Generator Not Generating - Will it Make Power Again?

Поділитися
Вставка
  • Опубліковано 29 вер 2024
  • Jason found this generator on Facebook Marketplace for free! According to the previous owner, the engine runs but no power output. Is it a parts machine or will it make power again?
    Generator Model: PM0123250
    AVR Part#: 0069326SRV
    Predator Generator Not Making Power
    • Predator Generator Not...
    I no longer use Harbor Freight Super Heavy Duty Degreaser in my ultrasonic cleaner. Harbor Freight changed the recipe. The bottle previously stated "NON-CORROSIVE". Now it says "CORROSIVE", "do not user on Aluminum". It now damages most carburetors. Recently I have been using Simple Green PRO HD with good results.
    Visit My Amazon Store:
    www.amazon.com...
    Amprobe ACDC-52NAV: amzn.to/3vRgRy7
    Kill A Watt: amzn.to/3Ui8WTU
    Mini Torch: amzn.to/4bZTku4
    Oscilloscope: amzn.to/3UkttqL
    Simple Green PRO HD: amzn.to/3UqsXGu
    Squeeze Bottle: amzn.to/4cW0GjF
    Test Tank: amzn.to/3wi6DXG
    If you want to donate to the channel, you can use the UA-cam "Super Thanks" feature or via PayPal: www.paypal.com...
    #Powermate #GeneratorRepair #Generator #SmallEngineRepair #SmallEngine #DIY #Fixed #Troubleshooting #HowTo
    120 volts, AVR Error, AVR Install, AVR Replacement, AVR, Adjust Voltage, Alternator, Bad AVR, Bad Fuel, Bad Gas, Carburetor Rebuilt, DPE Winding, Fixed, Generator Head Test, Generator, Ground Fault, Hertz, How To, How-To, Insulation Test, Load Test, Low Voltage, No Output, No Power, No Voltage, No spark, Part Shortage, Predator AVR, Repair, Rusty Bowl, Sense Winding, Small Engine, Spark Plug Boot, Stalling, Stalls, Stuck Main Jet, Surging, Troubleshooting, Unbalanced Load, Water in Fuel, Will Not Start, Won't Run

КОМЕНТАРІ • 265

  • @Bassguitarist1985
    @Bassguitarist1985 3 місяці тому +46

    James, check all the connections, specifically the neutral lug. Anytime a load on L1 drops volts but volts increase on L2 is a sign of a loose neutral lug. This is a common problem and can destroy connected equipment. I'm guessing there is high resistance building up somewhere, either in the outlet panel, end bell terminal block, or worst case the center tap in the stator is flaky. Great video as always!

    • @jcondon1
      @jcondon1  3 місяці тому +23

      I would think a load on L1 would pull voltage down on L1 and the AVR would increase power to the field to maintain L1 voltage which would then cause an overvoltage in the unloaded leg. Will have to try this on another generator. The terminals were clean, but resistance was a little high going through one of the circuit breakers.

    • @Bassguitarist1985
      @Bassguitarist1985 3 місяці тому +11

      @@jcondon1 Exactly. The AVR is using 1/2 of the split phase at 120 volts as a sense winding to adjust its current to the rotor field. It shouldn't matter which leg it is on both legs should be balanced since the returning current should go back on the neutral. High resistance will make an adverse voltage spike on one side that is not equally loaded.

    • @jeffclark2725
      @jeffclark2725 3 місяці тому +3

      @@Bassguitarist1985 Agree with that thinking, almost need a second AVR for the second leg to prevent the over voltage but stay balanced to the first leg, would have to do some thinking on how to make all that all work out , or i am overthinking all this

    • @Bassguitarist1985
      @Bassguitarist1985 3 місяці тому +4

      @@jeffclark2725 no need for a second AVR. There's definitely something going on with the neutral lug or one of the jumpers perhaps. High resistance somewhere is causing that voltage imbalance.

    • @jeffclark2725
      @jeffclark2725 3 місяці тому +5

      i wish i would have known you and James 10-15 years ago, thinking back to the generators i could have fixed and saved compared to what as not saved with the knowlege today thanks

  • @stoyantsalev3109
    @stoyantsalev3109 3 місяці тому +20

    Ah, the infamous ungenerator... Or degenerator? Not sure...

  • @Amy_McFarland
    @Amy_McFarland 3 місяці тому +8

    Can you update whether or not you get the new AVR? And if you do get it, maybe load test again that would cool too see the difference in performance.

    • @mkortmann
      @mkortmann 3 місяці тому +2

      Another AVR will not change the behavior; it's designed this way with these generators. An inverter, for example, can work differently.

    • @philliphall5198
      @philliphall5198 3 місяці тому +2

      Yes put the correct one back and let’s see what the difference is 😊

    • @jcondon1
      @jcondon1  3 місяці тому +6

      I would like to do that. Hopefully it eventually ships. I would think the same 10 volts swing would be there. Instead it would be distributed better. When L1 was loaded the output was L1: 119v and L2: 130v. Would think with an AVR that monitor the 240 it would look more like L1: 115v and L2: 125v.

    • @philliphall5198
      @philliphall5198 3 місяці тому +2

      @@jcondon1 I’m allway impressed with your knowledge and disire to see how it works and effects the overall outcome
      Thanks from 105 west Texas

  • @notlisted-cl5ls
    @notlisted-cl5ls 3 місяці тому

    nice to see ya try to fix that chicom junk

  • @KaldekBoch
    @KaldekBoch 3 місяці тому +2

  • @pierrebrunet1529
    @pierrebrunet1529 3 місяці тому

    its fine if you have an known good avr but what is when you dont hqve one can you test it with voltage

  • @cjbowes998
    @cjbowes998 3 місяці тому

    The stator should act like a transformer with dual windings. Within limits, the voltage on both legs should be the same despite having an unbalanced load.

    • @eDoc2020
      @eDoc2020 3 місяці тому

      The imbalance is because the windings themselves are fairly high resistance, almost an ohm. The generated EMF is the same on each but 0.8 ohms gives excessive voltage drop on the loaded leg.

  • @notprovided2823
    @notprovided2823 3 місяці тому +19

    Your speaking style is a pleasure to listen to, as you describe what's happening. And your expertise is recognized and much appreciated. Nicely done, James!

  • @ron827
    @ron827 3 місяці тому +5

    James - 1, landfill - 0

  • @jamesward5721
    @jamesward5721 3 місяці тому +12

    We work on big, heavy, filthy, rusty vehicles all day every day - I always watch your videos with "workplace envy" James - small, light, nice & tidy - not fighting muck, rust, dirt, debris, big fastners that need gas-axing off, constant grinders hacking into mushed metal, working in spaces too small for any human to fit into, while wearing a welding mask, getting showered in hot metal, lol.
    Your version is like an oasis of calm in comparison to the utter chaos we have to work in. Watching you work is like man-yoga for the working brain. :-) Everyone here always says "If you can't function & work in utter claustrophobic chaos without your head melting, this ain't the job for you.."

  • @doughunt5175
    @doughunt5175 3 місяці тому +9

    I like using one size too small hose pliers. Put them in front of the hose & pull it off.

    • @jcondon1
      @jcondon1  3 місяці тому +2

      Good idea

    • @ericvaughn1126
      @ericvaughn1126 3 місяці тому +1

      I may try that too

    • @loganconner6814
      @loganconner6814 3 місяці тому

      @@jcondon1 Where could I find replacement "s.o." style cord, if I wanted to replace the main power wiring in my portable generator?

  • @loucinci3922
    @loucinci3922 3 місяці тому +3

    @14:24 you tested L1(Red) to ground. Then @ 14:38 to tested COMMON to ground. Thought you should have tested L2 (Black) to ground. ??? Just thinking what I would do and you kind of threw a curve ball at me. Got confused. Could you clarify?

    • @jcondon1
      @jcondon1  3 місяці тому +3

      L1 and L2 are just 2 coils of wire. It does not matter what end you test to ground since it’s just the other end of the same wire.

  • @restorick2378
    @restorick2378 3 місяці тому +10

    If you ever decide to create educational videos for genny repair, I'm all in! Fantastic videos - thank you!

    • @bobcarry4820
      @bobcarry4820 3 місяці тому +6

      If you watch his channel you will find a ton of genny repair videos. James goes into great detail on repairing generators, both motor and generator. He explains things as he goes and then does them. I have learned so much.

    • @restorick2378
      @restorick2378 3 місяці тому +3

      @@bobcarry4820 Indeed - I try not to miss any of the videos. I've learned a ton from James and appreciate his methods and tips/tricks. While I'm a pretty good mechanic and can work on any small engine, getting a theoretical understanding of how a generator works and related troubleshooting is where I fall short. I do appreciate his thorough explanations and I'm starting to pick up on basic testing. I've always wanted to learn as much as I can about the gear I have so I can properly maintain and troubleshoot when issues arise. But gennys are one piece where my baseline knowledge falls short. And as I approach my retirement, I'm working to learn as much as I can. My goal is to be the crazy old fart who fixes stuff for a dozen eggs or a chicken... ;-)

  • @cliffordreynolds1835
    @cliffordreynolds1835 3 місяці тому +12

    Good morning. Just found your channel. Love watching you fix stuff.

    • @stephenreiner1523
      @stephenreiner1523 3 місяці тому +1

      You're so sedate but at the same time thorough. Thank you James as always.

  • @philliphall5198
    @philliphall5198 3 місяці тому +4

    Change out the spark plug to ngk please and keep the old one for backup 😊

  • @KensSmallEngineRepair
    @KensSmallEngineRepair 3 місяці тому +3

    It took 3 hours, two coffees and a Tea to get through this one! Why would the AVR only address one leg?

    • @jcondon1
      @jcondon1  3 місяці тому +1

      Not sure. Seems kind of random. I guess the one that monitors only the 120 can be used in a generator that only produces 120v and 120/240.

  • @cobbleup
    @cobbleup 3 місяці тому +9

    I found an old 7000 watt generator at the dump a few years ago, Subaru engine ran good but no generator power. It has 2 big capacitors that didn’t spec out so I gambled and installed 2 new one of similar values and now it works great. 🤠

  • @mofoq
    @mofoq 3 місяці тому +2

    Always wondered if you'd ever make an universal AVR to use for testing/diagnostic purposes 🤔

  • @artpeck9272
    @artpeck9272 3 місяці тому +2

    You do know that there are special pliers for pushing a hose off a fitting. I’m sure Harbor Freight has them.

  • @RiverratGoRVing
    @RiverratGoRVing 3 місяці тому +3

    Thanks, James.
    Always the best information on troubleshooting.
    Keep posting.
    Michael

  • @gantmj
    @gantmj 3 місяці тому +6

    I have a Powermate near identical to this one, and a video you did where a breaker was bad helped me out.
    I didn't replace it like you did, but I drilled out the rivets and opened it up to see what was going on, and it was the way the external wire was pulling on it bent it and opened up the contact and let it arc some. I unbent it, used a nail file to clean both contact surfaces at once, closed it back up with small nuts and bolts, and reconnected the wire in a way that wouldn't pull on the terminal sideways.
    Didn't have to spend any money. Thanks.

    • @eDoc2020
      @eDoc2020 3 місяці тому

      Since a circuit breaker is a calibrated safety device I would replace it instead of bending the internals back into shape. If it was just a switch or relay it would be fine.

    • @gantmj
      @gantmj 3 місяці тому

      @@eDoc2020 The parts that do the breaking were not bent.

    • @eDoc2020
      @eDoc2020 3 місяці тому

      @@gantmj Then what was bent?

  • @philliphall5198
    @philliphall5198 3 місяці тому +6

    Great job but I think you should order the correct part just to keep it simple oem wiring because the next guy might get confused 😊

    • @jcondon1
      @jcondon1  3 місяці тому +7

      It is on order. Not sure I will ever get it :(

    • @philliphall5198
      @philliphall5198 3 місяці тому

      @@jcondon1I just ordered 1 k of parts and 25% was back ordered 😢😢😢

    • @jcondon1
      @jcondon1  3 місяці тому

      @@philliphall5198 that is what happened when I rebuilt the ttr125. Closer to 2k in parts. Most arrived within a week. The rest showed up 3+ months later :(

  • @jacksoncroyce6063
    @jacksoncroyce6063 3 місяці тому +3

    I look forward to Thursdays because of this channel. I have learned a lot. Thankyou, from England.

  • @GNX157
    @GNX157 3 місяці тому +4

    James, I recently got a free Ryobi RYI4022X inverter generator that was being put out to the curb for disposal. It was practically in new looking condition even though it had came out as a new model in 2019. The owner was quite sure he didn’t want it and said it wouldn’t start no matter what he did. He also broke the pull rope on the recoil starter from trying to start it so much. Anyway, the ultimate cause of it not starting was the low oil level sensor doing its job, and the owner (I’m guessing) not knowing the correct way to check the oil, as well as overall letting it get too low. On this model the dipstick plug should be unscrewed, the stick cleaned, and then the plug just set back in to measure the level, not screwed back in. On this engine, when I checked it, the oil level was just visible at the bottom of the stick, but only when the stick was screwed in all the (incorrect) way. Checked correctly, the oil didn’t even appear at all on the stick until I added over 8oz of oil, where 18oz is the correct capacity when full. So it was the low level sensor keeping the engine from starting and running. I also replaced the torch (junk) spark plug with an NGK, and the carburetor also needing cleaning as it would surge after starting. I added a good amount of Redline fuel system cleaner to the gas and after 30 minutes of running, the surging stopped. Now it starts and runs on the first or second pull.

    • @jcondon1
      @jcondon1  3 місяці тому

      It’s amazing how much stuff is thrown away for no reason. Good thing it had an oil sensor.

    • @petersack5074
      @petersack5074 Місяць тому

      @@jcondon1 Cause, of this ? NOT enough farms, for BOYS TO GROW UP TO BE real MEN. Farm life - naturally teaches ' all kids - about most everything ''. City life = no ' hands - on '' experiences......hence.....when something doesn't w o r k.......throw away. They don't realize, that ' learn by doing '' is A MODERN NECESSITY. ....anyway....(old farm kid)

  • @Rorschach1024
    @Rorschach1024 3 місяці тому +4

    How to make that AVR work is simple. Put two 10 Meg ohm resistors in series across the 240, and put the sense wires across one of the resistors

    • @eDoc2020
      @eDoc2020 3 місяці тому

      I'm 99% sure that wouldn't work. The AVR's input impedance is probably a few hundred kiloohms at most. Your divider's impedance would need to be many times less than this for proper functionality. A pair of 10k resistors would probably work but they'd be dissipating a few tens of watts.

  • @robertpeters9438
    @robertpeters9438 3 місяці тому +4

    I think if I bought a generator I'd also want a 2nd carb and AVR and fuel filter. And I'd be tempted to plumb an extra valve for draining the tank.

    • @philliphall5198
      @philliphall5198 3 місяці тому +1

      The extra value is a good idea for sure, seems the screen stops up alot with a full tank 😢😢😢

    • @philliphall5198
      @philliphall5198 3 місяці тому +2

      I do have a box with extra new carb , filter and hose plus several clamps
      Wife is disabled and I’m not taking chances 😊

    • @jcondon1
      @jcondon1  3 місяці тому +2

      Both are cheap insurance.

    • @rcf8367
      @rcf8367 3 місяці тому +2

      Plus a set of brushes

  • @swampy1584
    @swampy1584 3 місяці тому +2

    By the look of that old fuel that genny was diabetic 😂

  • @richardphelan8414
    @richardphelan8414 3 місяці тому +4

    very interesting analysis Jim on the AVR and How it monitors the load ,balancing the load a important factor ,and that sign wave was ugly and seriously clipping under load

  • @RossReedstrom
    @RossReedstrom 3 місяці тому +3

    I've got this "small" generator's little brother: model PM103007 3000W generator. Picked it up from a clearance website for approx $200 after riding through hurricane Ike and 15 days of no power. Has served us well for other storms as well as the deep freeze from a couple years ago that took out the Texas grid.
    Only problem wit it is I let the tank rust quite a bit, and when cleaning it out, added some acid and sort of got busy: a week later, it had removed the rust, as well as a good bit of the rest of the tank bottom. I use the generator with an external tank, set up to gravity feed from a plastic lawn chair next to the generator. Makes keeping it running easy enough, since I can refuel on the fly, a couple feet away from the hot engine, instead of right on top of it.

  • @anthonysummy6944
    @anthonysummy6944 3 місяці тому +8

    James, just a quick note on THD and sensitive electronics, and this comment comes with a strong caveat, which I will get to in a moment.
    First, most NEWER electronics use switching power supplies. The first thing that a newer switching power supply does is rectify the AC into DC before inverting it back to the proper DC voltage for the electronics. Power supplies of this design are impervious to the quality of the sine wave, since they rectify it immediately. It's pretty easy to tell if the electronics uses a switching power supply because on it's label, it will specify that the input voltage can be anything within the rage of 100-240v (or similar).
    Second, the caveat; if the device calls out 120v, or if it has a switch to select between 120v & 240v, or if it has a power transformer at all, then it is likely NOT a switching power supply, and would be highly sensitive to dirty power. When plugging devices like this into a non-inverter generator, one should always use a UPS (inline battery backup, the always-on type, not the consumer grade "standby" UPS) or a line conditioner.
    In summary, you're definitely not wrong; dirty power poses a huge risk to some sensitive electronics, just not ALL sensitive electronics. If your electronic device uses a universal (100-240v) power supply, it's perfectly alright to plug it into dirty power.
    I love our videos. It's one of the highlights of my week. I look forward to Thursday mornings, because I can watch your newest video!

    • @tomschmidt381
      @tomschmidt381 3 місяці тому +3

      I agree with your description of SMPS. However I want to add a caveat, most high wattage SMPS now include power factor correction. I don't know how sensitive they are to poor poor factor. Also some small supplies (LED lights etc) use a capacitive dropper so are sensitive to high frequency noise. Being a capacitor the higher frequency results in higher output voltage.
      That being said so far have not had a problem using our old school HF Predator genie but then we do not have a lot of hours. Buying a generator seems to have kept power failures at bay.

    • @pootispiker2866
      @pootispiker2866 3 місяці тому +2

      This is mostly guessing in a mostly incorrect comment. It's silly, really. Just google this stuff. It's okay to not know. It's not okay to act like you do.
      Power supplies that have a voltage selection switch are almost always switching power supplies but lack active power factor correction. Active PFC uses a boost converter to maintain a constant voltage on the high voltage DC side. It doesn't need a selection switch because the circuitry can accept the entire range of 100-240VDC. It will care about the input waveform, but only if it's extreme like a dirty square wave or just straight DC. Modified sine wave is built into the design considerations because of UPSs becoming popular. When there is a 115/230v (or similar) switch on it, the power supply does not have active PFC and at best uses passive PFC. Generally something like coils. While these care about the voltages, they don't really care about the waveform.
      Transformer power supplies care about both and consumer devices don't have a voltage switch. If it's made for 120 volts at 60 hertz, it can't be run at anything else without side effects.

    • @anthonysummy6944
      @anthonysummy6944 3 місяці тому +5

      @@pootispiker2866 My point about those power supplies with a voltage selector is that they WILL likely be more sensitive to a dirty waveform, because the high frequency component could affect the primary rectified voltage and result in an over-voltage condition at the switching device (SCR/MOS/Transistor/Etc). To say that my comment was "mostly guessing" seems a bit harsh and personal. I spent the better part of my career in electronics and computer hardware (12 years at RCA and 25 years at HP) so I do know a fair amount about the behavior of switching power supplies. You're correct in that some power supplies with input voltage selector switches are switching type power supplies, but not all of them are. In any case, they are far more sensitive to a dirty waveform than a power supply that accepts the full range 100-240v.
      In the end, my comment is still true that a modern switching full-range power supply that accepts 100-240v, will not likely be affected by a dirty waveform, and even if it is, not by much.
      EDIT: As I reread my post, I want to add this. Dirty power is NEVER as good as clean power, no matter what design or technology the device being powered is using. Even the best full range switching power supply will work better if it has clean power. PERIOD! Dirty power contains frequencies and waveforms that are not supposed to be there, and CAN affect even the best designed power supplies.
      I never intended my original post to spark a debate. I only intended to point out that a well designed power supply is better at handling dirty power, and is more impervious to these little portable generators. It is still (and always has been) a risk to run sensitive electronics on a generator that produces dirty power!

    • @jeffclark2725
      @jeffclark2725 3 місяці тому +2

      @@anthonysummy6944 I see where you are coming from, I remember when these little 2k suitcase generators came out 20 years ago, the inverter as highly advertised as to make the generators safe to run electronic stuff on without issue,that dirty power as a big selling point, then the AVRs came out and was the second solution, he still fixes a lot of these gen sets, thumbs up, that yellow Kipor he just got going was one of those inverter models, would like to see more testing with that one

    • @Critical-Thinker895
      @Critical-Thinker895 3 місяці тому +1

      The replies to your comment are funny. I would just add that in real life our sensitive electronics not only use switching power supplies but they come with a "bad power" signal that notifies our device when they need to shut down. All computers include this and have for many years. I'm glad you commented about this because it applies to more than 95% of people out there. The theorists and people who buy weird cheaper equipment can have their fun with you but you are correct for the real world.

  • @tom.2340
    @tom.2340 3 місяці тому +1

    I have a similar genny...behaving the same way as yours. Thanks for the information as always. Your videos are very helpful. Curious if you found a wiring diagram or schematic for this one.

  • @brianwood5220
    @brianwood5220 3 місяці тому +4

    Nice rescue, James. Thanks for sharing.

  • @rayb4838
    @rayb4838 3 місяці тому +1

    James, so tell us what the new purple cleaner is that you are using in the ultrasonic.
    I am still using the Heavy Duty cleaner from Harbor Freight!

  • @johnsalmon2501
    @johnsalmon2501 3 місяці тому +3

    Great video! Great job bring it back to life! Enjoyed watching.

  • @larrycleeton
    @larrycleeton 3 місяці тому +2

    It always amazes me how much water you find in the fuel. I've never had that occur with my equipment. How does it happen? Do they leave the equipment out in the rain?

    • @jcondon1
      @jcondon1  3 місяці тому +4

      Sometime it’s left out in the rain. This machine looked clean so likely just the ethanol in the old fuel pulling water out of the air.

    • @Fred2-123
      @Fred2-123 3 місяці тому

      Swings in temperature will suck air in and out of the tank. Moisture in the incoming air will condense in the tank. Plus the ethanol, because most people don't hunt for ethanol-free gas.

  • @YukonHawk1
    @YukonHawk1 3 місяці тому +2

    Definitely not a generator for sensitive electronics 😅. But in a pinch it will come in handy to save the day.

  • @brouwereric644
    @brouwereric644 3 місяці тому +2

    @ 23:26.... I like your DMM stand. Very professional.

  • @Paberu85
    @Paberu85 3 місяці тому +1

    Main function of AVR is to compensate for engine RPM drop and fluctuations under load (or load release, along with mechanical governer which is not always sufficient, flexible, fast enough). Having non original AVR monitoring one phase is adequate enough. When engine is loaded AVR will compensate for RPM drop for both phases, loaded and unloaded one. If you don't want to waste money on new AVR and still monitor both phases just throw in a 50/50 resistive voltage divider - 2 resistors 50kOhm each rated at 1W, you will monitor 2 phases difference (240V) but scaled down to acceptable by AVR level of 120V. I bet monitoring circuit don't need much current, so 50kOhm should do the trick, if not - make resistance a bit lower, 30kOhm or so.

  • @Floridabruce1960
    @Floridabruce1960 3 місяці тому +1

    When you were spraying the starting fluid in the carburator you had the gas turned off again. 🙂

  • @melkiorwiseman5234
    @melkiorwiseman5234 3 місяці тому +3

    That was another good save. It's funny, but I've never thought about the "legs" needing to be balanced, in all of the videos you've shown here. That may partly be because on this side of the world, we only use 240V so even if the generator internally uses two 120V "legs," they'd always be used together with an equal load on both.
    My generator repair is (I hope) in the final stages. I pulled the carb off again and checked the fuel line for blockages. No blockage so it just about has to be the main jet which is too small, so I drilled it out one more size. I noticed that one of the carb mounting bolts got its threads stripped (must be my fault, I guess - no way to measure and set the force I use to tighten the nuts) and one bolt would no longer tighten. In the end, I purchased a "vice clamp" and used that to unscrew the mounting bolt, then reversed it and screwed it back in so that I'd have clean threads to allow me to tighten both bolts properly.
    Unfortunately, by the time I got done with all of that, it was already getting late into the evening and because I don't want to bother the neighbours, I'm leaving it until tomorrow to see how it runs now (and hoping it runs properly at last).
    It's ironically amusing that you couldn't get that jet out even with the impact, since I had the same problem with the original carb and so in the end had to buy a new one since the old one was so badly gummed up that it couldn't be cleaned. It's even more ironic because the carb is exactly the same as the one on the genny in this video.
    Keep on keeping on, James. You have many people here who love watching your videos, and they definitely "help someone" like me. 😄

    • @jcondon1
      @jcondon1  3 місяці тому +4

      It definitely would not be an issue if only pulling 240v. Some of these generators are made with a switch to put in 120v only mode. Its great because it automatically balances the load and distributes the load evenly across the legs. Of coarse then you have no 240 :(. Hope your generator is fixed. Sometimes they can be a challenge.

    • @melkiorwiseman5234
      @melkiorwiseman5234 3 місяці тому +1

      @@jcondon1 Update: Hooray! It seems to finally be running correctly, with no die-out when the choke is turned off, and running okay even under a 1000W load (it's rated for 1500W continuous). There's some slight surging, but not too bad. The only thing I'm not sure of is the frequency. I have no way of checking if it's going over, under or right on the correct frequency. My frequency meter doesn't seem to like counting the pulses on the 12V DC output (flickers constantly through values as low as 33 and as high as the 300's, when I'd expect it to be 100Hz at our 50Hz mains frequency). It would be a bad idea to connect the meter directly to the 240V output since it's only rated for something like 30V, so I might need to try putting a 240V-12V step-down transformer in there and see if that gives me any joy. I'm now in the middle of changing the oil. The old oil doesn't look bad (still has a hint of the original colour) but I'm changing it anyway because it's been years, even though it's low-hours.
      Edit to add: I got a sound frequency app for my phone and it's showing around 1300Hz. Since this is a 4-stroke engine, that means it fires once every 2 rotations, which means that it must be running at around 2600 RPM. Checking the speed of generators on this side of the world, it seems that they need to run at 3000 RPM to get 50Hz so I need to bring that frequency up to 1500Hz. I'll do that a bit later, though. (Ugh! I do not like being older and disabled)

  • @Justicesdad
    @Justicesdad 3 місяці тому +1

    Jimmy, have you ever thought about designing your own generator? You have to be as knowledgeable as the companies that manufacture these thing, make a better one with all the things you wish they would incorporate

    • @jcondon1
      @jcondon1  3 місяці тому

      I have a list of things I would like to see if I ever get the chance to design one. Problem is the price likely would be a lot higher.

  • @thomasklosterman9870
    @thomasklosterman9870 3 місяці тому +1

    James, what kind of purple degreaser are you using in your ultrasonic cleaner?

    • @jcondon1
      @jcondon1  3 місяці тому +3

      Simple Green Pro HD

  • @curtisking2962
    @curtisking2962 3 місяці тому +5

    Good Thursday morning, again.

  • @10forthebigguy753
    @10forthebigguy753 3 місяці тому +3

    Getting ready for hurricane season. I’m load testing my small PowerMate. Is one amp at 120 V equal to 81 W 100 W or 120 W.

    • @frankwrogg2515
      @frankwrogg2515 3 місяці тому +1

      Google says 120w = 1 amp

    • @jcondon1
      @jcondon1  3 місяці тому +3

      One amp is 120 watts. Volts x amps = watts. Of coarse that is assuming your generator is producing 130 volts. One amp at 240 volts is 240 watts.

    • @eDoc2020
      @eDoc2020 3 місяці тому +1

      To be a bit more technical, 1 amp at 120V is 120VA of apparent power. The actual wattage depends on the power factor. For a resistive load like a space heater the PF is 1 so 120VA is 100W. Motor-based appliances or older electronics have a distorted current waveform so the PF is lower. This means it draws more current and VA for the same number of watts. Conversely, it consumes fewer watts per amp.

  • @danamanner9441
    @danamanner9441 3 місяці тому +2

    Interesting test of voltage on both legs under load.

  • @ScottDLR
    @ScottDLR 3 місяці тому +1

    Great channel. FWIW, I really enjoy your style of vids and I've learned a ton - thanks!

  • @Bud_51
    @Bud_51 3 місяці тому +1

    It's certainly worth buying the correct regulator for it...

  • @williamjones4483
    @williamjones4483 3 місяці тому +2

    After you've filtered out all of the water and impurities, couldn't you just pour the gas in your vehicle's fuel tank and burn it?

    • @snowflakemelter1172
      @snowflakemelter1172 3 місяці тому +2

      Stale petrol can be used up if added to fresh fuel say 25%.

    • @jcondon1
      @jcondon1  3 місяці тому +3

      I ended up doing just that. It was bad fuel, but not usable. Sometimes it’s just so bad I do not want to risk clogging the fuel filter in my car since the tank has to be removed to service it.

  • @elesjuan
    @elesjuan 3 місяці тому +1

    About seven years ago, I bought a Harbor Freight 4kw genset off craigslist that was "new in box, damaged" for about a hundred fifty bucks. The box had water damage, and the exterior lower chassis bolts had rust visible but the oil looked fresh so I went ahead and purcahsed it. Got home, filled up with some non-ethanol gasoline, checked the oil which was clean, and proceeded to run the break in period. After that, ran it out of fuel and squirreled away in my garage for a rainy day. That day came last week, in 2024. Dad called me and told me his power got taken out by a storm, and its rather warm right now... This would be the third time this calendar year he had to throw out the contents of his fridge and freezer. Naw. Told him I'd drop my genset off which he could run for a few hours to "recharge" his fridge and save his food.
    Figured before I Loaded up the genset in the car and headed his way, I should make sure it runs.... Spoiler: It didn't. Apparently running its tank dry didn't do didley squat to drain the carb. Oops. Thankfully, I'm not only a long-term subscriber of this channel, but Mustie1 and knew exactly what needed to be done in order to get this engine up and running at 100 percent. Twenty-five minutes of work later and my genset was running TIP TOP. Took it over to dads place and saved the day. His neighbors were none too happy, but that's their problem.

  • @watermanone7567
    @watermanone7567 3 місяці тому +1

    Nice work James: Ethanol fuel causes those carbs to plug up like that. I keep telling my customers to not use it, to no avail. Thanks for the video.

  • @aleblanc3547
    @aleblanc3547 3 місяці тому +2

    You may have already done this, but could you explain what a good sine wave should look like verses a bad one and why that should be of concern? Isn’t it enough to have the proper voltage and correct Hz (cycles)?

    • @jcondon1
      @jcondon1  3 місяці тому +7

      The proper voltage and hertz are important. THD is the measure of other frequencies in the output besides the primary. In this case we want 60 hertz. 0% THD would mean that only 60 hertz is in the output. In this case we maxed out at 27% THD. That indicates that 27% of the output were other frequencies (harmonics) beside 60 hertz. Devices cannot use that power and instead dissipate that unwanted energy as heat. It can lead to failures in sensitive electronics.

    • @aleblanc3547
      @aleblanc3547 3 місяці тому +2

      @@jcondon1 great explanation. I didn’t know about the excess heat and fully understand how if the heat has to be dissipated and a computer or other small devices would have trouble with that. Thank you!!

    • @eDoc2020
      @eDoc2020 3 місяці тому +1

      @@aleblanc3547 Different devices care about different parameters of the waveform. Most things you might think are "sensitive" like computer power supplies and phone chargers actually care very little about the power quality. Things you think won't care (like a cheap LED light bulb) care about slew rate so the higher harmonics will cause extra current flow. Other things like motors only care about lower harmonics.

  • @imysteryman
    @imysteryman 3 місяці тому +1

    The thing I don't care to much about in most generators is they are a 2 pole and require 3600 rpm and they make a lot of noise. The 4 pole generators run at 1800 rpm and are much quieter, surely they should last a bunch longer since they are not screaming.

    • @johnhardasnails7464
      @johnhardasnails7464 3 місяці тому

      Yes you are right about 1800 rpm generators ! Usually they are diesel engine type running slower. Occasionally some large gas units run at 1800 rpm but very rare. Generac has 1 liter 15-17kw gas units running at 3600 rpm still. The standby 25-30 kw generators running propane or natural gas are 3600 as well. The water cooled generators may run at 1800rpm but those are in line 4-6 cyl or even v8 to get the torque needed when on natural gas to generate high kw requirements

  • @jaydee7454
    @jaydee7454 3 місяці тому +1

    a small amount of metholated spirits in the tank will surround those water droplets and allow them to pass through the carby and be burnt

  • @randycoureton-te4im
    @randycoureton-te4im 6 днів тому +1

    I’m having trouble with a Honda clone. Do u have a list I can go from on checking everything. I can’t find a problem and I bought a new avr but still not making power.

    • @randycoureton-te4im
      @randycoureton-te4im 6 днів тому

      I’ve watch several of your videos and you really have a great talent

    • @jcondon1
      @jcondon1  6 днів тому +1

      Thanks. I do have a play list on no power troubleshooting: ua-cam.com/play/PLoj6DvbhMTzs2Xhx82Wsj7-quXNATsdv5.html&si=ZmHk-B6JX-BcC9VS

  • @rodneymiddleton9624
    @rodneymiddleton9624 3 місяці тому +1

    Nice job!! Great find on the replacement AVR from the Predator. I'll have to remember that. Thanks Jim!

  • @tdevosodense
    @tdevosodense 3 місяці тому +1

    Why not adjusting the voltage while its running ? 🤔🤔 Just put on rubber gloves 👍

    • @Fred2-123
      @Fred2-123 3 місяці тому

      One accidental slip could cause a short and destroy the generator.

  • @larrynash7940
    @larrynash7940 3 місяці тому +2

    Would cleaning the slip rings improve the sine wave?

    • @jcondon1
      @jcondon1  3 місяці тому

      It would help a little if they were really dirty.

    • @larrynash7940
      @larrynash7940 3 місяці тому

      What causes a good or bad waveform?

  • @robertmorin6495
    @robertmorin6495 3 місяці тому

    Leg two went to 119 volts after a load was placed back onto leg one. The only time it read 130 volts was when only leg one was in use, and no load was on leg two. This setup should be fine as long as leg one has a load before using leg two. The AVR is affecting both legs because of why James said: increased power to the field

  • @richb419
    @richb419 3 місяці тому +1

    Hi James, good video. for loosing bolts and screws I was instructed to place an appreciate bar or screwdriver on the fastener and strike with a hammer, that drives it into the threads enough to loosen it enough for removal. I mostly used that for bleeders on brake cylinders.
    Rich

  • @mikecalvin1402
    @mikecalvin1402 3 місяці тому +1

    🎉🎉🎉🎉🎉🎉🎉🎉🎉😅😅😅😅😅😅😅😅😅

  • @petersack5074
    @petersack5074 Місяць тому

    Hi, thankyou for all the education. I have a Suzuki SE 3000 AD . Yellow, older model. Was working good, then started to kinda growl - like it was overworked. i unplugged the rectangular, AVR from the brushes - the 3-4 pin connector. Started to pickup RPM to 3600 again. ? Question . Is something shorted (rotor - stator ? ) or is the AVR gone ka-put ? Thanks, for all you do.....(brushes in good condition, no burning/rotten egg smells coming from it ).

  • @jamestobler8473
    @jamestobler8473 3 місяці тому +1

    The expression is ( leave well enough alone ).

  • @brandonoh777
    @brandonoh777 2 місяці тому

    Would anybody have an idea of approximately what the windings of a Harbor Freight Tailgater 2-cycle 63 CC generator winding should be? There's four wires coming out of the powerhead 2 Reds and 2 Browns... The 2 Reds go to the outlet through a breaker the 2 Browns go to a capacitor.. I disconnected all four of them I get 1.9 ohms Reds (120v) and 7.8 ohms browns... it's worked for a long long time it just stopped making power while it was running last weekend... I also tested the capacitor it's supposed to be 12 microfarad +- 5% and it tested to be about 10.55 microfarad so outside the 5% quite a bit...any ideas? I also tested both Reds and both Browns for a short to ground and found none

  • @davegibson4255
    @davegibson4255 Місяць тому

    Dude to people who don’t have a clue you shouldn’t be their leader. The way you throw your stuff around bolts nuts tools generators is crazy. Then you forced that bolt until it broke when it was still on the rubber mounts even though you removed the nuts was still holding the stator there is always a way to remove parts so your logic of force until something breaks is ridiculous! And the Rotor ROTATES and the Stator STAYS Please call them properly if you are teaching. As well use a torque wrench especially on the electrical connections in a 3600rpm vibration environment. I’m sure you know how the aluminum case breaks because you’ve broken it /them before. Your use of the word UMMM is very professional and informative at beginning of most sentences. I would hope you take my criticism seriously and either learn from it!

  • @leroijr407
    @leroijr407 Місяць тому

    Hi james. No one local seems to know how ti fix my Champion 10k starting watt generator. The ohms to the slip rings are 65. 75-78 through brushes. Exciter 2 blue wires have 1.5 ohms, the other 2 are .5 ohms. Whej started, i get only 22 volts ac at one if the 120v plug outlets, and no voltage on the other 120v outlet. When testing resistance on the 240v plug, i get .5 or .6 ohms on each leg. None of the stator wires are shorted to ground, and none of the 4 wires going to the avr are shorted to ground. ARV has been swapped 2 times, new, still same. Stator wires test good, but bottom wrapping is very dark black. Can the ohms test ok on the stator 3 wires but still be bad? 8 need your master skills my friend. Please help me. In florida and i need this bad. Thank you.

  • @kirkc5823
    @kirkc5823 3 місяці тому

    Hello again,
    I have an older Generac 5500XL. It was only making power in 1 of the 2 120v sockets( nothing in the 240v socket) so I pulled the electric panel cover and found a broken 120v socket broken with the lean completely separated from the socket. So I took a picture bought a new one and installed it exactly as the broken one was wired, now I get 0, no voltage from any socket. They all have continuity all the breakers have continuity but no voltage anywhere. Any ideas? There was around 20 ohms through the brushes which looked fine, windings looked fine from what I could see ,but it's older and completely different from anything I have seen you working on, no avr, no terminal block wires all just push connectors that run back into the generator head...

  • @stragenmitsuko
    @stragenmitsuko 3 місяці тому

    James ,what could cause an engine ( briggs&stratton 10.5Hp riding mower ) to suddenly run pig rich .Black smoke , no power , engine stalls . Coke's off and not blocked . Ran fine for years and then suddenly this happend . Haven't got a clue where to start really . Cleaned the carb ,no avail . New plug , no avail .

  • @KevinRodriguez-rp1rw
    @KevinRodriguez-rp1rw 3 місяці тому

    Hello James I really like you channel, I purchased in 2006 three Coleman Paul meats 5000 6250 max and I’ve never had a problem with any of them just done my normal maintenance. Looking for a older power mate that has a 30 amp plug because I moved to Texas and I want to run a a 3 ton AC unit with a soft start do you know what the largest watch they made and do you know where I can purchase one thank you for all you do I appreciate it

  • @bazzmac4094
    @bazzmac4094 3 місяці тому

    James,
    Would you consider doing a short video explaining the differences between inverter, brushed and brushless generators - particularly the advantages and disadvantages of each type? And what applications each is suitable for?
    Thanks

  • @benjamincresswell3713
    @benjamincresswell3713 3 місяці тому

    Hi , Nice job going thru the normal stuff and trouble shooting the electronics. I would say, what we have here is a product of today's quality control. It could be a corroded copper or brass wire end or even the pinch making the connection, but my experience with the way companies do things today is they cut corners and leave "well enough" alone. I have heard a statement for many many years now: " Good enough for who it's for." I really don't care for that statement, except for when who it's for is me and I'm the one deciding upon the value of pursuing a better outcome. I would never allow that thinking process to govern the placement of unit onto the public at large. But, and sadly in my opinion, excellence is NOT something that all companies strive for these days. Or, as Taryl Fixes all says, "it ain't the space shuttle." So, in that case you get what you pay for. Another phrase I don't care for. I worked in GM engineering for 36yrs and I saw first hand how we went back to the drawing board (or breadboard) and started over until we got exactly what we were looking for. Doing things that way is not cheap, but research and development never really is. A standby generator is not that important, at least not a couple of kilowatt generator. Thank you for taking the time to do the balance test, it was interesting to think about. ben/ michigan

  • @noelcastle3986
    @noelcastle3986 3 місяці тому

    Not impressed with that generator using the 120volt AVR the 240 AVR probably a big improvement plus its prettty poor THD . And its struggling to maintain its running rated load , couldnt imagine it doing that for too long at 3000watts. Must be a very cheap machine i wouldn't risk it on sensitive loads or near rated loads.

  • @oldodger
    @oldodger 3 місяці тому +2

    Great content, great presentation.

  • @Barracuda48082
    @Barracuda48082 3 місяці тому +1

    What would be the reason to monitor only one winding knowing most uses are 120v loads, and a few 240v ? Build cost? Results would end up over loading one half of powerhead if the rated wattage was reached on the half.
    In my opinion, monitoring both would be a plus for the manufacturer for dependability.
    I see many labeled with watts but unless it is listed in the manual, we can only take the safe choice as that number being the surge or peak startup rate.
    James, another good video..
    As my father used to do, cotton ball in a funnel, screen fuel going into any tank !

    • @jcondon1
      @jcondon1  3 місяці тому +1

      Monitoring the 240 would be more accurate. Still though there would be a 10 volt difference. When loading L1, we saw L1 voltage go to 119v and L2 130v. If it monitoring the 240 output, then would expect to see the same 10v difference but distributed more evenly across the legs. Something more like L1: 115v, L2: 125v.

    • @watermanone7567
      @watermanone7567 3 місяці тому

      The ethanol fuel is causing the water in the tank, not usually from the gas station. Ethanol pulls the moisture from the air as the temp changes from day to night, the tank expands during the warm day and as the night air cool the tank pulls in the humid night air and the tanks ends up with lots of water in it.

  • @johnclyne6350
    @johnclyne6350 3 місяці тому

    I've swapped out the battery because it was three years old. Cost as much as a good car battery. I change the oil once a year & put Mobil 1 in mine. I clean it twice a year & syphon the gas out every year & put in fresh fuel with Star Tron fuel enzyme & Marine grade Stabil. I never have stale fuel but to be safe I put gas a year old in my vehicles.
    I bought a gallon of straight gas for my gas powered Honda ground rod driver. It's a 4 stroke. I added both preservatives three years ago & it's still good. It only drives ground rods. Costs $3000 new.

  • @eliotmansfield
    @eliotmansfield 3 місяці тому +1

    so glad we use 240v here in europe.

  • @REVNUMANEWBERN
    @REVNUMANEWBERN 3 місяці тому

    I've got a B&S Gen, think it's a 10000 , what would you suggest is the top 5 in order of failure would be the parts to fail? I'm thinking IF I can still get those parts maybe I need to get them to shelf for possible future use, & I mean the electronic parts only because I converted to propane so I have no carb issues

  • @robertmailhos8159
    @robertmailhos8159 3 місяці тому +1

    I'm thinking of The AVR isn't working on this Gen set

  • @centauri61032
    @centauri61032 3 місяці тому

    Interesting... I always assumed the AVR would monitor the voltage across the 240v on a generator, thereby essentially checking both legs. I never considered that they would only monitor one of the legs and ignore the other. Seems like a design flaw to me.

  • @MitchEllis-dn9lf
    @MitchEllis-dn9lf 3 місяці тому

    James, I notice you quite often using a pull bar to loosen spark plugs and oil drain plugs. If you have half way decent ratchets they should be fine for all be the most stubborn spark plugs say.

  • @scottpecora371
    @scottpecora371 3 місяці тому

    I never try to start any machine I'm told won't start untilI'vee drained what's usually bad gas, drained the carb and added a quart of fresh fuel. Its amazing how many times the engine will stumble briefly then run fine!
    Never try to start an engine on old fuel!

  • @cusoonmyfriend3738
    @cusoonmyfriend3738 3 місяці тому

    Hi James thanks for the video
    i can get vanguard 5,5 BS generator for 100 euros, hasnt started in years, good deal ? looks brand new, no scratches etc

  • @robertcochran7103
    @robertcochran7103 3 місяці тому

    Do you think the capacitor on the original AVR unit can be desoldered and replaced with an identical new capacitor? That might not fix the problem though. I shall have to search around for old generators that are thrown out....

  • @lesmontgomery6498
    @lesmontgomery6498 3 місяці тому

    We used to put 12 volts dc to the brushes. This would usually produce about 75 vdc. If so all windings are usually good

  • @loganconner6814
    @loganconner6814 3 місяці тому

    Where could I find replacement "s.o." style cord, if I wanted to replace the main power wiring in my portable generator?

  • @nickk20571
    @nickk20571 3 місяці тому

    If they don't make that AVR anymore, you might be able to contact that guy again that did that one old small red generator that you did a video of that the guy remade it or something. Sad that we have working equipment's that they want to stop selling parts for.

  • @JoeMama-pb8hx
    @JoeMama-pb8hx 3 місяці тому

    Finally been able to do some maintenance on my generator after a few 🌪 tornadoes come through Ohio. It was over due after the 1st one but been so busy with cleanup. We had 49 within a month. Lots of trees in the road and i lost count on how poles that were damaged. And when the last one hit i was out in the woods riding my 4 wheeler and had a hard time trying to ge back up the one hill. Looked like a small river with how hard it was raining and lightning struck a tree 40 foot from where i was stuck at because of no 4 wheel drive

  • @kthwkr
    @kthwkr 3 місяці тому

    I think you are concluding that in the future always monitor both legs with dual Kill A Watts. That will be interesting.

  • @objection_your_honor
    @objection_your_honor 3 місяці тому

    The bulging cap is the fault.
    Since it's all potted, and a new one is only $25, one would be a fool or desperate, to try to fix it.

  • @WJCTechyman
    @WJCTechyman 3 місяці тому

    I have looked at Powermate as a budget option with plastic fuel tanks, incredibly basic alternators that have a plastic end bell and this thing seems to show similarities.

  • @Joseph-u6d
    @Joseph-u6d 2 дні тому

    Just watching you pull so many times!?!?!?😢😢😢

  •  3 місяці тому

    AVR monitoring only one leg is one of the usual pitfalls with the cheap threephase Generators over here in europe. if you have high load on the monitored phase the voltage on the other two will go through the roof and damage equipment. this it one of the many reasons why you should not feed your house (which is usually fed by three phases over here) drectly with a generator, unless you have very even loads on these phases.

  • @harrygregory6227
    @harrygregory6227 3 місяці тому

    I love watching your videos, also where can I get a replacement disc drive for a ps2 fat?

  • @chrisk5433
    @chrisk5433 3 місяці тому

    The THD for this generator seem worse than most. Would cleaning the rings and putting a new set of brushes clean up the output at all?

  • @philoso377
    @philoso377 28 днів тому

    Nice video and presentation.
    Since these generator operates a single correction loop on single field coil to drive two independent output coils A and B. It is unreasonable to expect balance coil voltages. Unless we have independent field windings to drive each output windings.

  • @artpeck9272
    @artpeck9272 3 місяці тому

    One word …. Kroil. I’ve seen gun restorers use it on hopelessly rusty weapons with astonishing results.

  • @larrrs3
    @larrrs3 3 місяці тому +1

    I use the old fuel to light my fire pit while camping. No waste.

    • @FlushCut
      @FlushCut 3 місяці тому

      Dumb.

    • @larrrs3
      @larrrs3 3 місяці тому

      @@FlushCut you only use 2 to 3 ounces. Really old gas burns but doesn't flash up.
      I worked in a laboratory for over 20 years and more than once had to have old chemicals hauled off it's very very expensive and before you say just take it to a haz waste collection center it's very expensive for the city that put on the event and I happen to know this because I ran the hazwoper program for over 20 years too.

  • @loucinci3922
    @loucinci3922 3 місяці тому +1

    Enjoyed the video. Thanks for sharing

  • @Fred2-123
    @Fred2-123 3 місяці тому

    Since you had it open, why not check and clean the slip rings & brushes, too?

  • @danielneidinger9578
    @danielneidinger9578 3 місяці тому

    what brand is your replaceable tip screwdriver, kind of like it

  • @larrykelly2838
    @larrykelly2838 3 місяці тому +1

    Very interesting video.