  • Met up with JCI tech to service our YMC2 chillers that have been surging and Loss of Subcooler Liquid Seal warning resolved #york #chiller #hvac

КОМЕНТАРІ • 15

  • @springws14lbss
    @springws14lbss 2 місяці тому +7

    Sounded like the Titanic engine room at the start!

  • @TBJK07Jeep
    @TBJK07Jeep 2 місяці тому +1

    Loss of subcooler seal is when your drop leg temp gets lower than your condenser temp. It basically is calculating that there is flash gas instead of a full liquid seal. Also on your drive heat exchanger, pull both heads when brushing it. One side may look ok, but when you pull the other, it will look like shit. It’s more work, but in the end its better.

  • @zekenzy6486
    @zekenzy6486 2 місяці тому +1

    Great video. Thank you for sharing. Those are big chiller

  • @thesilentonevictor
    @thesilentonevictor 2 місяці тому +4

    That sound at the start had wondering what the issue i was saying must be surging lol

    • @subcoolHVAC
      @subcoolHVAC  2 місяці тому +1

      Yep, with high pitch tap from check valve.

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 2 місяці тому +1

    Cool video. Glad to see they raised the liquid level....60% seems a tad high, but i get it. During start up, it seems like they always set it to 35%-37%. We do the maintenance and repairs on our customers YK's. Did they clean the heat exchanger for the VSD coolant. That can get pretty nasty over time. A lot of people wait till they get high temp alarms before doing it though. Enjoyed the video...thanks for sharing

    • @subcoolHVAC
      @subcoolHVAC  2 місяці тому +2

      Yeah, it ran better at 42% but JCI tech settled on 50% , they backwashed the exchanger, I did see some high motor baseplate alarms in the history after they left… probably from air. The old coolant was dark . Thanks Jason! 👊

    • @jasonjohnsonHVAC
      @jasonjohnsonHVAC 2 місяці тому +1

      @@subcoolHVAC 42% seems to be the sweet spot here.

  • @Ericbakereb1
    @Ericbakereb1 2 місяці тому +1

    Thought you were in a factory or so.ething at first lol.

    • @subcoolHVAC
      @subcoolHVAC  2 місяці тому +1

      🤣 yep, it was definitely an unexpected kind of surge

  • @dragonstorm9968
    @dragonstorm9968 2 місяці тому +1

    Sounds like that there is the EMERGENCY STOP BUTTON FOR to immediately stop a machine.

    • @subcoolHVAC
      @subcoolHVAC  2 місяці тому +2

      That’s the last button to push