  • @tobycalhoun8004
    @tobycalhoun8004 2 роки тому +1

    Thanks for the videos! I'm currently building my third food truck but always refer back to your videos for a refresher. I will add that if I ky running 120, you can run a jumper wire between both power legs to provide power to both sides. It needs to be clearly marked to only use 120 at that configuration, but if in the future someone wanted to run 240 it would be an easy conversation.

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      There we go!!! Love the tip, and also thank you for watching. Appreciate that 💯

  • @RJ-cc1fz
    @RJ-cc1fz 3 роки тому +2

    Hey bud. I use the same 120v generator and I use both legs of the breaker panel. You just need to use the hot leg from the generator-plug and jumper it in the panel. Jumper the legs at the lugs. Love the generator, thanks for the recommendation

    • @fbaltierrez
      @fbaltierrez  3 роки тому

      Absolutely that works! I actually was going to add that to the Video decided not too and said the mini breaker option but you are correct

    • @DB-eu6vf
      @DB-eu6vf Рік тому

      If possible, do you have a visual or link to how this is done?

  • @randybowers8115
    @randybowers8115 2 роки тому +2

    Great video thank you so much .. doing a mobile art gallery and I have no clue about electrical . I have a eco flow electric generator .. it only have house plugs as plug ins .. but I will buy a adapter plug so that way I can plug it into the breaker box !

    • @fbaltierrez
      @fbaltierrez  3 місяці тому

      You can add mini breakers. amzn.to/44QYbvh

  • @wes293
    @wes293 Рік тому

    if you need a lot of power like I do, you COULD use 2 generators to get 240v. Hook each hot lead to the electrical panel prongs. This eliminates the need for a parallel kit which only offers 120v most the time.

  • @Ahsao
    @Ahsao 3 роки тому +1

    Thank you!

  • @MikePhoTravelVlogs
    @MikePhoTravelVlogs 3 роки тому +3

    Hey quick question on the generator. Do you cover the generator and propane at all when it rains and snows? I seen your video and looks like you just leave it outside exposed. Basically asking is it ok to leave a generator and propane outside exposed. I live in the Midwest and plan using it year round. Thanks in advance. 💯💯👍 Keep up the Great work!

    • @fbaltierrez
      @fbaltierrez  3 роки тому

      Great question. The generator I do cover bought a generator cover. The propane tanks I do not they sit under the generator so they get pretty blocked off from elements typically

  • @katycodella817
    @katycodella817 2 місяці тому

    Great video! Do you also need to ground your panel box to your trailer frame? My outside plug has a plastic box, so I can't ground to it either.

  • @bryanchavez5726
    @bryanchavez5726 3 місяці тому +1

    Hey frank! Long-time viewer first-time commenter! So the panel is single phase only has space for 2 brakers? Hownwould i be ablento run more circuits for example that need to be independent? I noticed the link says its. 16 space panel.

  • @johnflood4665
    @johnflood4665 Рік тому

    Thanks!

  • @julioroque7704
    @julioroque7704 Рік тому +1

    Gracias por estar horientarme enmi proyecto

  • @lewis5074
    @lewis5074 Рік тому +2

    So if you use mini and connect the other side then you could have technically 8 circuits correct?

    • @fbaltierrez
      @fbaltierrez  Рік тому

      Yes but you wouldn't need that many circuits in such a small space being a truck or Trailer

  • @centralcoast6720
    @centralcoast6720 2 роки тому +1

    Hey Frank question I just found your channel I find it very interesting. I need overnight power for my trailer just to run the freezer and fridge when it’s parked on non working days. I have a 50 amp-240v plug on my trailer for my generator. How can I get electricity from a 120 watt home outlet just to keep my stuff cool over night? What kind off cord outlet do I need.

  • @danielcox7520
    @danielcox7520 3 роки тому +2

    Hey Frank! Thanks again - as always- for your awesome insight! Is there any way you can demonstrate exactly how you ran the SO cable underneath the trailer, and up into the electrical panel?

    • @fbaltierrez
      @fbaltierrez  3 роки тому +1

      A few videos back I show it. Let me see if I can get the link for you

    • @danielcox7520
      @danielcox7520 3 роки тому +1

      Awesome! Thanks again!

    • @miltonmendoza7714
      @miltonmendoza7714 Рік тому

      Hey frank big question
      How much money you end up expending with the trailer and equipment. And how long it took you to get done??

  • @stevensanchez7802
    @stevensanchez7802 2 роки тому +2

    Hi Frank, I have a 50 amp plug on my food truck but the cable it’s on it’s a 12 gage, just wonder if that’s going to be good for that big of a 50 amp plug? Thank you!

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      12 gauge is only rated for 20 amps, you'll overheat the wire

  • @mobilesushibargirl
    @mobilesushibargirl 3 місяці тому +1

    How are you grounding your food truck? My fire inspector says I need a ground rod but I’ve never seen this before. My trailer is grounded according to the manufacturer and we use a breaker panel and 50 amp plug

    • @fbaltierrez
      @fbaltierrez  3 місяці тому

      Our fire department or building department does not ask us for that. So haven't ran into that issue yet unfortunately. Typically this is considered a mobile kitchen and does not have all the requirements that Typical brick and mortar restaurant has. That's how I would word it to them

  • @JasonWalker-vt1om
    @JasonWalker-vt1om Рік тому +1

    Frank, I know that when finished I need to get a health inspection for my certificate for operations. My question is do I need to get anything else inspected like electrical or plumbing earlier in the process? Is it like in a house where an inspector has to come and make sure you are up to code? I just don't want to get all my FRP up and then someone is like, hey I need to see all your electrical to make sure you are to code. :)

    • @fbaltierrez
      @fbaltierrez  Рік тому +1

      You would have to ask the mobile vendor department in the city you want to sell in and they'll get you squared away. With us they do not but it's different everywhere

  • @hodge16
    @hodge16 3 роки тому +2

    You can run some generators on parallel kits and they are 4 prong 50amp. That's what I'm currently doing.

    • @fbaltierrez
      @fbaltierrez  3 роки тому

      There we go. Never used that style of power but have seen others use it 👍👍

  • @thanhnguyen-ze9lh
    @thanhnguyen-ze9lh 3 роки тому +2

    HI FRANK
    I am going to use generator Westinghouse 7500-9500 watts with 4 prong inlet and 4 prong inlet box. I will connect all 4 wire following your video to inlet box BL-W-RD and GR. I still have the red wire on the panel, do I connect to another side? And if I connect to another side, can I use both side of the panel 30amp?
    Thank you.

    • @fbaltierrez
      @fbaltierrez  3 роки тому +3

      Good morning, watch my videos coming up this week. I'll hopefully explain the electrical to be easier to understand on my new Food Truck build

  • @BobsFUNFOODS
    @BobsFUNFOODS 3 місяці тому

    Is the breaker panel in my food trailer considered a main panel or sub-panel? Do I need to remove the green bonding screw?

  • @travisthurston8685
    @travisthurston8685 Рік тому +1

    What’s your thoughts on putting the electric panel above the sink at the front of the trailer?

    • @fbaltierrez
      @fbaltierrez  Рік тому

      It can be done, I'm not the biggest fan of it, but it can work

  • @danielnunez7930
    @danielnunez7930 2 роки тому +2

    Great video, I am planning on using a 50amp generator just wanted to confirm the so cable will need to be rated for 50amps along with the inlet plug? If so the 50amp inlet connector has 4 prongs red, black, white and ground correct? That would allow me to add the extra 2 circuits at the panel

    • @danielnunez7930
      @danielnunez7930 2 роки тому

      Also because ampere rating for that so cable it would need to be awg 6 instead of awg 8 correct ?

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      The red and black are not what allows you to have 2 extra circuits that's what gets you 240 volts.

    • @danielnunez7930
      @danielnunez7930 2 роки тому +1

      @@fbaltierrez gotcha I was under the impression that I could use 8/3 or 6/3 cable and use the black for x red for y along with w for neutral and then my ground with a 50amp inlet plug. So that won’t allow me to use the 2 extra circuits?

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      @@danielnunez7930 it can. Maybe I misunderstood but yes you are correct as long as you don't use a double breaker than you are good. My bad

    • @danielnunez7930
      @danielnunez7930 2 роки тому

      @@fbaltierrez thanks for the info

  • @dmandable
    @dmandable 2 роки тому +1

    Frank, quick question on the wiring, do you need to run armoring when running the interior wires?

    • @fbaltierrez
      @fbaltierrez  2 роки тому +1

      That depends on your building inspector if they do inspect it. Some places do some don't

  • @user-in8yg7vz2g
    @user-in8yg7vz2g Рік тому +1

    If I am running two 4500 westinghouse generators would the breaker box still be setup the same ?

    • @fbaltierrez
      @fbaltierrez  Рік тому

      Depends how you are using them. In parallel or do you have 2 different inlet boxes

  • @acostaedwin986
    @acostaedwin986 8 місяців тому +2

    How can I put in a large electrical box since I'm going to use some extra cooling equipment!?

    • @fbaltierrez
      @fbaltierrez  8 місяців тому +1

      Ypu don't need anything incredibly big, a small 16 space is plenty. They aren't terribly big

    • @acostaedwin986
      @acostaedwin986 8 місяців тому

      Thanks frank

  • @vishkitchen
    @vishkitchen Рік тому

    Hey Frank can i di the same thing you did in this video and leave the red wire out from the panel

  • @joelb2178
    @joelb2178 2 роки тому +1

    Hi Frank - thank you for this series. I was wondering about stabilizing jacks - how do you keep your trailer level?

    • @fbaltierrez
      @fbaltierrez  2 роки тому +1

      In my personal experience I never unhitch my trailer off my truck ever when I am in season at an event. But when I park the trailer off season without my truck I have never had a issue with the Trailer Tipping

  • @Best.Finds11
    @Best.Finds11 10 місяців тому

    I have a question about my electric. I’ve been screwed over so many times by people and companies with my issue. So I am at a point that it’s easier to just do it myself. Would it be possible to IM me, because after watching this video ( which makes sense) only confused me more, given how my wires, etc are connected in my box. Thank you soo much!!

  • @thankyouvlog9333
    @thankyouvlog9333 2 роки тому +1

    Hi frank.. question..why the cord you using the male has 3 pin and the famale has 4 holes.. your inlet gen box has 3 prong which is the famale goes to inlet box has 4 holes.. can you pls explain. Thank you

    • @fbaltierrez
      @fbaltierrez  2 роки тому +1

      It's if you want to use 240V you would use the 4 spaces but since I only use 120v only 3 spaces are needed

    • @thankyouvlog9333
      @thankyouvlog9333 2 роки тому +1

      @@fbaltierrez thank you... i install my main panel under sink would that be ok or it depends on the town

    • @fbaltierrez
      @fbaltierrez  2 роки тому +1

      @@thankyouvlog9333 depends on town definitely, but it works not the ideal place but it works

  • @FamilyChannelfun32
    @FamilyChannelfun32 3 роки тому +1

    Frank so I have a ac up top. Fridge freezer. And exhaust fan and outlets. Last year we were maxed out at 30 amp. So would 50 be ok to do. My generator which does propane and nat gas does do up to 50 amp. I'm assuming you run yours at 30 amp

    • @fbaltierrez
      @fbaltierrez  3 роки тому

      I would do 50 if you can. Yes I run 30 amps no AC

  • @strings1955
    @strings1955 2 роки тому +1

    Appreciate your videos. With two 15k BTU rooftop a/c would it be simpler to run 240v from the genset, and have two 120v circuits from the two legs?

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      Could be. I don't use AC units in my trailer so wouldn't be the biggest expert for that

    • @strings1955
      @strings1955 2 роки тому

      @@fbaltierrez Thanks. Know anybody?

  • @JohnJones-rj2zd
    @JohnJones-rj2zd Рік тому

    I. Your description with your links of equipment, I see you have regular 15 amp outlets. Do you not use gfi outlets on your food truck builds?

  • @acostaedwin986
    @acostaedwin986 Місяць тому

    Frank aqui en el estado de washintong el cable que hace tierra tiene que ir conectado en el chasis de el trailer como podria hacerlo?

  • @SgtRobChapu
    @SgtRobChapu 2 роки тому +1

    On the box plug coming from gen. Can’t we use the matching 3 prong 30amp female plug to match the gen. And do away with the prong altogether?

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      Which prong are you referring to? Can't visualize it

    • @SgtRobChapu
      @SgtRobChapu 2 роки тому

      The same plug type as the generator 30amp 3prong. Or is there some type of building code that states twist lock only? Ty

  • @sbabb13662
    @sbabb13662 2 роки тому +1

    Hi Frank. Was watching this and I noticed that your plug won't be able to fit in that box. The box is 3 prongs and the plug is 4 prong. How does that work

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      Yes that was an old 30 amp box I had now I use the 50 amp which comes with the 4

  • @moises-salazar
    @moises-salazar 3 місяці тому +1

    Is there a reason you didn’t put the cable through the breakaway has on top?

    • @fbaltierrez
      @fbaltierrez  2 місяці тому

      I run my power wire inside my walls so I don't use the knockouts on tops or sides

    • @moises-salazar
      @moises-salazar 2 місяці тому

      @@fbaltierrez I got that. I meant the one that’s on the back of the panel right above the breakers. Next to mounting holes.

  • @ronniebonaparte2642
    @ronniebonaparte2642 2 роки тому +1

    I'm putting a 120 breaker in and I have the breaker box going on the inside of the trailer and the cable for the generator to go outside the trailer will this same practice work for that

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      Yes. On my newer electrical videos if you haven't seen those from about 2-3 weeks ago maybe that's what you mean I assume

  • @johnflood4665
    @johnflood4665 Рік тому +1

    Hi Frank,
    What model Cargo Mate did you buy. Thanks, John

  • @r.llynch4124
    @r.llynch4124 Рік тому +1

    So I have a predator gen and need 240 volts to 1 equipment in trailer and 120 to the other stuff. Would I need to run 2 individual wires/gauges to 2 inlet plugs on the trailer. Sounds like I would need to panels inside, one for 120 and one for 240. Kinda confusing since the gen has separate plugs all over the place.

    • @fbaltierrez
      @fbaltierrez  Рік тому +1

      Keep it simple only use the big plug send that to the panel inside and then distribute from there to the entire trailer. Think of it like a house everything distributes from the main panel.

    • @r.llynch4124
      @r.llynch4124 Рік тому +1

      @Frank Baltierrez yep I Ike simple. So use the 120/240 volt plug to trailer beaker box, dont worry about the other 120 volt plugs on gen, right?

    • @fbaltierrez
      @fbaltierrez  Рік тому

      @@r.llynch4124 I go to the inlet box first and then the breaker panel as I show on the videos

    • @r.llynch4124
      @r.llynch4124 Рік тому

      @@fbaltierrez Not so simple after all. I have a 240 v unit pulling 18 amps and then 2 refrig units pulling approx 6 amps total PLUS 2 13,500 btu ac units pulling 13 amps each .. Still sounds like I will need several cables running from gen to trailer ,breakers.

  • @marcodelao9148
    @marcodelao9148 2 роки тому +2

    wouldn't a food truck panel technically be a sub panel and therefore neutral and ground should not be bonded. generators should have a grounding conductor terminal for true earth grounding. bonding in this case would make the grounding conductors into current carrying conductors and thus energize the metal food truck. I think lol.

    • @fbaltierrez
      @fbaltierrez  2 роки тому +3

      You are correct. I have to redo that video as possible I wasn't very clear on that. 👍 thank you for reminding me

    • @marcosdominguez3702
      @marcosdominguez3702 Рік тому +2

      Now I’m confused… so the way you wired it up in the video is not correct? In another video you connected the grounds into the neutral bar… how should it be grounded?

  • @samuelnieves565
    @samuelnieves565 2 роки тому

    Hola Frank, tengo una pregunta, nesesito poner nueva intalacion electrica a mi food traila, yo lo puedo hacer, gracias a tus videos pero NESESTO UN PERMISO DE LA CIUDAD, O NESESTO CONTRATAR ELECTRSISTA CON LISENCIA?

  • @mikewhalen2024
    @mikewhalen2024 3 роки тому +1

    Hey, quick question, I’m not getting any power from the generator to the panel. I have the hot wire running from x to x any ideas where I should start troubleshooting? I did have to make the cord

    • @fbaltierrez
      @fbaltierrez  3 роки тому +1

      And on the panel how did you wire it?

    • @mikewhalen2024
      @mikewhalen2024 3 роки тому +1

      @@fbaltierrez It was an issue inside the cord. Just sent my first truck out of the door thanks to you

    • @fbaltierrez
      @fbaltierrez  3 роки тому

      @@mikewhalen2024 nice!!!!!!! Glad you found the issue

  • @thatbeardguyoutdoors651
    @thatbeardguyoutdoors651 2 роки тому

    I am looking to split my electric to either run the entire trailer off 1 plug in when I have 50amp or to plug in a secondary power supply and then split the box to run half the trailer off one circuit panel and then the other half off another when I only have 30amps available. Would you have any ideas on how I would do this? Have to plug in points on the trailer and then run into 2 separate panels which have a switch between to split power or run it all through one plugin is what I'm thinking but not sure how to do that split?

  • @wickscanflip9912
    @wickscanflip9912 Рік тому

    What if I want the option to have my generator power my truck and then say I wamt to habe access to local electricity hookups. Is there am adapter I add to the reliance plug?

  • @mannycarrasco8120
    @mannycarrasco8120 Рік тому +1

    Hi bro so can you hook up food truck to generator and a main panel at a home

    • @fbaltierrez
      @fbaltierrez  Рік тому

      No. Only to the generator or to a regular outlet in your home or parking area

  • @HTX-713_
    @HTX-713_ 2 роки тому +1

    What wire do I use for 220 plug for the main wire to the generator?

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      Depends on your amperage needed. I have used 6 gauge wire now but it depends on your amperage needs

  • @stevenromero6125
    @stevenromero6125 10 місяців тому +1

    Ball park of what thus would cost?

    • @fbaltierrez
      @fbaltierrez  10 місяців тому

      For the electrical work required or for a food trailer

  • @german_valle2024
    @german_valle2024 2 роки тому +1

    Por que no haces tutorials en Espanol ???

    • @fbaltierrez
      @fbaltierrez  2 роки тому

      Buenos Dias, esta Semana voy a ser un walk thru de una que tengo Aqui

  • @julioroque7704
    @julioroque7704 Рік тому +1

    Amigo donde hagarras las. Plogas

    • @fbaltierrez
      @fbaltierrez  Рік тому

      50 Amp Generator Plug
      www.amazon.com/gp/product/B000HS0HQW/ref=as_li_tl?ie=UTF8&camp=1789&creative=9325&creativeASIN=B000HS0HQW&linkCode=as2&tag=rollingburrit-20&linkId=10042d0aa2d8ad0a2df1e1d6382444a3
      Generator inlet Plug
      www.amazon.com/gp/product/B000HRWGBW/ref=as_li_tl?ie=UTF8&camp=1789&creative=9325&creativeASIN=B000HRWGBW&linkCode=as2&tag=rollingburrit-20&linkId=bdb8d132228fd5d3a72ed4104096769c

  • @claudiojuarez1444
    @claudiojuarez1444 2 роки тому +1

    Hola frank estoy construyendo una coffee truck y nesecito dos generadorss Como los instalo tengk que poner dos cajas de brakers Como le ago

  • @gianvitolanzisera9169
    @gianvitolanzisera9169 Рік тому

    Hi Frank where can I find that same exact gene cord for sale?

  • @dmandable
    @dmandable 2 роки тому

    or is that a local requirement that i need to find out about... I am being told that i must have a certified contractor do the work, so I am thinking that I can do most of it and have a contractor inspect and sign off on it.

  • @ricojennings6867
    @ricojennings6867 Рік тому

    How can I upgrade my electrical panel from 50 amps to 100 amps

  • @rafaelrodriguz2142
    @rafaelrodriguz2142 2 роки тому

    Ola miro mucho tus bideos pero casi no pones bideos en español

  • @Ocgaming2011
    @Ocgaming2011 3 роки тому

    How much you selling it for

  • @daprincebun
    @daprincebun 3 роки тому

    Trying to wire my ice cream truck with electro freeze 3phase ice cream machine

    • @scottschlesser
      @scottschlesser 3 роки тому +1

      You will need a 3 phase generator or other 3 phase power supply for your ice cream machine. I think you could also install a 3 phase convertor. For something like this, you are better off with single phase machinery or hiring a licensed electrician for the install.