York Chillers Down After Lightning Storm || Buildings Are Hot

Поділитися
Вставка
  • Опубліковано 7 січ 2025

КОМЕНТАРІ • 200

  • @asbestosfibers1325
    @asbestosfibers1325 Рік тому +30

    These comments are hilarious.
    How are you supposed to check voltage without over riding the cabinet switch lock....
    I feel sorry for all of yours lack of testicular fortitude.
    Ppe wont save you. It just keeps all the meat together so its easier to clean up.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +5

      Thanks asbestosfibers 👍👋😎

    • @ericapelz260
      @ericapelz260 Рік тому +3

      "Testicular" fortitude is not required. I've been in plenty of 480 V MDPs with and without PPE. Those are nice, new, and clean, so no worries. I would have checked the voltage on all three legs at the top, then checked continuity on the fuses, and then ohmed the coils, but we all approach diagnostics in our own way.

    • @brianroselli229
      @brianroselli229 Рік тому +1

      lol you are correct I'm guessing a lot of the folks that have commented never even seen a panel in person

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +2

      The burnt coils were easy to smell 👍

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +2

      👍👍

  • @willbran2887
    @willbran2887 Рік тому +11

    I worked as a Chief Operator for many years at a distillation plant that used a York Chiller to supply cooling water to the total condensers. It was a real pain when the chiller went down. Great job on troubleshooting and getting these chillers back on line.

  • @Keith_WB2VUO
    @Keith_WB2VUO Рік тому +1

    I did eddy current testing on chillers from 1984 until 2014. I can "feel" the noise in the room and smell all of the machinery. It brings back memories! Thanks cor your video!

    • @subcoolHVAC
      @subcoolHVAC  Рік тому

      Thanks for sharing, when it’s too quite you know something is wrong 😀

  • @billsmitrhg8137
    @billsmitrhg8137 Рік тому +4

    Finding a fault, getting that wind up sound when you push the button on a big, chiller, fan, press, for a bunch of hot grumpy customers. Love it. Sounds like victory.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +2

      Grumpy is correct, and want to know when it will be fixed as soon as you arrive. Thanks for the comment!

  • @debndave4871
    @debndave4871 Рік тому +7

    I worked as a chief engineer/supervisor in a hospital for many years. Dealt with this stuff on a daily basis. When storms roll through the tokus puckers up pretty quickly. We had 7 Carrier and York chillers, 50 air handlers and Tower Tech cooling towers. Retired early and no longer on call 24/7. I miss the daily challenges.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +2

      Thanks for sharing, congratulations! Less than 7 yrs to go for retirement here 👍

  • @thesilentonevictor
    @thesilentonevictor Рік тому +22

    When you know your way around its looks so simple

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +8

      I’m familiar with this chiller plant and it’s sequence of operation. Thank you for the comment !

  • @IanGSully
    @IanGSully 10 місяців тому +1

    That chiller that you started up I thought had one of the coolest startup sounds ever!!!

    • @subcoolHVAC
      @subcoolHVAC  10 місяців тому +1

      They do sound good on start up, but definitely need hearing protection when working in there awhile . 🎧

  • @davedrew9328
    @davedrew9328 Рік тому +1

    Really good took me back to when I was an Electrician in Croydon South London.

  • @stephenvale2624
    @stephenvale2624 Рік тому +15

    Any special reason for probing a live box without gloving up?

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +6

      No, Thanks for watching 👍

    • @cosmicinsane516
      @cosmicinsane516 Рік тому +11

      Because basically no one in the HVAC industry follows arc flash PPE requirements. I’m guilty of it myself.

  • @REWYRED
    @REWYRED Рік тому +9

    That design of starter and coil was made by FURNAS at one time until Siemens bought them out in the 90s.... Used to work at a supplier then and sold tons of Furnas motor control, that stuff was pretty robust.

  • @dannydaghavarian9185
    @dannydaghavarian9185 Рік тому +1

    Great find! Thanks for sharing! lot of love from Australia

  • @robertstonebreaker8394
    @robertstonebreaker8394 Рік тому +6

    Nice work safety always # 1

  • @pigrew
    @pigrew Рік тому +14

    I don't deal with industrial installations, but was there any sort of surge-protection installed in the cabinet? I wonder if they would have saved the coils.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +8

      There was, there were ahu’s starters around the site that lost coils and fuses too wasn’t just isolated to the plant

    • @LatitudeSky
      @LatitudeSky Рік тому +1

      Surge protection won't stop a direct hit from lightning. Or even a nearby hit. Had one hit outside my house where everything was on UPS units. Distance between strike and house was under one meter. It still smoked a lot of stuff. It even blew out items unplugged being stored on a shelf. Apparently there was a EMP of sorts given the very close range of the strike. The UPS units just could not mitigate that much that close and that quickly.

  • @fredsalter1915
    @fredsalter1915 Рік тому +4

    What is that button to the right of the breaker lever? Did you call it a "restarter"? Just curious because I work at a chemical plant and we have the same kind of setup. Is a restarter the same thing as that breaker lever? Thanks!!!!!!!!!!!!!

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +4

      It’s the overload reset button for the starter assembly, typically blue or black in color. Red is to test the overload relay. There is a button on the front panel that is supposed to allow reset without opening if lined up correctly. Thanks for commenting 👍

  • @ocsrc
    @ocsrc Рік тому +2

    Why is there no surge guard on these? I have a panel surge guard and I have had lightning strike twice and it blew it both times and I replaced it both times and it saved everything else from damage.

  • @zekenzy6486
    @zekenzy6486 8 місяців тому

    Great Video. Thank you for sharing

  • @RoaddogRoaddog
    @RoaddogRoaddog Рік тому +2

    Awesome 👏🏼 job

  • @brendakoldyk1647
    @brendakoldyk1647 Рік тому +17

    You may want to put a MOV across all the coils so that doesn't happen again they are cheep and fast acting so only the fuse will blow.

    • @whatevernamegoeshere3644
      @whatevernamegoeshere3644 Рік тому +9

      MOVs break down over time, leaking more and more current, so they need to be fused. That is something that is often forgotten about and not only they lead to wasted power but I have seen ones blow up and turn main distribution boards into hell on earth

    • @scowell
      @scowell Рік тому +4

      @@whatevernamegoeshere3644 Yep... they are one-shot devices... and you don't know when it fails open, only when it fails closed. After every strike replace all of them... that's why MOV's are a PITA.

    • @misterhat5823
      @misterhat5823 Рік тому +1

      @@scowellMOVs are not "one-shot devices," but they do degrade over time. Normally they fail with excessive leakage current. If they fail open, it's because they've burned open.

    • @joemilton7552
      @joemilton7552 Рік тому

      SPD right on the board

  • @ccthepope
    @ccthepope Рік тому +3

    wow, thanks for posting!

  • @hectortorres542
    @hectortorres542 Рік тому +1

    Thank you for the video.

  • @georgebrabec1749
    @georgebrabec1749 Рік тому +1

    Those are real fun at 3:45am. Hello McGiver tricks

  • @jrb_sland
    @jrb_sland Рік тому +13

    First things first - does your three-phase power exist? If the service is old enough to use big fuses, use a [properly rated] voltmeter to check for ~ zero volts across the three fuses. A blown fuse can throw a huge confusing factor into diagnoses. Great video, btw...

  • @generalmayhem9336
    @generalmayhem9336 Рік тому +3

    Very cool, no pun intended.

  • @ausseamore8386
    @ausseamore8386 Рік тому +1

    thanks for sharing

  • @BeezyKing99
    @BeezyKing99 Рік тому +20

    for hands free recording; I'd suggest a magnetic phone holder/mount so we can get nearly the same POV angle as you do when you gotta get into the cabinets for metering/repairs... definitely gonna stick around for more content, I always wondered how these beasts ticked compared to the regular HVAC equipment.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +3

      I use magnet camera mount when possible, did use on this video some, recording was a last minute thought, getting the plant up and going was priority. Thanks for watching

    • @BeezyKing99
      @BeezyKing99 Рік тому +2

      @@subcoolHVAC yeah, I noticed that after I've left my comment (it was right before I noticed the mounted position, showing side view)

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      @@BeezyKing99 😎

  • @Jilocasindragon
    @Jilocasindragon Рік тому +3

    But what does it chill?

  • @michaelsullivan479
    @michaelsullivan479 Рік тому +2

    Great video, could you install commercial grade surge protection to avoid the spike?

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +2

      There was a panel protector in place , appeared to be inoperable. Referred to Electrician to check out. Thanks for watching

  • @dylanfoxaygameh5281
    @dylanfoxaygameh5281 Рік тому +2

    what kind of factory neesd these huge types of cooling
    these are massive!

  • @PraxZimmerman
    @PraxZimmerman Рік тому +4

    They're so tiny and adorable 🥰

  • @ocsrc
    @ocsrc Рік тому +2

    490??
    I have never seen that voltage before
    480?
    600 I have seen

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      Canada?

    • @franklofarojr.2969
      @franklofarojr.2969 Рік тому +2

      Maybe a 480 running higher than spec.
      I've seen 120V power running at 127V here in Southern Nevada.

  • @ocsrc
    @ocsrc Рік тому +4

    Chiller 1 says DON'T TOUCH THAT!!!!!

  • @yixnorb5971
    @yixnorb5971 Рік тому +3

    I worked as a maintenance engineer on the physical plant of a high rise in Phoenix. An old 2 pipe system. A pipe for the boiler, a pipe for the chillers and a common supply and return pipe. When switching from heating to cooling, and vice versa, one must shut down the chiller or boiler for a while to let the water temperature moderate for the supply lines to the air handlers. Rather dangerous as failure to do so can rupture equipment. To make matters worse, all the thermostats were pneumatic. These required periodic oiling of the system with non-detergent oil to avoid bubbles in the thermostats of all 22 floors of units. Somebody used the wrong oil and thousands of dollars worth of thermostats had to be replaced. Then somebody thought it would be cute to throw an incendiary device down the garbage chute. And a lady watching the movie Towering Inferno thought it was a news report on the building and called the Fire Department. Five trucks and the chief showed up. Then a lady left a pot of boiling chicken unattended while shopping and burned up her entire apartment. Place was built in 1962. Asbestos everywhere. I quite that job as soon as possible.

    • @yixnorb5971
      @yixnorb5971 Рік тому +1

      P.S. Pressure breakers had degrading plastic housings, and if too many people shut off taps at the same time, they would blow and flood behind the walls. Locations of these were unknown as their locations were not in the blueprints.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      Wow, Thanks for commenting 👍

    • @ua7pyro591
      @ua7pyro591 Рік тому

      Incendiary device lol

    • @jollygreen4639
      @jollygreen4639 Рік тому

      Sounds like the college I worked at but we called it a three pipe system; chilled water/cold deck, hot deck and a common return back to the boiler room.

  • @Nighthawke70
    @Nighthawke70 Рік тому +6

    Never underestimate Mother Nature.
    Get some electricians out there and get a RFQ for lightning and surge protection for your investment.
    Then a invest in a cluebat to use over the C-Levels until they are convinced the central plant needs to be protected. The weather is not going to improve for some time

  • @ocsrc
    @ocsrc Рік тому +2

    What type of facility is it? Telcom?

  • @gsxrsquid
    @gsxrsquid Рік тому +2

    They are York. How soon can you replace them with Carriers? ;)

  • @RichTheEngineer
    @RichTheEngineer Рік тому +2

    What size are those chillers? Look to be 500 ton York units. Recently did some system integration for New York state government main campus; two new 500T Yorks and a 6000T Carrier, which replaced a 1960s era 2500T steam powered chiller.

    • @RichTheEngineer
      @RichTheEngineer Рік тому +3

      One of five 2500T steam powered chillers. They are going to replace another one probably next winter, and would like to do another one, but National Grid (utility) would need to upsize their service. That 6000T Carrier comes with a Siemens 5500HP medium voltage motor (4160VAC 3ph.) and a Rockwell Automation PowerFlex 7000 drive, which is about 40 linear feet of large cabinets.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому

      Now that’s some major tonnage and volts, have to verify tonnage but It’s between 300-400T if I remember. Thanks for sharing

  • @guygfm4243
    @guygfm4243 Рік тому +3

    Now that’s a chiller

  • @RodgerMudd
    @RodgerMudd Рік тому +6

    Some one please change that motor bearing!

  • @cosmicinsane516
    @cosmicinsane516 Рік тому +3

    Oh boy, ya got Yorks. Good luck. Can’t say Trane is much better though.

  • @keilikea01
    @keilikea01 Рік тому +9

    Of course it's the part in the back of ALL the wires😂

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +3

      Yep, challenge accepted 👍👊. Thanks for watching!

  • @SoutheastHVAC
    @SoutheastHVAC Рік тому +2

    Love the chillers man!

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      Me too! Thanks for the comment 👍

  • @kd5crw
    @kd5crw Рік тому +4

    It blew the starter coils and not the control transformer windings? And all the VFDs in the building lived? They must be really junk coils.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +4

      All were Siemens coils, it blew the fuses on transformer secondary on 5 out of 6 and only 2 fuses on the primary side of one. Drives survived this time. 👍

    • @RichTheEngineer
      @RichTheEngineer Рік тому +2

      Drives tend to protect themselves better.

  • @BartlettTFD
    @BartlettTFD Рік тому +28

    AT&T requires that personal NOT wear rings or watches when working in a high voltage environment‼️

    • @lyokss
      @lyokss Рік тому +3

      Even rubber rings like he was wearing? Watches and other jewelry I understand.

    • @dvsmotions
      @dvsmotions Рік тому +3

      I didn't see any "high voltage" environment in this video.

    • @adamruck
      @adamruck Рік тому +2

      @@dvsmotions High voltage is a relative term. If you are designing a12vDC power supply then 120VAc is the high voltage side. If you are line worker then 120VAC is the low voltage side, up to 35KV is considered "medium voltage". If you are a controls or automation engineer than all of your 24V field instruments are considered low voltage and your 120/480 loads are considered the high voltage side. It is completely relative to your perspective.

    • @donraptor6156
      @donraptor6156 Рік тому

      Stick your hand on the wire lugs then! You won't see anything either!

  • @MrJujubean
    @MrJujubean Рік тому

    Great video

  • @johnkelly7264
    @johnkelly7264 Рік тому +1

    Really interesting... and informative. Great presentation style. Subbed here.

  • @KoolinwithKrauss
    @KoolinwithKrauss Рік тому +4

    Make some NOISE!!! 😂 heck ya man crushing it 💪🏻

  • @edswider9309
    @edswider9309 Рік тому +1

    Ok video it brings back memories

  • @lokis9210
    @lokis9210 Рік тому +3

    So how exactly do these ginormous systems work? The chillers compressors are centrifugal (like turbos)?

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +8

      Twin screw rotary type compressor is used to move the refrigerant, a slide valve actuated by press. Diff. Gas solenoids controls capacity They are removing heat from the circulating chilled water loop that connects to all air handlers and rejects the heat to the condenser side cooling towers (water cooled)

  • @chadhartsees
    @chadhartsees Рік тому +2

    Hah... I wonder if this was my place of work. We had some chillers go down recently. It sucked.

  • @Fifty4Phoenix
    @Fifty4Phoenix Рік тому +2

    When something breaks, it has to be the part in the back. And 5 of them, too.

  • @wasim486
    @wasim486 Рік тому +1

    Awesome video. I learned before not to roll the truck without some trm2's in it

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +2

      I had enough to cover a few but the shop was nearby for more parts. Thanks for watching

  • @matthewdievendorf9609
    @matthewdievendorf9609 Рік тому +2

    It doesnt surprise me to see these MCC act this way after being struck by lightning

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      Yep, several ahu starter coils had same results. Thanks for watching

  • @Sasskin
    @Sasskin Рік тому

    What's the cost of one of these chillers? I have one chiller looking exactly like that from 2011, YA SA SD4 never used. Is there a market for these things?

    • @subcoolHVAC
      @subcoolHVAC  Рік тому

      Honestly I don’t know the exact cost, I’m not involved in purchasing. In today’s market I would guess over $100k

  • @redramroyal54
    @redramroyal54 8 місяців тому

    When starting up a chiller like Yorks with solid state starters, it’s not the best idea to stand in front of the starter on start up.
    Always a chance of arc flash if something in the starter fails

  • @DRAggIN123
    @DRAggIN123 Рік тому +2

    Good video man I'm in south florida too are you 725?
    I was thinking by the looks of that chiller plant that looks like south florida

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      Yep,,South FL. My Dad was 725 I’m not. Thanks for watching

  • @mikelCold
    @mikelCold Рік тому +2

    Super cool to see how society keeps working, all you

  • @Aa-ron01
    @Aa-ron01 Рік тому +7

    No rubber mats in front of those cabinets. You should have a personal mat in that case. With the speed you're moving, you will touch bare live metal eventually.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому

      Thanks for commenting 👊

    • @Sixta16
      @Sixta16 Рік тому +3

      I think the biggest issue is that funny amurican electrical panel design, that you need to stick yo hand arm length deep to reach what you need to work on.

    • @WhatIsThisVid
      @WhatIsThisVid Рік тому +2

      @@Sixta16 It's a Siemens MCC panel, far from an "american" design.

  • @5000go2
    @5000go2 Рік тому +1

    Just thank god they paid the extra money for those display screens

  • @hillppari
    @hillppari Рік тому +4

    poking barehanded in a live cabinet. ouch

  • @ToxicwasteProductions
    @ToxicwasteProductions Рік тому +4

    What kind of crazy stuff are they cooling? That thing is massive! Must be like Googles server farm or something 😂

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +5

      Close , it’s a School campus. 😀

    • @ToxicwasteProductions
      @ToxicwasteProductions Рік тому +3

      @@subcoolHVAC dear God that thing is massive for a school. Ive only seen way way smaller things here in Sweden. Must have been a really fun day working in that thing. I would have loved it :)

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +4

      @@ToxicwasteProductions It gets hot here in South Florida so more tonnage needed. That’s cool you’re watching from Sweden, Thank you !

    • @ToxicwasteProductions
      @ToxicwasteProductions Рік тому +3

      @@subcoolHVAC I love to learn new stuff and really enjoy watching expensive equipment :) Florida is super nice :) want to visit sometime =)

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +3

      @@ToxicwasteProductions Nice, hope you get to visit sometime.

  • @Technoguyfication
    @Technoguyfication Рік тому +29

    I know you know what you're doing, but seeing you stick your bare hands into the box and bypass the door interlock on the breaker made me cringe so hard. I'd be fired immediately if I tried doing that. Be safe out there.

    • @jbagsz1234
      @jbagsz1234 Рік тому

      Your very right, back when I was with my old company there is a time when you had to do meter readings on live panels for troubleshooting purposes. Our procedure for that was we had to fill out a “live work” permit that had to be signed off by a supervisor then we had to have a second person with us along with proper ppe if we failed to do this there would be a strong possibility of immediate termination. I’m thinking this guy is a private contractor so company rules wouldn’t apply to him.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      Thanks for the comment and the concern, I appreciate. I’m Contracted HVAC employee, I receive work orders to repair/replace HVAC equipment like in this video, there’s no taking out permit to work on and troubleshoot like in Lineman work here. Most of the probing was on 120v control circuit, the 480v was present and I was aware what had potential . Once starters didn’t engage after finding blown control fuse I knew I’d be just replacing coils and fuses with power disconnected. Wasn’t expecting to do 5 for sure but was an interesting call first thing in the am.

  • @timskiff9422
    @timskiff9422 Рік тому +2

    No hearing protection either i presume

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +3

      Thanks for watching officer 👍

  • @billnipp2309
    @billnipp2309 Рік тому +2

    are you an electrician?

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      No, HVAC tech

    • @billnipp2309
      @billnipp2309 Рік тому +1

      @@subcoolHVAC If you open up a bucket in an MCC, turn the power back on then reach in and work on it at my company, your first day would be your last. Unless youre an electrician. ty

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +2

      Here they send HVAC to get equipment back online, Thanks for watching

    • @billnipp2309
      @billnipp2309 Рік тому +1

      @@subcoolHVAC be safe.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      You too brother 👍

  • @moodyga40
    @moodyga40 Рік тому +2

    3 phase power

  • @akshonclip
    @akshonclip Рік тому +4

    1.21 Jigawatts

  • @kitwalker520
    @kitwalker520 Рік тому +1

    Been there - can be hairy

  • @justinjones6810
    @justinjones6810 Рік тому +2

    Is this a university or a school system seems really expensive for a school system but a university could afford it

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +3

      School system 👍

    • @justinjones6810
      @justinjones6810 Рік тому +2

      @@subcoolHVAC I would hate to see what the taxes are in that school district

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      I have to pay them 😢

  • @justin8894
    @justin8894 Рік тому +1

    487V scares me.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      Respect all the volts. Thanks for watching!

  • @ThumperKJFK
    @ThumperKJFK 2 місяці тому

    🤙

  • @zordmaker
    @zordmaker Рік тому +1

    0.6A is stupidly too small for the control circuit. Asking for trouble.

  • @donraptor6156
    @donraptor6156 Рік тому +1

    Where the Sam Hill is your Assistant? NEVER open a HV panel alone!

  • @Glipsnarp
    @Glipsnarp Рік тому +2

    Imagine lying on your resume and you get tossed into something like this....

  • @larrysmith8281
    @larrysmith8281 9 місяців тому +1

    Touch it

  • @martylynchian8628
    @martylynchian8628 6 місяців тому

    WTF is that thing? A Submarine torpedo launch tube?

    • @subcoolHVAC
      @subcoolHVAC  6 місяців тому

      Close, it’s a water chiller for HVAC 😁

  • @TheChillerGuysHub
    @TheChillerGuysHub 10 місяців тому

    @subcoolHVAC
    I’m not sure how to reach out to you, but Your videos are great.
    I’m sick of manufacturers owning information on all of the chillers, and telling you what you can and can’t do, and always saying that they have to send a factory guy for a simple problem. I decided to build a platform for guys to come together and diagnose issues together on chillers, and provide video based training without having to spend 5k like you would at the factory. Is this something you are interested in helping me build? Let me know brother.

    • @subcoolHVAC
      @subcoolHVAC  10 місяців тому

      Thanks for reaching out, I started this channel to share my work and troubleshooting experiences on mostly Commercial equipment with some residential to give anyone who is curious how they work, breakdown and get repaired. I’ll help out where I can, should be an email link on my channel information page. Your channel has great information 👍

    • @TheChillerGuysHub
      @TheChillerGuysHub 10 місяців тому

      @@subcoolHVAC i finally found it haha i sent you an email. looking forward to it man.

  • @jeffreyrex8232
    @jeffreyrex8232 3 місяці тому

    This style of screw was not York’s finest hour. Horribly inefficient machine. Rattles itself apart in no time at all, let alone the oil system issues.

  • @pheonix2160
    @pheonix2160 Рік тому +4

    just an fyi you about shocked your self. Connecting pos lead first and not ground lead. Connecting pos lead first puts all that potential on that neg lead.

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +6

      So what happens when checking voltage across phases and not to ground? Thanks for the comment

    • @Dfk429S9fo3
      @Dfk429S9fo3 Рік тому +1

      Um yeah, that's not how it works....

    • @iwontlagback7236
      @iwontlagback7236 Рік тому

      ​@@subcoolHVACi do believe some voltmeters work by measuring the current flowing through a known internal resistance, with ohm's law you can then know the voltage. If that internal resistance is low enough you may indeed be at risk of shocking yourself, whether it's the positive or negative lead of the meter.

    • @pigrew
      @pigrew Рік тому +5

      This would be mostly a myth. Voltmeters have some internal resistance (often 10 Mohm, but some are as low as 3 kohm). If you only probe the live wire, the floating probe will be at whatever voltage you are probing. If you touched the floating probe, you could get a small zap (though through a high impedance, it wouldn't be able to cause a large arc-flash at

    • @stargazer7644
      @stargazer7644 Рік тому +3

      Sure it puts all that potential on the neg lead - but through a 10 meg ohm impedance. You won't even feel a tingle as it'll load down to about 0.5V if you touch it. Where do you guys hear this stuff?

  • @davedrew9328
    @davedrew9328 Рік тому

    You should never be doing that type of job on your own you should also have another person with you preferably another Electrician or at least an apprentice ( a trainee an Electrician ).

    • @subcoolHVAC
      @subcoolHVAC  Рік тому +1

      Thanks for the comment, building maintenance was there just not on camera 👍

  • @dooropens7594
    @dooropens7594 Рік тому +4

    If someone saw me troubleshooting like you did at work with NO PPE I would be sent home for 3 days with no pay. or fired

    • @subcoolHVAC
      @subcoolHVAC  Рік тому

      There’s a whole lot worse out there working on this stuff, Thanks for sharing 👋