Trane Package Unit Not Keeping Up!

Поділитися
Вставка
  • Опубліковано 24 чер 2024
  • In this video I visit a customer whose package unit had hidden problems! #hvacguy #hvac #airconditioning #hvaclife #heatingandcooling #hvactrainingvideos #hvactechnician #skilledtrades #bluecollar #bluecollarpride #trane #evaporatorcoil #dirtycoil ‪@hvactactical‬ ‪@HVACKnights‬
    Merch Store : hvac-guy-2.creator-spring.com
    Here are links to the tools I use, And it costs you nothing extra to buy from this list:
    Makita Wet/Dry Vac: amzn.to/3VVHpsz
    Veto OT-LC: amzn.to/3wSK1Nj
    Appion AV760: amzn.to/3OkrwHC
    Fielpiece SC680 Clamp Meter: amzn.to/33rhxvE
    Fieldpiece SC480 Clamp Meter: amzn.to/33kfgCB
    Fieldpiece SMAN 480 Digital Manifold: amzn.to/3twfVvA
    Fieldpiece DR58 Leak Detector: amzn.to/3nt1TXw
    Fieldpiece JL3KM2 Bluetooth Manometer set: amzn.to/3blMrJR
    Fieldpiece Bluetooth Scale: amzn.to/3Gzveab
    Fieldpiece SDMN6 Manometer: amzn.to/3qwk9RP
    Yellow Jacket Tubing Expander: amzn.to/3sjuK3a
    Milwaukee M12 Impact Driver: amzn.to/37xXkqk
    DIY Vacuum Attachment for drains: amzn.to/3tDpfNU
    Fieldpiece Smart Probe Kit : amzn.to/34NG3HL
    Klein Heavy Duty Wire Strippers : amzn.to/3I8YNzT
    Klein Needle Nose Crimpers/Stippers: amzn.to/3fuwXlw
    Klein Knee Pad: amzn.to/3cy6FB0
    Klein 7in1 Flip Socket: amzn.to/3bpabwG
    Klein Journeyman Pliers: amzn.to/3tvB60w
    Milwaukee Slim Packout On My Torch: amzn.to/3KeLm3j
    Aluminum Packout Wall Mount on torches : amzn.to/3Kf9hQg
    Milwaukee Tool Box: amzn.to/322iyK9
    Veto Pro Pac Tech MCT: amzn.to/3nwwQdA
    Milwaukee Hook Blade Knife: amzn.to/33F3m5T
    Testo 300 flue gas analyzer: amzn.to/3IcS3Bd
    Western Nitrogen Regulator: amzn.to/3rmdKrx
    Klein Canvas Bucket: amzn.to/3FyzKVf
    Flag Velcro Patch Kit: amzn.to/3K8Eswx
    Supco Magnetic Door Switch Holder: amzn.to/34IcXcL
    Milwaukee Magnetic Light: amzn.to/3FulCfF
    Milwaukee Rechargeable Headlamp: amzn.to/3nuXsvf
    SS2 Float Switch: amzn.to/3K7LJMW
    3-Amp Breaker: amzn.to/3nxaSXJ
    Appion Valve Core Removal Tool: amzn.to/33CFArw
    Appion G5 Twin Recovery Machine: amzn.to/33Dvd6C
    Yellow Jacket Large Tubing Bender: amzn.to/3qwJv1U
    Similar Small Tubing Bender: amzn.to/3fJsziJ
    Fluke Twist Guard Test Leads: amzn.to/3216R6j
    Honeywell T-4, 2-Heat, 1-Cool Programmable Thermostat: amzn.to/3qtIuaX
    Kidde Carbon Monoxide Alarm: amzn.to/3qtIIyP
    SolderWeld Flame Resistant Magnetic Blanket: amzn.to/3qtJ4Wb
    Malco 1/4 - 5/16 flip bit : amzn.to/3nr67yU
    Quick Check Acid Test: amzn.to/3GA2XAy
    Wiha Torqe Screwdriver : amzn.to/3u1swH6
    Wiha Torqe Screwdriver 1/4” adapter: amzn.to/3IH22Pw
    Compressor Tote: amzn.to/3H8xHst
    Inspection Mirror: amzn.to/3r9PERV
    Wiha TorqueVario-S 10-50 in/lb Torque Screwdriver : amzn.to/3GbKAku
    1/4” adapter for Wiha Torque Screwdriver : amzn.to/3u8g0pq

КОМЕНТАРІ • 97

  • @HVACGUY
    @HVACGUY  10 днів тому +21

    Yes, I’ll be back to seal return.

    • @andyvitz
      @andyvitz 10 днів тому +3

      Yeah the Schrader valve when you unscrew that top one sounded like it was leaking just so you know might want to replace the Schrader valves on that unit

    • @dock_yard1149
      @dock_yard1149 9 днів тому +2

      @@andyvitz but pressures were fine, so ... maybe not as long as caps seal the valves

    • @MariosACandRefrigeration
      @MariosACandRefrigeration 9 днів тому

      recommend ,return vents above the doors ,that house is at negative pressure,and it will struggle with no returns.

    • @jthonn
      @jthonn 9 днів тому +3

      @@MariosACandRefrigeration All you have to do is take an inch off the bottom of the doors, if that's the case.

    • @MariosACandRefrigeration
      @MariosACandRefrigeration 9 днів тому

      @@jthonn most new doors have a 1 inch piece of press wood on the bottom,for support.

  • @bobchamp3159
    @bobchamp3159 9 днів тому +14

    There might be a problem when you walk up and the compressor sounds more like a vacuum pump 😂, that sounds is cavitation I believe.

  • @Eddy63
    @Eddy63 9 днів тому +5

    Good little vid Curt ... How bout them Vols ⚾Champs ... Thx

  • @OGHVAC
    @OGHVAC 6 днів тому

    Another fur coat coil but of the evaporator type. Awesome job done as usual Curtis!

  • @kens.3729
    @kens.3729 9 днів тому +4

    Was that a Compressor or a Popcorn 🍿 Popper ? 😬👍

  • @aland680
    @aland680 10 днів тому +11

    Looks like someone was living in the package unit.. Nasty!

    • @jthonn
      @jthonn 9 днів тому

      A whole family! Nasty for sure, and unhealthy.

  • @lynncomstock1255
    @lynncomstock1255 9 днів тому +2

    The beginning conditions at 3:20 are ridiculous once you see the condition of the indoor Coil at 8:23. That amount if blockage should make the coil freeze up. The ending low superheat at 14:56 indicates that the metering device must be an orifice. It's likely that someone previously overcharged the system to address a persistent icing issue due to very low airflow. Therefore, it's essential to check the external static pressures. Sealing the return might further reduce airflow.
    It's also highly probable that the system is too large for the home. A smaller, properly sized unit might be a better match for the current ductwork.

  • @tolbert3671
    @tolbert3671 9 днів тому +5

    Been there done that. Suit up, put on your gloves and tape your wrists and ankles and wear a a good quality filter mask. Don't forget to spread some bait when your done.
    I really enjoy your videos. Stay safe.

  • @RyanHughes-hq1xj
    @RyanHughes-hq1xj 9 днів тому +4

    Those are (were) my favorite compressors. Very bulletproof. Great video. Thanks for posting.

    • @jthonn
      @jthonn 9 днів тому

      They are good, as soon as I saw it, I said there's another big red.

  • @jthonn
    @jthonn 9 днів тому +3

    Some critters for sure, she even said so. I never heard of keeping the doors closed because of varmints before. There was something rattling in that compressor that did stop, weird, but we have all heard some weird stuff in units and compressors before. It has got to be cooling much better now. As someone has stated before, there sure are lots of package units in your area. Nice job

  • @thesilentonevictor
    @thesilentonevictor 9 днів тому +3

    Good job Curtis

  • @ericvonzeppelin9981
    @ericvonzeppelin9981 9 днів тому +6

    that system is overfilled. Someone added refrigerant to get the suction pressure up and never looked at the plugged evaporator.

  • @chrisnapier5626
    @chrisnapier5626 9 днів тому +2

    Great job,Curtis!

  • @hinspect
    @hinspect 9 днів тому +5

    We bought a Victor Rat Trap that is powered by "C" Batteries, and it sure gets the job done! There was an opening in our Log Garage from the outside that they found. It was killing one or two per night. There are no poisons for the Cat to get into! No more problems this year 😉

  • @porky7753
    @porky7753 9 днів тому +5

    Somebody left the winter blanket on, on the evaporator.

    • @dbmail545
      @dbmail545 9 днів тому

      Because the evaporator coils are always wet with dew when in operation, any filter leakage causes a problem very quickly.

  • @hvac_audaz_firme
    @hvac_audaz_firme 10 днів тому +3

    Finished just in time ☔. That coil was filthy even had a guest rat😂...Saludos Vato

  • @Bryan-Hensley
    @Bryan-Hensley 9 днів тому +1

    Those damn things go through expansion valves like crazy. I bet I've changed 15 or 20.

  • @ftwbreeze
    @ftwbreeze 9 днів тому +4

    Another save by HVAC GUY! Thank you Curtis

    • @HVACGUY
      @HVACGUY  9 днів тому +2

      You bet!

    • @jthonn
      @jthonn 9 днів тому +1

      Yeah, another slam dunk.

  • @philiphusain3923
    @philiphusain3923 9 днів тому +2

    Another great save!
    .
    Use fiberglass filter? Where you were measuring liquid line temperature and pressure was before the condenser. Did it have a pressure port after the condenser?

  • @kg4muc
    @kg4muc 9 днів тому +1

    That thing was a vacuum cleaner! Sucked up all in sight😊

  • @robalexander7348
    @robalexander7348 9 днів тому

    A much cleaner coil now Curtis 👍 Au

  • @dbmail545
    @dbmail545 9 днів тому +2

    That compresser sounds like it's overfilled but I don't see it sweating.

  • @jimbergen5232
    @jimbergen5232 10 днів тому +4

    It's when you are in a slight rush you faulter. Today is it " About to rain on me.. " - the other vid when you tried to go fast to save the Church some time/hour rate. Heck we all do it.

  • @michaelbuxton9368
    @michaelbuxton9368 10 днів тому +4

    That return flex should be replaced. That dust indicates rodent damage.

  • @johnnym.rodriguezr3562
    @johnnym.rodriguezr3562 6 днів тому

    Great job!

  • @garym108
    @garym108 7 днів тому

    I find the ones that have the coil outside the house with the compressor interesting. I take it it is always temperate climate there or something. Cannot imagine that in a place like Bismarck North Dakota. You would have tons of cold air coming in from that opening.

  • @stevencossaboon3237
    @stevencossaboon3237 9 днів тому +2

    Nice work Curtis.

  • @Funkybulb
    @Funkybulb 9 днів тому +1

    Looked like fluffy been living in there

  • @gordongrimes2797
    @gordongrimes2797 9 днів тому +1

    I am supprised the evaporator is not froze solid. and the charge numbers looked good? thanks Curtis

  • @CrappyCornFlake
    @CrappyCornFlake 9 днів тому +3

    There's gotta be a rat living in that duct work. That was nasty. I'm surprised a coil that dirty didn't effect the pressures too much. You should have told that lady that closing doors isn't going to keep the critters out. Rats can squeeze into wherever they want. Give her a good spook. lol

  • @Emerickocsis
    @Emerickocsis 9 днів тому +1

    Good Job!!!

    • @HVACGUY
      @HVACGUY  9 днів тому

      Thanks!

    • @Emerickocsis
      @Emerickocsis 9 днів тому

      @@HVACGUY how many calls you usually run a day

  • @MariosACandRefrigeration
    @MariosACandRefrigeration 9 днів тому +2

    3:20 shows you,there is more to this,then nice gadgets.

  • @jasonjennings8125
    @jasonjennings8125 9 днів тому +1

    that poor coil still looks dirty afte rbeing cleane dI had a rheem package unit i eventually was able to get rid of and get a regular split unit with a heat and a gas furnace

  • @DiogoDC123
    @DiogoDC123 10 днів тому +2

    You would assume low superheat with an evap wearing a fur coat

  • @TxGuitarPlayer
    @TxGuitarPlayer 9 днів тому

    Good job

  • @corruptedbrain6
    @corruptedbrain6 9 днів тому +1

    why would my superheat drop when it was normal before the clean?

  • @radzer0966
    @radzer0966 9 днів тому

    Didnt know trane used those popcorn compressors GE puts in all its fridges.

  • @edjansen6096
    @edjansen6096 9 днів тому

    That compressor sounds like it has some ball bearings in it

  • @OnusBones
    @OnusBones 9 днів тому +4

    The compressor sounded like it was shaking an aerosol can.
    Maybe she needs to adopt a young barn cat who has been taught by Momma Kitty how to kill quickly and that the prey is food.

    • @jimdavis6833
      @jimdavis6833 9 днів тому +4

      Cats don't need to be taught to hunt or kill mice. It's in their nature. Mine is 14, and had never seen a mouse til about 16 months ago when a family of them found their way into my house. It took her about 3 weeks to get all 9 of them. I haven't seen one since.

    • @OnusBones
      @OnusBones 9 днів тому +2

      @@jimdavis6833 All cats will hunt, yes. Barn cats are particularly efficient about it, and don't leave little carcasses to rot under the couch.

    • @corruptedbrain6
      @corruptedbrain6 9 днів тому

      @@jimdavis6833dont take life so serious bud. of course onusbones knows that cats can hunt lol

    • @jimdavis6833
      @jimdavis6833 9 днів тому +1

      @@OnusBones My cat personally delivers the carcasses to me, even in bed. She never chews them up, just worries them to death, then deposits them where I'll be sure to find them.

    • @OnusBones
      @OnusBones 9 днів тому

      @@jimdavis6833 Your kitty is trying to teach you how to take care of yourself!

  • @cre8tive31
    @cre8tive31 9 днів тому

    Hey HVAC Guy! I have a question for you. Can a double breaker auxiliary heat strip kit be wired using one breaker or one side of the heat strip, instead of both breakers.

  • @Jon-hx7pe
    @Jon-hx7pe 9 днів тому +1

    in this situation wouldn't it make sense to put filter inside package unit instead of at grill - protect the coil in case of return duct leakage.

  • @ChrisCreech-uf2ty
    @ChrisCreech-uf2ty 10 днів тому +2

    Rats not a mouse

  • @bosserman1964
    @bosserman1964 9 днів тому

    need to pull a new return duct too and clean the cond coil...

  • @AaronPowellvox
    @AaronPowellvox 9 днів тому +2

    I still don’t understand why you use that foam gun. The coil cleaner is supposed to be put on as a liquid so the foaming action pushes the debris out of the coil.

  • @keithsac2542
    @keithsac2542 9 днів тому +1

    Doors need to be kept open in this case.

  • @jameslong3351
    @jameslong3351 8 днів тому

    Someone ran that unit without a filter for a long time.

  • @stevendebiasi428
    @stevendebiasi428 10 днів тому +6

    There an animal somewhere in there

    • @dock_yard1149
      @dock_yard1149 9 днів тому +4

      Yeah for sure, and it has a huge passageway right into the home's interior. I'll bet that sucker has chewed a hole part way between filter closet and the compressor unit, allowing detours into crawl space and framing. Nasty.

  • @JesseDoesHVAC
    @JesseDoesHVAC 10 днів тому +2

    Sounds like non condensibles in the compressor?

    • @dbmail545
      @dbmail545 9 днів тому +1

      Sounded overfilled to me too but the compressor wasn't sweating.

    • @richardbartlett6932
      @richardbartlett6932 9 днів тому

      non condensables in the compressor Hows that work???

    • @JesseDoesHVAC
      @JesseDoesHVAC 9 днів тому

      @@richardbartlett6932 well something like air is not generally excepted to be run through a an AC compressor. Things like contamination of moisture is not going to condense the way refrigeration has been designed to condense.

  • @Level-333
    @Level-333 9 днів тому +2

    How does a coil get that dirty if a filter is being used?

    • @playlegit7
      @playlegit7 9 днів тому +1

      because of that hole in the return, it sucks unfiltered air through any gaps or cracks.

    • @dbmail545
      @dbmail545 9 днів тому +2

      A clogged filter will buckle and let dusty air in contact with the dew covered evaporator. The dust and water form a mud that becomes even more insulating when they dry. Doesn't take but a week for a leaky airfilter to cause a problem with the evaporator.

    • @MariosACandRefrigeration
      @MariosACandRefrigeration 9 днів тому +2

      mickey mouse.

    • @bobboscarato1313
      @bobboscarato1313 9 днів тому +1

      Open air return somewhere!

  • @thomasgautney5586
    @thomasgautney5586 9 днів тому +2

    Wow! Complete blockage, that won't make it cool... Any bird or rodent nests.... Have you ever seen anything like that before?

  • @chriseh09
    @chriseh09 9 днів тому +2

    Ugh that filter.....to thick for that return as it was just sucking it in!! Maybe a regular filter would be better? Take care and I appreciate the video!

    • @dbmail545
      @dbmail545 9 днів тому +1

      Doesn't matter how thick the filter is. Once it clogs it will buckle and let dust collect on the evaporator.

    • @chriseh09
      @chriseh09 9 днів тому

      So you’re saying you can’t restrict airflow with a filter that is to thick or has to high of a MERV rating for the CFM’s needed?

  • @michaelhaiden6718
    @michaelhaiden6718 9 днів тому +1

    You need to change your brand of coil cleaner

    • @richardbartlett6932
      @richardbartlett6932 9 днів тому

      yep, that was a really poor attempt at cleaning the coil...cover it with soapy water and leave it. You could see the foam on the ground was clean with no dirt dragged out the coil so it's doing nothing. The finished result was still surface dirty so it'll still be plugged .

  • @jamierushing
    @jamierushing 10 днів тому +1

    Hi bro

    • @HVACGUY
      @HVACGUY  10 днів тому

      What's up?

    • @jamierushing
      @jamierushing 10 днів тому

      @@HVACGUY nothing much it is so hot here

  • @GreyRockOne
    @GreyRockOne 9 днів тому +3

    AND to finish a proper cleaning job on the coil.. chemicals aren't cutting it, looks like a fin cleaning tool is in order..

  • @richardbartlett6932
    @richardbartlett6932 9 днів тому

    That coil cleaner is useless, it's just foamy soap. . Buy some decent stuff that actually gets the dirt out.
    Get both coils properly clean, upgrade or repair the ducting then pull the charge and weigh it back in..

  • @jasonabbott5161
    @jasonabbott5161 8 днів тому

    hmm i see that my comment was deleted😆

  • @lookgd
    @lookgd 9 днів тому

    12 subcool and 11 superheat before clean
    10 subcool and 0 superheat after indoor coil clean
    overcharged, but i dont think outdoor coil clean would make any difference

    • @throttlebottle5906
      @throttlebottle5906 7 днів тому

      probably the last guy did a gas and go to get suction pressure up, vs. find and fix the issues. it's on the right track now *pun intended*