TXV TROUBLE, ICE ON EVAPORATOR, HOW TO ADJUST THE TXV?

Поділитися
Вставка
  • Опубліковано 25 гру 2024

КОМЕНТАРІ • 158

  • @davidmears9410
    @davidmears9410 2 роки тому +6

    I hope you are the top paid sparks in Maersk. Such a range of skills.

  • @kabarotv6591
    @kabarotv6591 2 роки тому +5

    The best channel for all the electrical works onboard a vessel.

  • @oleksandrchernov2781
    @oleksandrchernov2781 2 роки тому +11

    Very good video. For defrosting vegetable room better disconnect power supply for solenoid valve and keep running fan for 2-3 hours- also very good way.

  • @ΜΑΝΩΛΗΣΖΩΝΟΥΔΑΚΗΣ
    @ΜΑΝΩΛΗΣΖΩΝΟΥΔΑΚΗΣ 8 місяців тому +1

    thank you for ur time to show us problems of recarding ac and provision systems on board. the line after the expansion valve can be icy but when the TEV is icy this means that a sudden drop of pressure happens before the TEV which can be caused if the TEV filter is dirty.

  • @srujan-eh6mz
    @srujan-eh6mz 2 роки тому +2

    You are explaining like very cool and with patience ☺️

  • @DJVAUGHNCHINNENT
    @DJVAUGHNCHINNENT 14 днів тому

    this information is really profound.....thanks a lot.

  • @jeggercalihat1994
    @jeggercalihat1994 9 місяців тому

    Solid idol 👍 dami ko na natutunan kahit d pa ako nakapag barko 😁

  • @edgar5608
    @edgar5608 2 роки тому +3

    Awesome, another well done job.
    As a still inexperienced Engineer, I would really like to sail with you. Im sure that I would learn a lot. And just having really good colleagues like you would for sure keep one motivated to constantly improve :)

    • @leckyjake
      @leckyjake  2 роки тому

      thank you for your support

    • @niky7197
      @niky7197 Рік тому

      No I go with him... 😠

  • @heavydiesel
    @heavydiesel 2 роки тому +8

    Interesting vid!
    I work on a lot of really old systems, have seen a few TXV's where the inlet filter has become blocked with dirt. Also have had a few where systems have been converted from CFC's to HFC's where the TXV has got wax in it which also blocks the flow.

    • @leckyjake
      @leckyjake  2 роки тому

      thanks

    • @rustblade5021
      @rustblade5021 2 роки тому +3

      yes it is probably clogged or faulty txv but this works fine for temporary fix

  • @Timpon_Dorz
    @Timpon_Dorz 9 місяців тому

    Very well made. Thank you... Explained a lot

  • @elmerbiongan9784
    @elmerbiongan9784 2 роки тому +1

    very informative video, thanks for sharing ideas on how to fix this kind of trouble on the reefer machine.

    • @leckyjake
      @leckyjake  2 роки тому

      thank you for the support

  • @ChandanaPriyantha-pq3uv
    @ChandanaPriyantha-pq3uv 6 місяців тому

    Interesting lessons are there,I would like these trouble shooting of machineries,Thank you sir

  • @RajanKumar-xc8pm
    @RajanKumar-xc8pm 18 днів тому

    Nicely explained.👍👍

  • @Budiono-yk8dw
    @Budiono-yk8dw 8 місяців тому

    Terima kasih sudah berbagi pengetahuan & pengalaman anda dalam bekerja,,video anda sangatlah bagus dan sangat penuh dengan ilmu pengetahuan.

  • @rajeshsonkamble2552
    @rajeshsonkamble2552 Рік тому

    Air conditioner & refrigerator work Never ending to learn to new work

  • @FrankMatawai
    @FrankMatawai 8 місяців тому +1

    Very well explanation done. Thanks 🙏

  • @rubenereso5805
    @rubenereso5805 7 місяців тому

    Nice 👍👍 Sir 🙏 I have good learned for your discussion about the refrigeration thank you so much Sir👏👏👏👍👍👍

  • @rohilkumarsaini9126
    @rohilkumarsaini9126 2 роки тому +2

    Thank you sir for sharing wonderful knowledge.

  • @SreejeshKS-lw1iz
    @SreejeshKS-lw1iz 8 місяців тому

    Your all videos are very useful.Please add more videos of reefer container issues

  • @bassamrajjoub9843
    @bassamrajjoub9843 Рік тому +2

    Thank you master.God bless you.

  • @manubkrishnan
    @manubkrishnan 2 роки тому

    Thanks for the video... expecting more videos on refrigeration and AC...

  • @bassamrajjoub9843
    @bassamrajjoub9843 9 місяців тому +1

    God bless you teacher

  • @mahmoudmoussa9687
    @mahmoudmoussa9687 2 роки тому +1

    I totally agree with u and you are really amazing 👏

  • @davidsanders6957
    @davidsanders6957 5 місяців тому +1

    You the man !

  • @michaelmacuha8341
    @michaelmacuha8341 Рік тому

    thank you 💕 very well explained and informative .. more educational videos like this will help our kabaros

  • @leroytheconvoy713
    @leroytheconvoy713 10 місяців тому

    Nice video, thanks for posting!

  • @El_Robinson
    @El_Robinson 2 роки тому +1

    Great Video!!! Thank you for sharing.💯💯

  • @somendranathchatterjee7704
    @somendranathchatterjee7704 2 роки тому +1

    Nice video, well done buddy.

  • @warnadisuwarlan6606
    @warnadisuwarlan6606 4 місяці тому

    Thanks so much for your sharing brother.

  • @reefercontainerph4182
    @reefercontainerph4182 2 роки тому +1

    Very Informative video sir! thanks for sharing

  • @tsalikistsalikis3118
    @tsalikistsalikis3118 2 роки тому +3

    THAT'S WHY YOU SHOULD ALWAYS USE EVAPORATORS WITH HEAT ELEMENT AND TIMER FOR DEFROST NOT ONLY FOR TEMPERATURES BELOW ZERO BUT ALSO FOR TEMPERATURE ABOVE ZERO WITH HIGH OR LOW HUMIDITY IN THE COLD ROOM.
    AND YOU WILL NOT SEE FOR EVER ICE IN THE FINS OF YOUR EVAPORATORS.
    NEVER TOUCH/TRY TO ADJUST THE EXPANSION VALVE BECAUSE IT IS FACTORY ADJUSTED WITH THE CORRECT SUPER HEAT.
    CHOOSE THE CORRECT ORIFICE.
    KEEP THIS ADVICE FOR THE FUTURE.
    THANKS FOR READING 🇬🇷

    • @officerkrupke4966
      @officerkrupke4966 2 роки тому

      Stewards dept. leaving doors open all the time. I cant believe that system came without defrost heaters..

    • @tsalikistsalikis3118
      @tsalikistsalikis3118 2 роки тому

      @@officerkrupke4966 YOUR OPINION Sir.

    • @tsalikistsalikis3118
      @tsalikistsalikis3118 2 роки тому

      THAT'S WHY WHEN THE DOOR IS OPEN,
      IT'S SHOULD GIVE THE DOOR SWITCH,
      THE ORDER TO CLOSE THE SOLENOID VALVE AND FANS TO STOP.
      IT DEPEND FROM THE ORDERS YOU GIVE TO THE ELECTRICAL PANEL.

    • @officerkrupke4966
      @officerkrupke4966 2 роки тому +1

      @@tsalikistsalikis3118 That still isnt going to get rid of the high humidty air introduced each time room is accessed. Need after market defrost heating strips installed with timer to initiate and shut off solenoid and fan.

    • @tsalikistsalikis3118
      @tsalikistsalikis3118 2 роки тому

      @@officerkrupke4966 DID YOU READ MY LAST COMMENT ?
      I THINK YOU AGREE WITH ME.
      SAME SENSE WITH DEFERENT WORDS.

  • @16valve64
    @16valve64 2 роки тому +1

    Thanks a lot Jake

  • @globalgate8480
    @globalgate8480 2 роки тому

    Very nice, enjoy your posts

  • @ScorpiomarineTV
    @ScorpiomarineTV 2 роки тому +1

    Thankyou for this video sir.

  • @rahmansaleh5695
    @rahmansaleh5695 2 роки тому +1

    Good job bro 👍👍👍

  • @danielfdo4889
    @danielfdo4889 2 роки тому +1

    Very useful 👍

    • @leckyjake
      @leckyjake  2 роки тому

      thank you for watching

  • @gregdekkers2667
    @gregdekkers2667 2 роки тому +2

    If you have to adjust the TXV to solve an issue that wasn't there before with similar settings I would say the TXV is faulty or you possibly miss something else (blockage around inlet TXV?) and are solving a problem by offsetting your TXV. (P.S. I sailed on he same vessel as you in 2009 - Maersk Salalah.)

  • @dennisvirtuoso6478
    @dennisvirtuoso6478 2 роки тому

    Tnx sa info sir..dagdag kaalaman

  • @wasimedoo7994
    @wasimedoo7994 2 роки тому

    Very good information nice job

  • @pawan.malakar
    @pawan.malakar Рік тому

    Very good knowledge form video.

  • @paologringoescalante6916
    @paologringoescalante6916 Рік тому

    Thank you, leck!😊

  • @majidrad7516
    @majidrad7516 11 місяців тому

    Thank you and good luck buddy 👍

  • @seamantv6182
    @seamantv6182 Рік тому

    Very helpful to other sir idol

  • @johnthompson9918
    @johnthompson9918 2 роки тому +6

    Should you check for superheat with a thermometer and gauge pressure prior to adjusting valve? I hope so.
    The room doesn’t look like a new installation. Possibly worth replacing the TXV completely if it isn’t functioning ok

    • @davidsanders6957
      @davidsanders6957 5 місяців тому +1

      Can't find a parts house in the middle of the Atlantic Ocean 😮😮😮😮

    • @johnthompson9918
      @johnthompson9918 5 місяців тому +1

      @@davidsanders6957 isn’t there a refrigeration wholesale down just off Bedrock Road? 🤪

  • @svyat8710
    @svyat8710 2 роки тому

    I liked this Video 👍👍👍💯

  • @johncoyote9012
    @johncoyote9012 2 роки тому

    Nice info and kudos to u amigo. Keep safe always.

  • @hvacknowledgechannel1621
    @hvacknowledgechannel1621 7 місяців тому

    Good explanation

  • @smileforever3486
    @smileforever3486 9 місяців тому +3

    isn't the TXV supposed to automatically adjust the amount of refrigerant passing through by sensing the refrigerant temperature at the output of the evaporator coil?

  • @tomasmahuis-teles1976
    @tomasmahuis-teles1976 4 місяці тому

    Good video , l have a question why the line of the line low side , is getting a little frosty, on a walk in freezer

  • @dmitriibugayov6975
    @dmitriibugayov6975 8 місяців тому +2

    I can be wrong, but Superheat is the amount of heat added to a vapor above its boiling point. As a result, it shows the amount of heat your Freon has gathered over time.
    This means that the evaporator is frozen because you have too LOW superheat, but not too high! Too much Freon goes through txv and in the video you are reducing the quantity of Freon and that is why increasing superheat. Am I correct, colleagues?

    • @lambertobaldovino4535
      @lambertobaldovino4535 8 місяців тому

      Parehong tama ang explanation ninyo sir jake and Mr. bugayo pero ang tingin ko ang problema nasa spring tension,dahil na rin sa sobrang ice build up umabot hangang feeler bulb.kaya kinulang nang bukas ang expansion valve .yong pag adjust ni sir jake counterclockwise ay nagbalik sa tamang opening uli yong txv.hope nakatulong sa pag analyze nang problema.

    • @davidsanders6957
      @davidsanders6957 5 місяців тому

      🎉

  • @marinonglubas6103
    @marinonglubas6103 4 місяці тому

    Rip sir lecky laki tulong talaga mga video mo 😊

  • @androcadivida957
    @androcadivida957 Рік тому

    Galing talaga idol

  • @tjairicciardi9747
    @tjairicciardi9747 2 роки тому

    great video

  • @jonnyjonnyyespapa8013
    @jonnyjonnyyespapa8013 Рік тому

    Valve looks like there is a restriction. Also the type of frost build up on coil indicates lack of defrost and high humidity entering walk-in box

  • @babaolowo35
    @babaolowo35 2 роки тому

    Thanks 👍

  • @Marineelectricalknowledge
    @Marineelectricalknowledge Рік тому

    Please do video on refrigerator cycle system.

  • @LucasOli09__
    @LucasOli09__ 7 місяців тому

    Hi my friend Leckyjake, I'm speaking from Brazil, I'm trying to find out about the Alj281 from the Daikin container.. Other than the SMV valve, the SMV coil, and the solenoid coils, what else can cause this alarm?

  • @migz4360
    @migz4360 2 роки тому

    sir thank you for the video..

  • @muhammadfaridsulton5668
    @muhammadfaridsulton5668 Рік тому

    Hello mr lecky. I am also electrician of the ships. I want to learning with you about cold storage no cool because having ice on expansion valve. I ask to you what cause this ? Please help me

  • @TheBTheBeurope
    @TheBTheBeurope Рік тому +5

    That's why there is a method called ''DEFROSTING''
    (1) Stillstand - Shutting the system till the ice melts
    (2) Let the fan only run in the evaporator
    (3) Heating rod in the evaporator.
    (4) High-Pressure hot gas flowing pipe from the compressor directly to the evaporator.
    All the above-mentioned processes apart from the 3, are automated and have time intervals.
    You adjusted the TEV by turning counterclockwise. This means you opened the valve more. This means more refrigerant is sprayed in the evaporator. When more refrigerant is sprayed in the evaporator, it gets cooked more slowly ( turns to gas form more slowly). This will result in the refrigerant leaving the evaporator in a semi-liquid state. This will result in very low SUPER HEAT.
    I don't think you have solved the problem.
    The temperature in the vegetable room seems to return back to normal because after you cleaned the ice block from the evaporator the fan is circulating the air in the room properly. But soon ice block in going to form in the evaporator and the same problem returns back.
    Instead of adjusting the TEV, you should have checked the DEFROSTING system's functionality.

    • @niky7197
      @niky7197 Рік тому

      It has no Dfos system....

    • @davidsanders6957
      @davidsanders6957 5 місяців тому

      Also, liquid leaving evap will "slug" compressor

    • @atifali1839
      @atifali1839 2 місяці тому

      Adjustment nut is downside so counter clockwise means closing the valve

  • @KamaleshSellamuttu
    @KamaleshSellamuttu 7 місяців тому

    Dear Lecki Jake, if there is too little refrigerant in the evap. coil, it will get excessively heated up ( high superheat ), resulting in sensing bulb opening the txv to admit more refrigerant to the evap. coil, however you state that there is too little ref charge in evap.coil due to high superheat - could you please clarify this? thanks

  • @nivri88
    @nivri88 2 роки тому +1

    Hey bro just have a question right above the TXV all the way to the evaporator was filled with ice what you think causing it? it’s a little condensing unit..thanks

  • @jayvinmarqueses9484
    @jayvinmarqueses9484 Рік тому

    Check first superheat, then you adjust accordingly.

  • @alegreberlin4628
    @alegreberlin4628 3 місяці тому

    How about walk in freezee sir icy on expansion valve,

  • @maheshkumarsubramani5329
    @maheshkumarsubramani5329 3 місяці тому

    When txv supplies more refrigerant ice will form on evaporator right .?
    If supply refrigerant too small how ice will form.
    Might be temperature not in level. Okay

  • @danishmomin8102
    @danishmomin8102 2 роки тому +1

    why back pressure valve is provided in veg room?

  • @celsoguillepa8153
    @celsoguillepa8153 9 місяців тому

    Sir Jake how to adjust thermostat meat room

  • @jahedkn
    @jahedkn 2 місяці тому

    How to find out superheat temperature?

  • @mariyaan1545
    @mariyaan1545 2 роки тому

    Thank you sir

  • @vamshikrishnagadde199
    @vamshikrishnagadde199 7 місяців тому

    Hello lecky have a nice day
    Actually I am on the same ship which you have done that vedio regarding the ice formation in veg room. I have adjusted the TXV but still same the ice formation please suggest what to do

  • @Haamid1977
    @Haamid1977 2 роки тому

    Thanks brother for this vedio.
    I want to know when all the three rooms are running evaporator outlet line is freezing up, but after switching off two units its not. what do you this will be reason. Checked refrigerant charge is ok.

  • @fabiantajale2576
    @fabiantajale2576 4 місяці тому

    Good day sir what the issue the TXV is cold.. but indoor is not cold

  • @alterator
    @alterator 2 роки тому

    Good

  • @bebeusxl9842
    @bebeusxl9842 2 роки тому +1

    Great video as always! Could you perhaps sometime in the future make a video on how to perform safety checks for the ME, Diesel GE, Emergency GE and Boiler?

    • @leckyjake
      @leckyjake  2 роки тому +2

      currently editing video regarding previous boiler trouble

  • @WASIMEDOO
    @WASIMEDOO 9 місяців тому

    So you increase the pressure on the txv is that right

  • @Cathay2017
    @Cathay2017 Рік тому

    Actually you need not to adjust expansion since it is a factory set. Adjusting is only be done in case of emergency. The icing of of evaporator not clearly emphasising the major cause.There is one big reason why icing occurs immediately. It is always the fault when malfunction of one component but pointing to expansion valve is really not the real thing at first.

  • @rajeshsonkamble2552
    @rajeshsonkamble2552 Рік тому

    Some reson ice frosting evaprater fan speed or not working

  • @francisg3349
    @francisg3349 2 роки тому

    Hi. What might be the cause of ice formation on the suction filter line of provision refrigeration compressor?

    • @smyejhamza
      @smyejhamza 2 роки тому

      If its after the filter ( the side that goes in the compressor suction port ) that means you've got a clogged suction filter, and maybe you are flooding back the compressor but maybe not, only superheat could tell you if you've evaporated all of the refrigerant or if there is still some trapped in liquid state

  • @seanintia77
    @seanintia77 6 місяців тому

    rest and peace sir

  • @lunger2006
    @lunger2006 Рік тому

    need a hot gas bypass for the vegetable room system

  • @arabarmwrestlingtv1693
    @arabarmwrestlingtv1693 2 роки тому

    thank you sir for all of this informations, i'm studying mechanical eng and i hope you can suggest some hvac books to learn more about fixing problems in hvac sys . thank u again .

  • @vishnuayapilla1791
    @vishnuayapilla1791 2 роки тому

    What to do with electronic expansion valve, sir can you please suggest me

  • @yousefhaeiri360
    @yousefhaeiri360 2 роки тому

    Hi jecki please make a video about boilers

    • @leckyjake
      @leckyjake  2 роки тому

      currently editing video from our previous boiler trouble

    • @yousefhaeiri360
      @yousefhaeiri360 2 роки тому

      You are the best ever.😍😍

  • @SupremeRuleroftheWorld
    @SupremeRuleroftheWorld 2 роки тому +3

    why not use a constant pressure valve to hold a fixed temperature? with that you can hold a exact temperature just above 0 without any chance of freezing. its the standard for flower storage for example.

    • @leckyjake
      @leckyjake  2 роки тому +1

      this is actually a vessel provision plant and changing the design requires approval from the class

    • @SupremeRuleroftheWorld
      @SupremeRuleroftheWorld 2 роки тому +1

      @@leckyjake yes, i understand that. i just wonder why they didnt use such a valve. is it just for parts commonality or just a engineer that assumes everything always works perfectly all the time?

    • @leckyjake
      @leckyjake  2 роки тому +2

      The temperature for the rooms should be variable, from negative 22 degrees Celsius to positive 22 deg Celsius. In this way they can use for various reasons.

  • @sukhwinder7636
    @sukhwinder7636 5 місяців тому

    Good evening bro

  • @claudiusderil7098
    @claudiusderil7098 Рік тому

    Sir please explain about superheat please

  • @arturollanto3984
    @arturollanto3984 2 роки тому

    I have a question what is the problem why have ice in met room and fish room

  • @acong9891
    @acong9891 Рік тому

    same trouble with my deep freeze.. but the trouble is happen in fish compartment.. are the solution is same like this video? hope u reply sir

  • @acmell3173
    @acmell3173 2 роки тому

    Great explanation, btw sir you are RAC TEHC.?

    • @leckyjake
      @leckyjake  2 роки тому

      I am an Electro Technical Officer onboard a ship

  • @JayjayCaluyo
    @JayjayCaluyo Рік тому +1

    big no sir,that valves is factory seated nothing to adjust check your control,fan blower and also refrigerant charge.

    • @leckyjake
      @leckyjake  Рік тому

      and yet after doing it the unit becomes ok

    • @JayjayCaluyo
      @JayjayCaluyo Рік тому +1

      Yeah but in few days you see

    • @leckyjake
      @leckyjake  Рік тому

      that video was already from last year and the system still in good running condition up to now

  • @dudungdkin2100
    @dudungdkin2100 5 місяців тому

    RIP leckyjake

  • @WALKINGJOURNEY-eq9zd
    @WALKINGJOURNEY-eq9zd Рік тому

    Txv already set the company when you buy if thers have issue need to be replace..

  • @formanworkshop2433
    @formanworkshop2433 Рік тому

    How are you bro? Where you from

  • @daludadoernelito
    @daludadoernelito 2 роки тому

    You have on line clases ?

  • @Mohammad.faizan.professional
    @Mohammad.faizan.professional 7 місяців тому

    Which ac is it

  • @manuellastrollo2168
    @manuellastrollo2168 Рік тому

    mabuti master hindi nasisira yung fan motor nyo pag binabasa nyo yung evaporator

  • @sherwinladera5818
    @sherwinladera5818 2 роки тому

    hey lecky ...how to apply to your company ...i am HVAC/RAC TECH. ..6 years experience

  • @franzduhina2475
    @franzduhina2475 4 місяці тому

    ser paano kng ice yung evarotor my tendisi ba expansion valve ang problema

  • @mototechtv.3774
    @mototechtv.3774 7 місяців тому

    fly high lodz rest in peace lodz

  • @japhetjalandoni2751
    @japhetjalandoni2751 2 роки тому

    Hello sir Lecky ano po Kaya problem ng reefer Namin Hanggang _4.0 lang yaw tumaas high pressure nya ok Naman low pressure bagsak Ang pressure napansin ko yong expansion valve ay nag yeyo na ano po dapat. Echeck