Oil System YK York Chiller

Поділитися
Вставка
  • Опубліковано 1 сер 2024
  • This is an overview of a YK centrifugal chiller. I walk through the base components of the oil system for hvac technician. HVAC training is a vital part of every tech's career.
    Get 8% off at TruTech Tools with promo HVACTIME
    www.trutechtools.com/?ApplyPr...
    Get tech support, training, and the Tech Blog at hvactimetx.com
    You can contact me at Hvactimetx@gmail.com
    Support my COFFEE problem through,
    venmo.com/code?user_id=316085...
    Zelle @ Hvactimetx@gmail.com

КОМЕНТАРІ • 56

  • @HVACTIME
    @HVACTIME  9 місяців тому

    YK online training at chilleracademy.com
    Get Confidence and Accuracy with this Troubleshooting Guide!
    hvactime.shop/products/yk-tech-sheet

  • @jpac2g
    @jpac2g Рік тому +10

    This video is pure gold, thank you for sharing your knowledge. Videos like this weren't available, and in this detail, just years ago. I can tell that you know your stuff, keep them coming please, Thank You!

  • @bill8985
    @bill8985 Рік тому +3

    It has been decades since i had to buy, install, and maintain one of these guys... Your explanation was super clear and brought back some nostalgia. Thanks!

  • @Erikmiles87
    @Erikmiles87 Рік тому +1

    Thanks. Was explaining eductor lines to my apprentice. I’m going to show him this video so he can see the internals

  • @GordonHVACR
    @GordonHVACR Рік тому

    Thanks for making this outstanding video! Proud of your hard work !

  • @twilks7878
    @twilks7878 Рік тому +1

    I love these chiller videos, I work at JCI and you explain better than my JM.

  • @fathmasameer7523
    @fathmasameer7523 Рік тому

    Great experience you deserve more subscribers dude thanks

  • @EverythingHVACR
    @EverythingHVACR Рік тому +1

    Great information Holden, thanks

  • @gatoguevara71
    @gatoguevara71 Рік тому

    Great job thank you for sharing your experience

  • @DannyBokma
    @DannyBokma Рік тому

    Ow man, all this information, thanks so much for sharing these insights! What a wonderful world an time we live in ^^!

    • @HVACTIME
      @HVACTIME  Рік тому

      Thank you for the support!

  • @tylerferrell2959
    @tylerferrell2959 Рік тому

    Dude you kill it in these videos

  • @onesimpleman1
    @onesimpleman1 Рік тому

    Excellent video on oil system

  • @wata_laf
    @wata_laf 7 місяців тому

    Wildly informative 👍🏼👍🏼

  • @TheRenaissanceBuilder
    @TheRenaissanceBuilder Рік тому

    Good video bud.
    I giggled a bit over the camera angles only because I recognize how difficult entertaining camera angles can be to find sometimes

  • @dmc357
    @dmc357 Рік тому

    Great video!!

  • @user-sx1rv9kb2q
    @user-sx1rv9kb2q 5 місяців тому

    I am a JCI YK centrifugal turbo chiller engineer.
    The video was very helpful.
    I would appreciate it if you could upload more videos. I am curious about the role of each material inside the chiller. The information about the oil line is similar to what I thought. thank you

  • @texture6
    @texture6 Рік тому

    Thank you to infinity

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC Рік тому

    Good stuff

  • @DronePilot4k
    @DronePilot4k 3 місяці тому

    Thanks!

    • @HVACTIME
      @HVACTIME  3 місяці тому

      Thank you very much!

  • @justinkendollrozinek
    @justinkendollrozinek Рік тому

    Super smart

  • @igariokmihailov4461
    @igariokmihailov4461 6 місяців тому

    great video buddy, i have a small leak on the oil sight glass, could be the o-ring , do i have to drain the oil in order to replace it, or i have to remove the front plate also? Thanks in advance

  • @bornjanuary25
    @bornjanuary25 Рік тому

    Kindly make review for Carrier chiller GX30 and 30GT with your amazing manner ( operation , service and maintenance )

  • @hvac8826
    @hvac8826 17 днів тому

  • @foodtravelxp24
    @foodtravelxp24 11 місяців тому

    Dear boss my york centrifugal chiller a Alam coming oil-low differential pressure calibration. So i can remove this alarm??

  • @kobebryant4750
    @kobebryant4750 Рік тому

    What is the meaning of oil variable speed pump contacts open? Plss help me

  • @brandonwalker4842
    @brandonwalker4842 7 місяців тому +1

    Did you have to recover all the refrigerant to work on the sump or where you able to isolate. I have to work on oil sump. I have isolation valve on discharge piping going to condenser but nothing on the evap. So, my question to you is do I need to recover the entire charge.

    • @HVACTIME
      @HVACTIME  7 місяців тому

      Yes, you wiil need to recover charge.

  • @DronePilot4k
    @DronePilot4k 3 місяці тому

    Thanks for the video , appreciate you taking the time to share. What is the sequence for the solenoid on the oil return line? Is it open during on cycles and closed on off cycles?

    • @HVACTIME
      @HVACTIME  3 місяці тому +1

      Yes, and the oil temp will influence it opening

    • @DronePilot4k
      @DronePilot4k 3 місяці тому

      Thank you very much , so if the oil temperature in the sump is already low it will stay closed?

    • @HVACTIME
      @HVACTIME  3 місяці тому +1

      @@DronePilot4k exactly

  • @joshstevens9826
    @joshstevens9826 Рік тому

    I'm curious, do you take annual oil samples?
    Or is it when a problem is suspected?
    Where I am wr do filters and oil samples with every annual we do.

    • @HVACTIME
      @HVACTIME  Рік тому

      I do annual samples with lab analysis

  • @Ariff-zt2gc
    @Ariff-zt2gc Рік тому

    Hi bro Holden , basically i've experiencing quite a number of times OIL - VARIABLE SPEED PUMP - DRIVE CONTACTS OPEN FAULT ALARM .
    Checked and verified no voltage across the output . Replaced to a brand new VSOP Board as well but the fault came back again in just 2 months . Any other alternatives or solution on what to check ? Can temporarily bypass somewhere to make the system online ?

    • @southendcycleworks
      @southendcycleworks Рік тому

      The VSOP boards lately are not very good quality. They usually come with a 1 year warranty and I've had to use it many times

    • @nellAyaR2034
      @nellAyaR2034 Рік тому

      Might want to get the input line inductor for vsop

  • @rmalanis13
    @rmalanis13 29 днів тому

    Having issues with a yk right now. While running sump LOP is about 60psig and evap is 38 psig. Changed oil filter and eductor. All valves open. Oil return solenoid working. But eductor filter stays hot, could it be bad balance piston seal, or faulty/plugged eductor block? If any one can assist it would be greatly appreciated

    • @rmalanis13
      @rmalanis13 29 днів тому

      To clarify Changed eductor filter, not block

  • @technicalfeatures5748
    @technicalfeatures5748 Рік тому

    Sir can you tell me how to cooling YK chiller heartsink, i have facing this problem high heart sink temperature

  • @jarredallen
    @jarredallen Рік тому

    I hate opening york chiller oil sump. they are always in an awkward location. they either in between compressor and condenser shell or at the bottom of the shells.

  • @user-rd5vm7si4o
    @user-rd5vm7si4o 6 місяців тому

    please advice have you ever have this problem ?, I am getting the oil loss in oil sump chiller York YK Centrifugal. The oil seems goes to evaporator
    The above problems occurs after :
    1. We have changed the oil Return Solenoid
    2. add extra valve for changing the TXV oil temp control (so if we need to change the txv no need to transfer pump down the R134a)
    3. Change the new oil pump
    The actions that we already redone :
    1. change again the oil return solenoid to the old one
    2. change the oil cooler heat exchanger
    3. change the txv oil temp control to the old one, but the extra valve for service still there (because of welded)
    4. checking the oil block eductor inside the oil sump ( the springs are doing pretty well)
    The problem still remain ,getting the oil loss in oil sump chiller York YK Centrifugal. The oil seems goes to evaporator
    please advice, do you have any suggestion

    • @HVACTIME
      @HVACTIME  6 місяців тому

      How much run time in-between trips?

    • @user-rd5vm7si4o
      @user-rd5vm7si4o 6 місяців тому

      only about start up 5 minutes , the oil sump level already minimum. The chiller still can run, but we just turn off the chiller off because the low level oil

    • @user-rd5vm7si4o
      @user-rd5vm7si4o 6 місяців тому

      before we already pump down out the oil in the evaporator with its r134a , drain all the r134a and the oil in evaporator side

  • @Henryolson09
    @Henryolson09 5 місяців тому

    Ferncos and PVC on the pressure safety valves!? That might be worse than not piping them outside at all

  • @andrewjacks8671
    @andrewjacks8671 10 місяців тому

    What does MTT mean? Multi-task trebuchet?

    • @HVACTIME
      @HVACTIME  10 місяців тому +1

      Make The Time for your spouse and family with our busy schedules.

    • @andrewjacks8671
      @andrewjacks8671 10 місяців тому

      @@HVACTIME MTT. I like it. Thanks for the in-depth videos. Much appreciated.

  • @HVAC-EngineerRam
    @HVAC-EngineerRam Рік тому

    Sir what is your language

  • @HVAC-EngineerRam
    @HVAC-EngineerRam Рік тому

    I want join this channel in Hindi language

  • @HVAC-EngineerRam
    @HVAC-EngineerRam Рік тому

    This video want in Hindi language please share

  • @ahmedabdeldayem8252
    @ahmedabdeldayem8252 4 дні тому

    thanks for your help but please speak slowly 😅