gregbowman3598 3 роки тому +1

    Good one Ryan 👍

  • @joerostkowski7313
    @joerostkowski7313 2 роки тому +1

    Heads up, 2 stage gas valves on carrier rtu have been failing alot lately 😕 midwest at least

  • @RichGT350r
    @RichGT350r 3 роки тому +1

    That’s a cold one brother! Thanks for sharing! 👍

    • @HughesManHVAC
      @HughesManHVAC  3 роки тому

      Thanks for watching Rich

    • @RichGT350r
      @RichGT350r 3 роки тому +1

      @@HughesManHVAC No worries Brother! I subbed as well, so I’m catching up on your videos! 👍

  • @EverythingHVACR
    @EverythingHVACR 3 роки тому +1

    Nice job man! Those retaining plates always go first.

    • @HughesManHVAC
      @HughesManHVAC  3 роки тому +1

      Thanks! Even new units start to get crispy after a year.

  • @forlast5231
    @forlast5231 5 місяців тому

    Check airflow. Some customers shut vents off in the building.

  • @tedpert8786
    @tedpert8786 2 роки тому +1

    Great video buddy keep up the good work!

  • @jonnymac31
    @jonnymac31 3 роки тому +1

    Sweet

  • @bobberger918
    @bobberger918 3 роки тому +1

    Good idea to change p.s. and sensor with board low cost

  • @Brutis-1983
    @Brutis-1983 3 роки тому +1

    Hate when guy are too lazy to clean up their mess. Had a Carrier do the same thing with internal control fault. Replaced board. Day later same thing. Thinking bad board . Talked a guy at Mingledoffs , we buy Carrier units from them. Turned out the Effect switch was going pad. Showed me best way to check them. Glad I don’t have to work in the cold and snow much. Enjoy your videos.

    • @HughesManHVAC
      @HughesManHVAC  3 роки тому +1

      Awesome man! It just worked after I reset it. I'm gonna look into that for sure

    • @Jeff-Lawrence
      @Jeff-Lawrence 3 роки тому +1

      Curious, what’s an effect switch

    • @HughesManHVAC
      @HughesManHVAC  3 роки тому +2

      Proving switch on combustion blower

    • @evasmechanical3902
      @evasmechanical3902 2 роки тому

      Brutish how do you check that effect switch?

    • @Brutis-1983
      @Brutis-1983 2 роки тому +1

      With power on unit with no call for heat unplug Hall effect switch. With your meter on DC scale. Connect negative lead to pin 3 and positive lead to pin one should read 7.5-10 volts DC. Move positive lead to pin two. Should read 21-24 volts. If not bad board.
      With plug plugged in connect negative lead to pin three and positive lead to pin one. Slowly rotate draft motor. On half a turn should read less than one volt DC. OTHER half of turn should read 6.5-9 volts DC. Then move positive lead to pin two. Should read 16.5-21 volts DC. If not replace Hall switch. Hope this helps

  • @clintglasgow5633
    @clintglasgow5633 3 роки тому +1

    👍

  • @tedhicks5431
    @tedhicks5431 Рік тому +1

    We have 2 identical units big 16s code 8 wouldn't reset after several trys replace LGC board like book said still code error 8 whats up anyone

  • @kenbassett5942
    @kenbassett5942 3 роки тому +3

    Not only faulty hall sensor but a faulty gas valve causes 8 flashes. Most times it’s stage 2, pink wire on valve. Should have jumped W2.

    • @HughesManHVAC
      @HughesManHVAC  3 роки тому +2

      Good advice 👍 thanks

    • @dn82180
      @dn82180 2 роки тому

      Just saw this and tech support said to change the gas valve. So far so good but it also worked for a few days after I changed the board. Also told me about the combustion fan. Said if you block the exhaust and it fires its the combustion motor hall effect sensor. He says the gas valve has a bridge rectifier in it that goes bad and it disables the board with 8 flash code. For something that appears to diagnose itself these are some pretty funky ways of failing. He says a lot of companies will just change the board, comb motor, and gas valve to ensure it's fixed.

  • @syedbasheer8210
    @syedbasheer8210 3 роки тому +1

    💫💫💫

  • @turbolag98
    @turbolag98 7 місяців тому +1

    I’ve come across 2 GrandAire RTU’s new installs throwing different error codes like internal control fault, pressure switch fault, high limit fault, rollout fault. What’s going on? Anyone have experience

  • @sknight0391
    @sknight0391 3 роки тому +2

    Intrnal lockout board code fault applejack cinnamon toast. That's definitely a bad canooter valve. Write it up 😎👍

    • @HughesManHVAC
      @HughesManHVAC  3 роки тому

      Lol, you want to do a livestream with me sometime? I think I would be hilarious 🤣

    • @sknight0391
      @sknight0391 3 роки тому +1

      @@HughesManHVAC I'll think about it.

  • @user-jr1ti7cx8b
    @user-jr1ti7cx8b 7 місяців тому

    Mine only has one contactor and reading 8 flashes

  • @steveblake8766
    @steveblake8766 3 роки тому +1

    #122 thumbs uP

  • @5822huron
    @5822huron 2 роки тому +1

    Get the heated gloves man

  • @angrycollector7012
    @angrycollector7012 2 роки тому +1

    I had a new board give me that control fault

  • @emmanuelleonruiz8697
    @emmanuelleonruiz8697 2 місяці тому

    6 flasing code please