York Ymc2 Chillers Shutdown Shortly After Scheduled Start Time… Tripped Main.. No Display VFD

Поділитися
Вставка
  • Опубліковано 21 кві 2024
  • Was contacted early in the morning prior to shift start by a coworker that the chillers abruptly stopped after starting, no pumps or chillers running, no display on vfd’s and a main breaker tripped…Priority work order generated and Here’s how we responded #chiller #york #hvac
  • Навчання та стиль

КОМЕНТАРІ • 62

  • @Ericbakereb1
    @Ericbakereb1 3 місяці тому +9

    Crazy that motor didn't show short when you two tested at the disconnect at the motor. Thanks for the video.

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +6

      I know, I was expecting to find one grounded. Better the pump motor than a tower motor 🫡

    • @Byron88
      @Byron88 3 місяці тому +7

      It's surprisingly common, after it blows the arc usually breaks the short, but its so close to being grounded as soon as you apply voltage again it arcs again, as you saw after the megger showed 0Mohm at almost 0 volts, the fault would have showed up right away with a megger vs a standard ohmmeter

    • @craiglewis8272
      @craiglewis8272 3 місяці тому +2

      @@Byron88yeah. That’s why I don’t like using a standard meter when checking for grounded motor

  • @ShaunPuzon
    @ShaunPuzon 3 місяці тому +5

    Your editing work is on point, sir! Yet another great video!

  • @mxslick50
    @mxslick50 3 місяці тому +15

    You should probably replace the contacts in that starter, closing into a short (and it opening on the original fault) would have pitted the contacts pretty bad. At the least, do a voltage drop measurement across all three contacts when you get the new motor running. Any voltage greater than about 2v across those contacts means they are bad.

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +4

      Definitely 👍

    • @dgapp76
      @dgapp76 3 місяці тому +1

      Agreed

    • @SupraTompan
      @SupraTompan 3 місяці тому +1

      You simply measure voltage before and after contacts?
      I would not have thought about this.

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +1

      Measure volt across contacts while energized, Thermal camera will also help determine if excessive heat is being generated in any contacts. 0 drop is 👍

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 3 місяці тому +5

    Yeah buddy....she gave up the ghost in style. Let the magic smike out....kinda lost opportunity for your helper to have gathered it back up in a bucket...😂😂😂😂....that smoke is valuable.....im just playing around. Great video as always

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +5

      Oh yeah, nothing like some bbq first thing in the morning. At least the apprentice got to see his first motor smoke release 😁Thanks Jason 👍

  • @littleprincess4417
    @littleprincess4417 3 місяці тому +3

    We once had a wire on a 277 volt 20 amp lighting circuit bypass not only the 20 amp breaker, but also the 225 amp breaker in the distribution panel and go back and get a 800 amp breaker in the MDP.

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +1

      That’s a strong willed wire 😃 Thanks for sharing

  • @ayoutubewatcher7009
    @ayoutubewatcher7009 3 місяці тому +2

    I miss working on the larger tonnage equipment, but not really.

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +1

      I hear you 👍 Thanks for watching!

  • @dgapp76
    @dgapp76 3 місяці тому +9

    I was told by an old AC duffer years ago to make sure you keep the smoke in. 😅

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +4

      Yep, I heard that too 😃

    • @TheChillerGuys
      @TheChillerGuys 3 місяці тому +2

      It’s so hard to put it back in after you let it out too… 😅

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +3

      Expensive too

  • @thesilentonevictor
    @thesilentonevictor 15 днів тому

    Good learning curve

    • @subcoolHVAC
      @subcoolHVAC  15 днів тому

      Always something to learn 👍

  • @plushdragon
    @plushdragon 3 місяці тому +7

    where someone with a paper bag to go boom when you reset the mains

  • @BOBKB3NZX
    @BOBKB3NZX 3 місяці тому +4

    I've noticed on higher current application that breakers meant to trip before a main will get stuck and not trip when they're supposed to. Maybe a quarterly exercise of them may alleviate that

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +2

      Thanks for the suggestion 👍

    • @ickipoo
      @ickipoo 3 місяці тому +3

      I think the issue is simply the peak fault current, which every breaker in series will see simultaneously. A sudden hard fault will have a high enough current to trip upstream breakers. In some applications, some series resistance or inductance is required to limit fault currents to manageable levels - breakers are only rated to break a certain fault current.

    • @mrfrenzy.
      @mrfrenzy. 3 місяці тому +1

      The main breaker should be programmed to prevent this, I would have a good electrician check the calculations and programming.

  • @MariMuthu-ck5ih
    @MariMuthu-ck5ih 3 місяці тому +2

    Good job 👍👍

  • @JW-qp5uf
    @JW-qp5uf 3 місяці тому +3

    Why are the chillers run in series? Are the temps higher on chiller 1 going into 2? Thanks for the video.

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +2

      There’s only 1 chilled water pump on this chiller plant, yes chiller 1 receives the warmer return water from the loop then passes through chiller 2 . Thanks for the question 👍

  • @fellpower
    @fellpower 3 місяці тому +1

    For a fast check, u can measure the resistance of the motors, but if u want to make it right, u should measure with an insulation tester, because it can be moisture on a broken cable / motor or something like that. with an insulation tester - u can find that

  • @djcode4714
    @djcode4714 3 місяці тому +6

    yay. another one
    bites them dust!

  • @LilyRoseElectric
    @LilyRoseElectric 3 місяці тому +1

    Great job 👏

  • @stevencossaboon3237
    @stevencossaboon3237 3 місяці тому +1

    Nice work Subcool.

  • @TheChillerGuys
    @TheChillerGuys 3 місяці тому +1

    Awesome stuff man!

  • @zekenzy6486
    @zekenzy6486 3 місяці тому +2

    Great Video. Good Job and Nice Work. Thank you for sharing. Is that motor pump short to ground is that why's chillers was tripped Main breaker ? Please. Could we have part 2 replace motor pump ^_^

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +2

      Yes, motor shorted to ground. Thanks for the question. Part 2 is possible 👍

  • @rock7282
    @rock7282 3 місяці тому +1

    Time to go with a new generation Baldor motor

  • @guygfm4243
    @guygfm4243 3 місяці тому

    Thanks for sharing

  • @user-ge5le4ku6j
    @user-ge5le4ku6j 3 місяці тому +1

    why no disconnect at the motor?

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +2

      There are disconnects 👍

    • @mxslick50
      @mxslick50 3 місяці тому

      Try watching the whole video.....

  • @Cinncinnatus
    @Cinncinnatus 3 місяці тому +1

    if you check to ground you should first check from ground to ground to make sure you actually getting a proper probe contact. 3:45
    Not saying something done totally wrong either just as you shown in the video earlier probe contact isnt always perfect so should be teaching them to get into the habit of making sure the ground is being read properly first.

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +3

      It’s more likely the initial short to ground cleared and when power applied it arced to ground again. Thanks for commenting

    • @Cinncinnatus
      @Cinncinnatus 3 місяці тому +1

      @@subcoolHVAC oh I wasn't referring to the cause nor am I implying it was overlooked/missed. Just saying you skip teaching a crucial step when checking for shorts to ground.
      Should always test first from ground to ground then test your lines/loads. If you just take your probe to a ground then use the other and start looking for shorts you assume to know that your grounded probe has proper contact.

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +2

      Thanks for watching

  • @brent562
    @brent562 3 місяці тому +2

    How much a motor like that cost?

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +1

      Somewhere between $4k-$5k depending on availability , I don’t do the purchasing though. Thanks 👍

  • @anthonybush3134
    @anthonybush3134 3 місяці тому +1

    What are you going to do with that impeller from the old pump?

    • @subcoolHVAC
      @subcoolHVAC  3 місяці тому +2

      The pump was removed to replace bearings and seals

  • @lilpbass
    @lilpbass 3 місяці тому +2

    I got some magic smoke I can sell you 😂