Solutions to Common Issues with PowMr Solar Inverter

Поділитися
Вставка
  • Опубліковано 6 вер 2024
  • Welcome back to the PowMr’s channel. In this episode, we've compiled some potential issues that might arise due to improper operation, along with corresponding solutions. We aim to address users' questions and guide you in minimizing the likelihood of problems through proper operation practices.
    👉: powmr.com/
    ______________________________________________________________
    0:28 Inconsistent Battery Voltage Reading
    1:21 PV Input Data Lower Than Configured Array Voltage
    1:53 Inverter Automatically Shuts Down After Startup
    2:16 Inverter Shows Battery or PV Power
    3:24 Inverter Reports Overload Error
    3:53 Inverter Reports Short-Circuit Error
    4:13 Inverter Reports Over-Temperature Error
    4:45 Battery Voltage Too High Error
    5:03 Abnormal Output Voltage
    Facebook
    / powmrsolar
    Instagram
    / powmrsolar
    TikTok
    / powmr_solar
    Linkedin
    / 89921328
    Email:
    support@powmr.com
    See you in my next video! :)
    ______________________________________________________________
    1: SunSmart 10K Split Phase Application Modes - 3 Modes Explained
    • SunSmart 10K Split Pha...
    2: How to Parallel Connect POW-SunSmart SP5k?
    • How to Parallel Connec...
    3: How to Install and Setup POW SunSmart10K Solar Inverter
    • How to Install and Set...

КОМЕНТАРІ • 120

  • @thesishelp1064
    @thesishelp1064 Місяць тому +1

    Hi I have a 24v 4.2kw powmr inverter
    What is the difference between main load output and second load output…
    Great inverter anyway

  • @kitezila
    @kitezila 7 днів тому

    I have an issue with Powmr 4.2kw + LiFePo4 battery.
    After 0 amps charging reached, it is still loud.
    I'm manually switch charging priority mode Utility-Solar only-Utility, only then it become silent.
    I'm using User Battery settings: bulk 28.0v, floating 27.6.

  • @muhammadshahzadyousaf1282
    @muhammadshahzadyousaf1282 3 місяці тому +1

    our inverter POW-HVM6.2M-48V-N installed a day ago, error 52 appears and the system is not restarting. what to do further? please advice.

    • @PowmrSolar
      @PowmrSolar  3 місяці тому

      Please send your problem to this email: support@powmr.com. Our teachnical staff will handle it for you.

    • @alexmendezdelarosa9333
      @alexmendezdelarosa9333 Місяць тому

      @Muhammadshahzadyousaf1282
      I have the same problem, when I turn on the inverter it lasts about 1 minute and a half, it tries to start and it doesn't and it gives an error 52, were you able to solve this problem? Did they solve it for you in powmr? tell me

    • @muhammadshahzadyousaf1282
      @muhammadshahzadyousaf1282 Місяць тому

      @@alexmendezdelarosa9333 i restarted the inverter. And it worked. Then it was hybrid mode. Now i am using it in off grid mode with sub mode.

    • @muhammadshahzadyousaf1282
      @muhammadshahzadyousaf1282 28 днів тому

      I have instslled batteries and using in off grid mode. Now this error not appeared​@@alexmendezdelarosa9333

  • @loretobenegildo361
    @loretobenegildo361 17 днів тому

    Just bought 6.2w, 48v powmr hybrid inverter last month. After installing, i conducted functional test to the unit. For 3w bulb there was no problem on the system. But when i tried an electric drill, the unit stops after 2 seconds and Error 52 appears. This tests were done several times but i got the same results. Can you tell what is the problem of the inverter?

    • @PowmrSolar
      @PowmrSolar  17 днів тому

      Please send your problem to this email: support@powmr.com.

  • @1akmason
    @1akmason 9 місяців тому +1

    I have your powmr 24v 120V 3000W hybrid inverter it did not come with the screws to connect the battery cables. What size am I supposed to use? Also the holes for things like the AC or even the batteries you couldn’t make them just a little bit bigger so people can use conduit there’s no way I’ll pass inspection having wires just exposed.

    • @PowmrSolar
      @PowmrSolar  9 місяців тому

      This model(POW-LVM3K-24V-H)?

  • @immrnoidall
    @immrnoidall 24 дні тому

    PLEASE HELP EXPLAIN. I have the older 3000 ka powmr all in one .In the app , in the "details" section, it lists everything going on.There is a" PV1 INPUT". I have no solar connected but also shows a second "PV 2 INPUT" showing " 122 AMPs , 60 volts input". WHAT IS THIS UNKNOWN INPUT? It makes no sense. please explain.

    • @PowmrSolar
      @PowmrSolar  24 дні тому

      Please send your problem with the product label to this email: support@powmr.com.

  • @YuriGolovatskyi
    @YuriGolovatskyi 25 днів тому

    Hey. Something happened. Can't turn off the hybrid inverter. 3.2kw 24v. When turning off - it starts endless loop with reloading each 2 seconds. Is there any way to reset it or check something? No errors are visible and when it turned on - working as expected

    • @PowmrSolar
      @PowmrSolar  25 днів тому

      Hi, please send your problem to this email: support@powmr.com.

  • @user-ux1tn6hg6z
    @user-ux1tn6hg6z 4 місяці тому +1

    Hello, I have New an inverter 2.4kw24V80A from your company that has a defect. When I connect the power outlet cable, the device beeps and turns off. What is the solution?

    • @PowmrSolar
      @PowmrSolar  4 місяці тому

      Please send your problem to this email: support@powmr.com. Our technical staff will handle it for you.

    • @PowmrSolar
      @PowmrSolar  4 місяці тому

      @@user-ux1tn6hg6z This email: support@powmr.com

    • @user-ux1tn6hg6z
      @user-ux1tn6hg6z 3 місяці тому

      ​@@PowmrSolarhello , i sent email and no one reply .

    • @PowmrSolar
      @PowmrSolar  3 місяці тому

      @@user-ux1tn6hg6z please send us a screenshot of your email.

  • @Nailman111
    @Nailman111 24 дні тому

    hello, i have POW-HVM3.2H-24V
    using it as UPS for my house, without solar panels connected
    inverter won't stop humming with fans even if batteries charged, and shows that i have some strange PV input about 20 volts, but as i said - i have no solar panels

    • @PowmrSolar
      @PowmrSolar  24 дні тому

      Please send your problem to this email: support@powmr.com.

    • @immrnoidall
      @immrnoidall 9 днів тому

      @@PowmrSolar YUP. Me too. I have no solar but the app says I have input on a PV2. there is no pv2. just a pv1 connection that correctly says 0 input. did you find out what this is?

  • @thedampestcrib6004
    @thedampestcrib6004 17 днів тому

    Hello I'm haveing issue with voltage coming out the pv side at night

    • @PowmrSolar
      @PowmrSolar  17 днів тому

      Please send your problem to this email: support@powmr.com.

  • @supremeautomotive6749
    @supremeautomotive6749 12 днів тому

    Im having issue im getting voltage from panels but now im not getting any watts or amps from my 80amp charge controller

    • @PowmrSolar
      @PowmrSolar  12 днів тому

      Please send your problem to this email:support@powmr.com.

    • @supremeautomotive6749
      @supremeautomotive6749 12 днів тому

      @@PowmrSolar I did already

    • @PowmrSolar
      @PowmrSolar  12 днів тому

      @@supremeautomotive6749 Okay, can you send me your email?

  • @anythingundertherain6192
    @anythingundertherain6192 5 місяців тому

    Hi,how to fix shorted battey terminal on the solar inverter. Removed the battery wire but shorted still there

    • @PowmrSolar
      @PowmrSolar  5 місяців тому

      Please send your problem with product label to this email: support@powmr.com. Our technical staff will handle if for you.

  • @Markslife101
    @Markslife101 10 місяців тому

    My inverter is showing 100volts coming from my panels, but the solar panel light doesn't come on and it doesn't charge the batteries .its the model 3000w 24 v hybrid inverter

    • @PowmrSolar
      @PowmrSolar  10 місяців тому

      Hi, kindly send your problems to this email: support@powmr.com.

  • @ramsaybolton9099
    @ramsaybolton9099 7 місяців тому

    I have a 10kw 48v split phase inverter. I’m trying to operate it in single phase mode, but I have to change number 39 on the menu to 0. 39 does not show up in the menu, help please.

    • @PowmrSolar
      @PowmrSolar  7 місяців тому +1

      Hi, please send your problems to this email: support@powmr.com.

  • @marinomekaniko2233
    @marinomekaniko2233 11 місяців тому

    hello, is it possible to use my POW-HVM6.2M-48V without battery?
    PB is flashing because i dont have battery,
    then No detection of solar panel data...can you help me with these problem? thank you

    • @PowmrSolar
      @PowmrSolar  11 місяців тому

      Hi, kindly send your problems to this email: support@powmr.com.

  • @bradkaminsky8007
    @bradkaminsky8007 9 місяців тому

    I just installed a separate powermr controller and complete system. The problem is the system works fine all night and still shows 3 or 4 bars of power in the morning but when a larger appliance tries to start the controller shuts off and then tries to restart, what is the issue here?

    • @PowmrSolar
      @PowmrSolar  9 місяців тому +1

      Hi, please send your product label and problems to this email: support@powmr.com

  • @marcelmarquart1233
    @marcelmarquart1233 5 місяців тому

    Hello PowMr Team,
    We have been using your inverter for a few days and it now shows the warning code "10" Output power derating. The ambient temperature is around 30°C and when the battery is charging from the grid this warning goes off. When the battery is discharging a few minutes later, the warning is off.
    Could you help with the warning?
    Thanks a lot,
    Marcel

    • @PowmrSolar
      @PowmrSolar  5 місяців тому

      Hi, please send your problem to this email: support@powmr.com. Our after-sales engineers will handle it for you.

  • @chencheepeng6669
    @chencheepeng6669 9 місяців тому

    When I switch off a table fan connected to a POW-HVM10.2M a 51 error fault code shown occur and shutdown the power output. Why this happened? Please advise.

    • @PowmrSolar
      @PowmrSolar  9 місяців тому

      Hi, please send your problems to this email: support@powmr.com.

  • @senses_FAIL87
    @senses_FAIL87 2 місяці тому

    why my powmr hybrid inverter after a year it is displaying fault code #1 even though fans are working? can anyone help me solve this problem?

    • @PowmrSolar
      @PowmrSolar  2 місяці тому

      Please send your problem to this email: support@powmr.com

  • @pawelfilipowski6329
    @pawelfilipowski6329 4 місяці тому

    Hello,
    I have a PowMR 4.2KW inverter connected with Lifepo4 battery pack.
    I choose to charge battery pack using just Solar Panels, and Output setup to SUB(default) What I see is that In this mode, inverter takes 80% of a power from a PV and the rest from Utility - even if PV could handle all power that Im using.
    If I will change settings and run inverter on SBU mode, All the power is taken from PV.
    So my question is, why even if PV power is big enough for the output this inverter in SUB mode always use power from utility. If I will run 500W on it I see that 430W is only taken from PV - rest from utility (of course im sure that this time my Panels could give around 1KW.

    • @PowmrSolar
      @PowmrSolar  4 місяці тому

      Hi, please send your question to this email: support@powmr.com. Our technical staff will handle it for you.

    • @thomastaylor8657
      @thomastaylor8657 2 місяці тому

      The inverter eats 50 watts it's not 100% efficient

  • @atty.gccjvlog6775
    @atty.gccjvlog6775 6 місяців тому

    Hi I bought POWMR 10.2KW why is the PV input 2 is not functioning? I want to use both input 1 and input 2 but only input 1 functions, what should I do?

    • @PowmrSolar
      @PowmrSolar  6 місяців тому

      Hi, please send your problems to this email: support@powmr.com. Please note that we may not be able to promptly respond to you due to the Lunar New Year. We apologize for the inconvenience this may take and thank you for your understanding. We wish you all the best!

    • @svyatoslav00012
      @svyatoslav00012 6 місяців тому

      Both That inputs internally paralelled (both leads to single mppt). So if you'll insert same string (same amount of same panels, facing same direction) - it will be ok, if it will be different string - it will not work well

    • @tanattjhon
      @tanattjhon 2 місяці тому

      @@svyatoslav00012wow thanks

  • @ravishankarbhat5198
    @ravishankarbhat5198 10 місяців тому

    Getting ac power at battery terminals. When I put tester on battery terminals its indicator shines and ac is present on dc side of the inverter. How is this possible?

  • @chamith256
    @chamith256 7 місяців тому

    I recently boughta POW-HVM3.2H-24V-N. fans spinning all the time. fans don't stop spinning even a load is not connected. that is very annoying

    • @PowmrSolar
      @PowmrSolar  7 місяців тому

      Hi, the fan will work as long as the inverter is working.
      Turn on the inverter with only the battery connected and wait for 5 to 10 minutes to see if it stops running with only the battery connected.
      Sometimes it may be that there are too many PV panels connected, and this situation may also occur.

  • @brosli84
    @brosli84 10 місяців тому

    We set to 230vac, 60hz but the frequency output is unstable 40 to 87hz output. So i try to isolate the solar panel to check of the frequency returns to 60hz and yes 60hz again. This means defective because solar panel must not affect the frequency of 230vac output 60hz should be stable to prevent damage in appliances and motor loads.

    • @PowmrSolar
      @PowmrSolar  10 місяців тому

      May I know the model number?

  • @rbkarasu434
    @rbkarasu434 10 місяців тому

    I bought 6.2kw inverter, after connection unable to turn ON my ELCB always tripped, found inverter got leak, L to ground 125V and N to ground 175V all one input and two out put got leaks. How to solve the issue there is any filter to remove?

    • @PowmrSolar
      @PowmrSolar  10 місяців тому

      Hi, kindly send your problems to this email: support@powmr.com

  • @divinelotusnb7910
    @divinelotusnb7910 4 місяці тому

    Can you please help me resolve issue of inverter beeping continuously…it’s giving a code 10. PLEASE HELP!!!!

    • @PowmrSolar
      @PowmrSolar  4 місяці тому

      Which model? Please send us the product label.

  • @lilmoscato1515
    @lilmoscato1515 7 місяців тому

    Our inverter has been working fine but now it won’t charge our batteries. We have enough power from the solar panels to power the entire house, and it shows that the batteries are charging but they aren’t. Are there any solutions to this?

    • @PowmrSolar
      @PowmrSolar  7 місяців тому

      Please send your problems with the product label to this email: support@powmr.com

  • @yblue-kr2jl
    @yblue-kr2jl 6 місяців тому

    I have 10kw hybrid inverter it stoped powering on I’ve checked all wires are working going into inverter

    • @PowmrSolar
      @PowmrSolar  6 місяців тому

      Hi, please send your question to this email: support@powmr.com

  • @markneilrojas4794
    @markneilrojas4794 11 місяців тому

    hello boss. i have a problem with my mr inverter. i received 01 fault alarm but my fan is still working and i already clean the dusts with blower but still receive 01 alarm. what is the best way i can do?

    • @PowmrSolar
      @PowmrSolar  11 місяців тому

      Please send us the model number.

  • @dawiddebinski8728
    @dawiddebinski8728 5 місяців тому

    I bought 2k inventer so far output is 7v instead 230v, input 100v from panels is not recognised it displayed 0. Unfortunately on AliExpress there is no warranty and seller refuses to send replacement. So those devices have incredibly low service, not recommended to anyone.

    • @PowmrSolar
      @PowmrSolar  5 місяців тому

      Hi, could you please send us your order number and AliExpress seller link?

  • @johsell07
    @johsell07 7 місяців тому

    Hello im having problems with fan failure need help to work with that only have 5 months installed

    • @johsell07
      @johsell07 7 місяців тому

      Is a split phase 10kw

    • @PowmrSolar
      @PowmrSolar  7 місяців тому

      @@johsell07 Please send your problems to this email: support@powmr.com

  • @muhammadshahzadyousaf1282
    @muhammadshahzadyousaf1282 3 місяці тому

    model POW-HVM-6.2M-48V-N۔
    SETTING#38 GRID TIE CURRENT۔ what is optimum value as no net metering is installed.

  • @diydesk
    @diydesk Рік тому +1

    This video provides a fantastic set of troubleshooting steps that will prove invaluable to new installers. Additionally, don't forget the importance of precharging your inverter capacitors before connecting the batteries. This simple step goes a long way in safeguarding PowMr Inverters and ensuring their longevity.
    ua-cam.com/video/0M_7s39E3Ds/v-deo.html

    • @topeye4202
      @topeye4202 9 місяців тому

      Yes thats smart, unfortunately most people doesn't do this. To preload the capacitors I've fix installed a tactile button with a 100 Ohm 5Watt resistor in series, across my single breaker. Just push the button for 5 seconds and then simultanosly switch on the breaker - thats it : )

  • @pr5991
    @pr5991 11 місяців тому

    I have connected 8 panels of 250 watts in series, in cloudy days, though voltage stays at least 280volts, the inverter charger stops charging and then start again, keep doing it every few minutes. What can be the reason?

    • @PowmrSolar
      @PowmrSolar  11 місяців тому

      Which model? Kindly send us the model number.

    • @theonekim3426
      @theonekim3426 9 місяців тому

      Mine too
      10.2kw

  • @adiwiratno9836
    @adiwiratno9836 4 місяці тому

    My inverter has 01 failur and konstan alarm...how can i solve this?

    • @PowmrSolar
      @PowmrSolar  4 місяці тому

      Which model? Please send us the product label.

  • @sonnysolatorio8356
    @sonnysolatorio8356 2 місяці тому

    Powmr 8.2 kw can communicate with lithium battery pack 51.2 200ah with can

    • @PowmrSolar
      @PowmrSolar  2 місяці тому

      Please send your problem to this email: support@powmr.com. Our technical staff will handle it for you.

  • @bobbymartinez1613
    @bobbymartinez1613 11 місяців тому

    Hello, may I know where I can buy motherboard for PowMr 3.2kw model?

    • @PowmrSolar
      @PowmrSolar  11 місяців тому

      Please send your problems to this email: support@powmr.com.

  • @miguelluna8921
    @miguelluna8921 11 місяців тому +1

    Como resuelvo el código 32 en un mppt powmr

    • @PowmrSolar
      @PowmrSolar  11 місяців тому

      Kindly send us the model number.

  • @chencheepeng6669
    @chencheepeng6669 9 місяців тому

    When I switch off a table fan connected to a POW-HVM10.2M a 51 error fault code shown occur and shutdown the power output. Why this happened? Please advise.
    Anybody out there with this model can try to connect a table fan and switch on and off to see any fault I encounter. I bought 2 sets giving me the same fault. Just for comparison please try, thanks

    • @PowmrSolar
      @PowmrSolar  9 місяців тому

      Hi, kindly send your problems to this email: support@powmr.com

    • @chencheepeng6669
      @chencheepeng6669 9 місяців тому

      they are not following up my problem. but I solve it myself

    • @user-lu9hi2jk5r
      @user-lu9hi2jk5r 7 місяців тому

      I have the same issue!!!!!
      How did u resolve it?

  • @dashley2525
    @dashley2525 6 місяців тому

    My 10.2 PowMr will harvest so Load is being met but battery is not being charge till about 1800 w. The PV input readout is an arbitrary .5 kw till about 1800 w PV input. No one has had a clue why so far. A replacement 6.2 kW PowMr works perfectly. So the issue is surely in the 10.2 unit. Issue existed at initial startup.

    • @PowmrSolar
      @PowmrSolar  6 місяців тому

      Hi, please send your problems to this email: support@powmr.com.

    • @dashley2525
      @dashley2525 6 місяців тому

      I have tried for months. They are the worst tech support I have ever had@@PowmrSolar

    • @ralphyc81
      @ralphyc81 5 місяців тому

      I'm having the same issue .5kw on an array that's over 3kw

    • @dashley2525
      @dashley2525 5 місяців тому

      I got an independent tech looking at it now. He says it checks out okay so I am still trying to get him to understand it. I was getting below 900 kw a month with it and now over 500 kw with a replacement 6.2 unit. If he finds why I will contact you and tell you what it was. @@ralphyc81

    • @dashley2525
      @dashley2525 5 місяців тому +1

      this is what the tech said - Hi sir Ashley, the technician observed your inverter and he said it is easy to overheat, and even though he will repair the inverter it is still useless, as per to him that kind of inverter is like a medicine term GENERIC, a disposable one. He suggests buying a new one with quality rather than pushing it to be repaired. Thank you

  • @MuhammadAhmad-cq6ir
    @MuhammadAhmad-cq6ir 4 місяці тому

    Dear plz help
    I have powmr 4.5kw but SBU mod is not working properly

  • @patriciuschristianto1560
    @patriciuschristianto1560 9 місяців тому

    my inverter powmr 5.5kw hybrid , just life for 3 day , n die.. see code error 09

    • @PowmrSolar
      @PowmrSolar  9 місяців тому

      Hi, kindly send your problems to this email: support@powmr.com

  • @markneilrojas4794
    @markneilrojas4794 11 місяців тому

    boss good am. nag fault aoarm 01 po ang aking mr pow inverter 5.5 kw. paano kaya ito masolutionan? nag blower ko na po wala parin ngyari

    • @jaymarbreguera591
      @jaymarbreguera591 6 місяців тому

      fan fault yan. hindi umaandar ang fan ng iverter pag ganyan.

  • @nhathoy7987
    @nhathoy7987 5 місяців тому

    why is it i read so many issue about your hybrid inverter?

  • @dashley2525
    @dashley2525 6 місяців тому

    Can anybody tell me of an electronics shop that can fix hybrid inverters like the PowMr 10.2?

    • @PowmrSolar
      @PowmrSolar  6 місяців тому

      Hi, may I know what's wrong with your machine?

    • @dashley2525
      @dashley2525 6 місяців тому

      My 10.2 PowMr will harvest so Load is being met but battery is not being charge till about 1800 w. The PV input readout is an arbitrary .5 kw till about 1800 w PV input. No one has had a clue why so far. A replacement 6.2 kW PowMr works perfectly. So the issue is surely in the 10.2 unit. Issue existed at initial startup.@@PowmrSolar

    • @PowmrSolar
      @PowmrSolar  6 місяців тому

      @@dashley2525 Hi, please send your problems to this email: support@powmr.com. Our technical staff will help you.

    • @dashley2525
      @dashley2525 6 місяців тому

      I did@@PowmrSolar

    • @dashley2525
      @dashley2525 6 місяців тому

      where is a repair center?@@PowmrSolar