ALTERNATOR AVR (PART 2)

Поділитися
Вставка
  • Опубліковано 11 вер 2024

КОМЕНТАРІ • 79

  • @aslamsajjad8867
    @aslamsajjad8867 6 місяців тому +1

    Yes it is compatible.

  • @robertoquinones3827
    @robertoquinones3827 2 роки тому +1

    Yes we can use that type of AVR but u have to supply input voltage at L-N to get 240Vac from stator windings output voltage with excitation current of 3amps per 10secs.

  • @EdelSM
    @EdelSM 4 роки тому +2

    for remote voltage adjustment potentiometer ay OK lng kahit more than 1watt, and mas better. but the resistance should be 1k as per the manual.

  • @gabornerimar2094
    @gabornerimar2094 4 роки тому

    Tnx you sa video sir good bless and more power

  • @goldgolden3004
    @goldgolden3004 2 роки тому

    Thank you so sir . Good bless you

  • @teloexplicaeldiamante2855
    @teloexplicaeldiamante2855 8 місяців тому +1

    MY AVR GAVE AT MAXIMUM RANGE, THE GENERATOR IS 220 V AND GENERATES 355 V.
    IT DOES NOT ADJUST BY THE VOLTAGE POTENTIOMETER. WHAT WAS DAMAGED?

    • @shuttlemarineengineering
      @shuttlemarineengineering  8 місяців тому

      What is the brand and capacity of the alternator?

    • @teloexplicaeldiamante2855
      @teloexplicaeldiamante2855 8 місяців тому

      IT IS A CARD EQUAL TO THE STAMFORD, BUT UNIVERSAL. MY QUESTION IS: WHAT COMPONENT WAS DAMAGED TO THE CARD SO THAT IT DOES NOT REGULATE THE OUTPUT AND IS AT MAXIMUM RANGE

    • @shuttlemarineengineering
      @shuttlemarineengineering  8 місяців тому +1

      @@teloexplicaeldiamante2855 Hard to know which electronic component gave up, but based on your info’s it’s on the regulation circuitry. But if fitted with remote V adjustment is suggest you check if it’s open or if connection from potentiometer to avr if not broken or loose. A loose remote V potentiometer also causes high V output. If no remote then AVR is defective. Thanks

  • @DieselGeneratortraining
    @DieselGeneratortraining 3 роки тому +1

    Sir did u suggest to install the 6 amps breaker on AVR output or not as u mention there is no Protection on AVR

  • @reymartmanablug2965
    @reymartmanablug2965 4 роки тому

    Very informative video sir.

  • @addiszemen1637
    @addiszemen1637 4 місяці тому

    Thank you so much

  • @franciscorabano8025
    @franciscorabano8025 Рік тому

    Sir.. mike pwedi nyo po ba magawan ng video yong sa load sharing at paralleling requirements para sa dalawa or more generators.. thanks

  • @teloexplicaeldiamante2855
    @teloexplicaeldiamante2855 8 місяців тому

    I HAVE AN AVR SX460 INSTALLED ON A 220V GENERATOR. BUT NOW IT IS GENERATING 360 V AND IT DOES NOT TAKE ADJUSTMENT BY THE VOLTAGE POETENTIOMETER. I ASK YOU: IS IT A PROBLEM WITH THE AVR CARD OR IS IT AN INTERNAL PROBLEM. BECAUSE THE CARD LOOKED GOOD

    • @shuttlemarineengineering
      @shuttlemarineengineering  8 місяців тому

      SX460 max input in 264V only and it’s receiving 360v and since this avr’s does not have fuses then your avr is probably gone. Check excitation V how high is it and from there you can confirm that you have a defective AVR. Damaged rotating diodes or burnt winding wont show a high voltage, instead it produces a very low V. Thanks

  • @kennethbuenaflor4372
    @kennethbuenaflor4372 3 місяці тому

    Hi ser How do you get over voltage of output 90v to 150v is that ok??

  • @joeopilas52
    @joeopilas52 3 роки тому

    The regulator of my 7.5 KVA generator has corroded and I want to replace it with a new AVR just like this SX460. I understand this is designed for a brushless generator which requires a smaller amount of current considering that the AVR is powering a slave generator which in turn supply a bigger amount of current to the exciter of the main generator.
    The way I look at it is that the voltages are just alright for my generator and the AVR. I just want to know if its 4A continuous current in the output is adequate to power the exciter field of my generator. By the way its exciter resistance is 6.9 ohms. Thank you very much and keep up the good post.

  • @theoryofeverything9439
    @theoryofeverything9439 4 роки тому

    Yes we can use but Only by using a step down transfer because as you see input voltage limit is 264 vAC and Alternator output (input for AVR) is 415 v. All other specifications are satisfactory like Excitation field resistance is above 15 (25 ohm in this case) and AVR output 75 vDC.

  • @raghavendragajapathy6476
    @raghavendragajapathy6476 4 роки тому

    Yes we can use.. Your videos are good.. Kindly share me some more videos about AVR .. Also i have seen few transformers inside alternators.. Please explain about that

    • @theoryofeverything9439
      @theoryofeverything9439 4 роки тому

      Only by using a step down transfer because as you see input voltage limit is 264 vAC and Alternator output (input for AVR) is 415 v. All other specifications are satisfactory like Excitation field resistance is above 15 (25 ohm in this case) and AVR output 75 vDC

    • @Adarsh19893
      @Adarsh19893 4 роки тому

      @@theoryofeverything9439 no need transformer.. Input voltage for avr coming from mid taped alternator terminals

    • @aiahamadumbayo1666
      @aiahamadumbayo1666 3 роки тому

      Is this avr 3 face

  • @kuyaerapshoo1256
    @kuyaerapshoo1256 3 роки тому +1

    Still compatible sx460 same as sx440 avr even 415volt. Am I correct Sir?

  • @rutchelgimeo1306
    @rutchelgimeo1306 3 роки тому

    Sir ask lng ako kasi ung gen set namin I convert nmun sa manual need talaga palit an ang avr kasi digital ung original nya

  • @reynariob.ermino5368
    @reynariob.ermino5368 3 роки тому

    Yng. Training. Nyo. Sír. Ay. Tangap. Ng. Marina. Para. Sa. ETO. Salamat. Sir...

  • @crellyortilla1194
    @crellyortilla1194 2 роки тому

    Thank you sir Mike God bless 🙏🙏🙏. Si undo ito

  • @denboymechanic
    @denboymechanic Рік тому

    I have 375kva nta855-g1 genset for poultry use. .the problema low herts low l-l low l-n kw low and shot down engine. .what is the problem sir can u advice me what is the probs of my genset 365kva

    • @shuttlemarineengineering
      @shuttlemarineengineering  Рік тому

      It really depends on the engine shutdown protection naka install sa system. But based sa info mo sir, low Hz means mabagal andar ng prime mover kya low L-L and L-N din yan definitely. Check na lang ano issue sa governor, fuel lines or other mechanical parts that is causing the RPM nd ema meet rated. If its 4poles yan 1800rpm Im assuming 4 poles windings. Thanks

  • @user-bb7hf1wj5r
    @user-bb7hf1wj5r 3 роки тому

    i need an instrution manual for avr taiyo exu-61a .please if you have it send a link.

  • @rodeldurban4534
    @rodeldurban4534 3 роки тому

    Sir very informative.. May narinig ako voltage droop san po makikita yan? Sa avr din po ba?

    • @shuttlemarineengineering
      @shuttlemarineengineering  3 роки тому +1

      Yes sir droop adjustment is located in AVR. Manufacturer has their own description on droop...you might see it as P/F, derating, AMP, PAR or sometimes even as a simple S. i hope makatulong sa iyo yang infos nyan sir. Thanks

  • @josec.eleccion9349
    @josec.eleccion9349 3 роки тому

    Good day engr. Anong schematic diagram ng ATS Pag connect sa generator. Salamat.

  • @gaminglover9652
    @gaminglover9652 3 роки тому

    Hello po pwede po pa discuss as440, nag under voltage po kasi ang genset tapos bigla namamatay possble po ba na sa avr ang problem..thanks po

  • @ianmichaelluaton9243
    @ianmichaelluaton9243 3 роки тому

    What if sir there is no residual magnetism so it means the avr will not work? And how to restore the magnetism? Thanks

    • @shuttlemarineengineering
      @shuttlemarineengineering  3 роки тому

      No it wont if the residual voltage is not suitable for the AVR triggering V, restoring by field flushing. thanks

  • @franciscorabano8025
    @franciscorabano8025 Рік тому

    Pwedi po ba yong dalawang generator na hindi pareho ang rated power?

    • @shuttlemarineengineering
      @shuttlemarineengineering  Рік тому

      Pwede yan sir aslong as not too huge capacity difference, important to note na they should have the same hz and exactly the same V at whatever loading %. Thanks

  • @glennjayranjo5554
    @glennjayranjo5554 3 роки тому

    Sir my dianamo alternator 5kva pano daigram nga pagkabit ng AVR ata anong brand.... Salamat

  • @dharmeshdj5869
    @dharmeshdj5869 4 роки тому

    Make vedio on sensor wiring to interfacing board on Disel generater

  • @roderickmagpantay6039
    @roderickmagpantay6039 4 роки тому

    Hi Can you discuss also AVR AS480 connection. thank you

  • @andreyaparecidosilva1374
    @andreyaparecidosilva1374 3 роки тому +1

    Presiso de legenda português excelente video

    • @andreyaparecidosilva1374
      @andreyaparecidosilva1374 Рік тому

      Hoje eu consigo entender inglês ,💪💪💪💪💪quem diria ,,🫡🫡🫡🫡

  • @jovsd.i.yprojects
    @jovsd.i.yprojects 3 роки тому

    Sir pwede va yan sa ref

  • @renechavez8275
    @renechavez8275 3 роки тому

    Pang 312 kva na AVR, ang model engine NTA 855

  • @becongcabahug7016
    @becongcabahug7016 3 роки тому

    Sir, need to reply to make more participant perhaps.

  • @melalbano6351
    @melalbano6351 2 роки тому

    Sir how about Generator control modules?

  • @justiceekong6116
    @justiceekong6116 9 місяців тому

    How can I convert maccalte AVR to work with Stamford AVR

    • @shuttlemarineengineering
      @shuttlemarineengineering  8 місяців тому

      What is the alternator output V rating and check nameplate what is the excitation V. From there it can easily be determined what brand and type of AVR can be used. Thanks

  • @ruelbajar8805
    @ruelbajar8805 3 роки тому

    good day sir ask q lng po Sana alarm ng genset perkins 500kva
    BOC L1L3

  • @borjokworkz6273
    @borjokworkz6273 2 роки тому

    Sir good day may generator po akong kinabitan ng AVR. GB170 po yung avr para po sa STC na mindong dynamo po. Ang problem po hindi po naaadjust yung voltage nya sa avr. Yung connection ko sa UVW ok naman po. Dun sa Dalawang Z po sinunod ko naman yung diagram base dun sa manual. Ano po kaya problem sir.? Thanks po

    • @shuttlemarineengineering
      @shuttlemarineengineering  2 роки тому

      Good day sir, yung mindong genset kasi basically brush type and walang exciter field and exciter rotor. Yung output ng stator na U-V-W dun din kukuha ng voltage input yun GB170 na avr, make sure tama yan, yun naman feed sa main field dadaan lang sa trio bridge diodes pra yung 3phase AC from a separate coil group ng stator papunta na main field maging DC volts, pero yung 1 line from stator daan muna sa avr terminals labels Z - Z pra ma regulate yun DC na feed sa main field. Kung maka download ka ng PDF ng manual then balikan mo itong explanation na ito mas maintindihan mo yan. I hope makatulong sa iyo sir. Stay safe

  • @richardparacuelles3612
    @richardparacuelles3612 2 роки тому

    sir magandang araw po,, naka encounter ako sa generator namin ,na sira kasi yung voltage adjuster kasi sinusunog niya yung parang transformer ,,,ngayun wala na akong ibnag paraan oara mag adjust dun lang talaga sa avr mismo ,,,anu pong nang yari jan sir?

  • @Fakir-ck4nh
    @Fakir-ck4nh 3 роки тому

    CATERPILLAR AVR PRICE PLEASE?

  • @modestovillocillo4844
    @modestovillocillo4844 2 роки тому

    May board sa avr ba na para sa delta connection para sa 75kva na avr?

  • @maribelmendoza5523
    @maribelmendoza5523 3 роки тому

    sir pwede ba gamitin ung avr sa generator pra sa submersible water pump.tnx

  • @theoryofeverything9439
    @theoryofeverything9439 4 роки тому

    Without transformer its impossible to use the AVR on this alternator

  • @willymerlan4548
    @willymerlan4548 3 роки тому

    Sir meron po ako nyan baka po bibili kayo ..?

  • @louiegalpo5413
    @louiegalpo5413 3 роки тому

    boss pa order nman po need ko sa 3kva generator k0

  • @protaciojrescarilla6199
    @protaciojrescarilla6199 Рік тому

    sir pwd ba makahingi ng contact no. mo, nag hahanap kz kmi ng mag bgay samin ng training

    • @shuttlemarineengineering
      @shuttlemarineengineering  Рік тому

      Kindly email us at perl.shuttlemarine@gmail.com and we’ll coordinate with you accordingly. thanks

  • @becongcabahug7016
    @becongcabahug7016 3 роки тому

    Boss paano e connect ang AVR sa three phase 220v generator? salamat

    • @shuttlemarineengineering
      @shuttlemarineengineering  3 роки тому +1

      Ano brand and model ng AVR mo sir, if 220V rated Voltage ng genset mo then madali lang kasi most of AVR naman has 180-260V input kya directly connected na sa any of the 2 lines.

    • @becongcabahug7016
      @becongcabahug7016 3 роки тому

      @@shuttlemarineengineering i have a GAVR20A po.

    • @shuttlemarineengineering
      @shuttlemarineengineering  3 роки тому

      Ok yan, madami na tyo nakabit na GAVR pero 15 nde 20, magandang AVR yan, pra nga syang universal kasi mataas excitation current kya pde yan sa ibat ibang brands.

    • @becongcabahug7016
      @becongcabahug7016 3 роки тому

      @@shuttlemarineengineering OK po sir, maraming salamat

  • @becongcabahug7016
    @becongcabahug7016 3 роки тому

    incompatible po Sir

    • @shuttlemarineengineering
      @shuttlemarineengineering  3 роки тому +1

      Compatible yan sir, youll be guided sa mga ibang parts ng vlogs natin for proper connection. Thanks

    • @becongcabahug7016
      @becongcabahug7016 3 роки тому

      Salamat po sir.

    • @kentbontilao1387
      @kentbontilao1387 3 роки тому

      @@shuttlemarineengineering sr tanong lang po yong ginagamit ang dvr paano maa adjust yan at pag wiring? Pwede po bang palitan ang dvr to avr? Salamat po