Goodman Gas Pack compressor not cooling bad news ending

Поділитися
Вставка
  • Опубліковано 1 лют 2025

КОМЕНТАРІ • 96

  • @WaterBanana17
    @WaterBanana17 4 роки тому +19

    Great advice at the end telling all the new techs to put the unit back together and leave it like you found it.. very respectable and top notch of you as always Mr. Ted 👍🏼

  • @jasonreitz6049
    @jasonreitz6049 4 роки тому +13

    Good advice there at the end. My motto is always leave the job site just as you found it, or better. Same applies to inside the customers home...put the furniture and belongings back where you found it and clean up. Make it look like you were never there.

    • @davidscott7005
      @davidscott7005 4 роки тому +4

      So true, I just did an attic furnace, access in closet, had to move the gals shoes to get my ladder in. Started to leave and go . . . then darn remembered I hadn't put the shoes back.

  • @beieber4life
    @beieber4life 4 роки тому +8

    Tech from Chicago, great video man, picked up on a few tips.. I agree with you , always put the unit back together 100% no matter how condemned it is.

    • @beieber4life
      @beieber4life 4 роки тому

      Oh, and awesome how u Gave a shout out to all those other youtube guys we all watch haha. Just like you said, great community we all share

  • @cardsfan-ym1bj
    @cardsfan-ym1bj 4 роки тому +4

    Need more people like you in the trades,quality and pride in ones work is gone these days.Great video as always. I put a new compressor in a lil 2.5 ton nordyne unit today as well.

  • @TheWoodman064
    @TheWoodman064 4 роки тому +1

    You have no idea how much I wish you were in my area right now! We are in California and we're now starting preparation to replace our air conditioner out and you are the first person I thought of to do it! We are in the Central Valley's so if you have any suggestions I would greatly appreciate it! We are not in a major rush!

  • @FLYWHEELPRIME
    @FLYWHEELPRIME 4 роки тому +24

    Typically when you hear gurgling noises out of your compressor, you better start shaking that money tree as hard as you can.

  • @sknight0391
    @sknight0391 4 роки тому +43

    Dang Ted, when I first heard that noise 2:50 I thought you had just eaten one of those gas station hot dogs you love so much 😂😂😂

  • @Austin23191
    @Austin23191 4 роки тому +1

    Good ol' Goodman. It's lived its life. Now it's time for a shiny new Trane. Good job Ted. Keep up the good work and good luck this summer. Here in Ohio we are finally warming up and getting into the cooling season. I suspect we will have a hot one

    • @Bryan-Hensley
      @Bryan-Hensley 4 роки тому

      That Goodman is 20 years old. Why would you try to talk them into another brand?

    • @speckulator7516
      @speckulator7516 4 роки тому +2

      Bryan Hensley I’m no fan of Trane but they got lucky if they haven’t had problems with a Goodman for 20 years.

  • @wb2vsj
    @wb2vsj 4 роки тому +1

    We just replaced that exact szme unit 2 months ago. The old Goodman served us well. We patched her up and best we could but decided to upgrade to a Trane 15XL pkg unit before the summer started. WOW, what difference. I've got penguins crawling out of my air vents giving me the thumbs up.

  • @bobgallo2178
    @bobgallo2178 4 роки тому +5

    Agree Ted, put everything back together, make the guy who gives a second opinion do some work. Also, for the younger guys, I like to take my sharpie and write the value of the run cap on an inner panel, just in case rust distorted it on the cap. This is not for my benefit, as I will soon be retiring. Stay safe all.

    • @762531971
      @762531971 4 роки тому

      I did the same thing. Writing that down helps a lot

  • @dylandrymond3951
    @dylandrymond3951 4 роки тому

    Common to start then common to run should equal start to run. Should be within 10% if not the compressor is bad. Sounds like a short to ground with continuity from winding to ground. If no continuity then you are in locked rotor amps. All equal a bad compressor. Thanks again Ted. I enjoy watching your clips. Your the only guy that I'll spend more than 5 minutes watching even if its 30 minutes long. Well, you and craig from " A.C. service tech." Appreciate your hard work and time spent filming these. I'm not as patient as you.

  • @arcticarrowhvacr
    @arcticarrowhvacr 4 роки тому +3

    The ole Goodman had a fairly good run and finally gave up the ghost. She retired. Nice video Ted.

  • @TheWoodman064
    @TheWoodman064 4 роки тому +7

    I really hope that if you change that unit out or even just the compressor you post a video of it!

  • @clo2304
    @clo2304 4 роки тому +3

    Good point on how to leave unit. I agree with that.

  • @chrisgormley5751
    @chrisgormley5751 4 роки тому +8

    I had the same exact situation on Friday. R22 unit, changed the capacitor but compressor still said nope. Tried a hard start kit, compressor tried and then said "no sir I am retired." Bye bye unit.

    • @frostproff4311
      @frostproff4311 4 роки тому

      Молотком надо было ударить по компрессору.

  • @Drvanosdrand
    @Drvanosdrand 4 роки тому +2

    Words of wisdom Ted. always be a professional !

  • @sampantiliano
    @sampantiliano 4 роки тому +5

    What happens when you push that contactor in and it blows up in your face? I have no idea why people do that you have a 350$ meter. I’ve seen it happen on bigger three phase systems. At least use a screwdriver

  • @johnreiter768
    @johnreiter768 4 роки тому +6

    4:43 "air conditioner crap out" 😂😂

  • @malekrhaddad
    @malekrhaddad 3 роки тому +3

    I have a Goodman just like this from 1998. It’s working but barely. I asked a tech about recommendation on brand for a replacement unit and they said they are all manufactured by the same company, so just buy the cheapest one. Is this true?!?! I find it hard to believe the QUALITY of the components are the same across all brands, but obviously what do I know. Do you have any recommendations on makes/models that are better quality or is what that tech told me true?
    Thank you!!!

  • @hozerhvac4406
    @hozerhvac4406 4 роки тому +1

    sounded like you had too many burritos there gunslinger! Great video Mr.Ted

  • @pburchins
    @pburchins 4 роки тому +1

    I noticed the flashing on this poor condemned unit. I just got through replacing a 23 year old Goodman gas pack unit with a new Goodman neither had that type of flashing. Where can you get that flashing?? Nice detail! I enjoy your channel!

  • @Uticagreens
    @Uticagreens 4 роки тому +1

    You are absolutely correct to say other techs love to badmouth each other. But karma is a wonderful thing when after failing their final inspection, a badmouthing mechanical contractor called us in to bail them out. It felt good . . . morally as well as financially. Here in NY, we have to comply with State, County and City codes as each will differ.

  • @RayRay-nb7tn
    @RayRay-nb7tn 4 роки тому +2

    I hear it from the beginning that start winding in the Can was ng. Very true always put back like you found it, you never want to give them the chance to run their mouths. Hopefully you will get the job.

  • @scottjones7279
    @scottjones7279 4 роки тому +1

    Good advice to leave it in as good or better shape than when you arrived, put it back together

  • @danmuehlbauer2602
    @danmuehlbauer2602 4 роки тому +9

    Wouldn't checking for grounds and checking the capacitor be the first two things to check before resetting a tripped breaker?

    • @speckulator7516
      @speckulator7516 4 роки тому +2

      Josh Smith Today, We ran across two of the old round Comfortmakers or “Comfortakers” as Ted likes to jokingly call them, from the late 70’s - early 80’s that are still chugging along.

  • @zekenzy6486
    @zekenzy6486 4 роки тому

    Great Video. I was learned checked bad compressor on your video today. Have a nice weekend ^_^

  • @gerardotrevino2232
    @gerardotrevino2232 4 роки тому +3

    Please never push in the contactor with your finger use an insulated screwdriver

  • @Eddy63
    @Eddy63 4 роки тому +1

    Good troubleshooting Ted ... Good vid ...

  • @serge.crispino418
    @serge.crispino418 4 роки тому +1

    Circuit breakers do not trip without reason - short to earth short between coils / phases. You do great work - I would not have used my finger to push in the contactor after you reset the breaker the first time - you had no idea what was shorted or where - I would have done a insulation test / megger before applying power and if you really needed to push the contactor in I would have used an insulated screw drive - please continue to work safely.

  • @RCM442
    @RCM442 4 роки тому +1

    Wish you were in my area..compressor in my system made a similar noise and had gotten so hot the thermal/sound blanket melted to it!

    • @dljones61
      @dljones61 4 роки тому

      RCM or Ted or anyone with experience.
      what’s your thoughts on those sounds wraps for the compressor, I just now installed one on my AC unit. I’ve had it for years but was not sure if the heat buildup would be something to worry about so I put off installing it. Wife’s complaining about everything with this covid 19 lockdown and figured it would be one less thing for her to complain about.
      After reading your comment I’m now having second thoughts and wondering if it would heat things up causing damage. Thanks Dave

    • @speckulator7516
      @speckulator7516 4 роки тому

      super Dave I like them, they make unit quieter.

  • @mushtaqmalik8292
    @mushtaqmalik8292 4 роки тому +1

    Good tips for newB Ted thank you sir!

  • @thedane6483
    @thedane6483 3 роки тому

    totally agree! dont let anyone bad mouth you

  • @MrStatic101
    @MrStatic101 3 роки тому

    Great video!!

  • @watermanone7567
    @watermanone7567 4 роки тому

    What happened to the copper head snake? Good call on the ac unit.

  • @Ted_E_Bear
    @Ted_E_Bear 4 роки тому +4

    Are you one of “The Bad News Bears “ ????

  • @universalservicetechust3578
    @universalservicetechust3578 3 роки тому

    That’s a super tech 👍🏼

  • @jasonreitz6049
    @jasonreitz6049 4 роки тому

    Just did a changeout today on a 9 yr old Bryant. Found the common terminal on the compressor completely blown out of it. Haven’t seen that in a while.

    • @Bryan-Hensley
      @Bryan-Hensley 4 роки тому

      Ran on low freon too long. Keeps the compressor scalding hot which breaks down the rubber seal.

  • @puretoronto
    @puretoronto 4 роки тому +2

    You buying used gloves from Steve?

  • @stevebennett1563
    @stevebennett1563 4 роки тому

    Ted get you one of those rechargeable small power screw drivers from Amazon use the same plug as your smart phone works great

  • @robbrantley8627
    @robbrantley8627 4 роки тому

    I have a question but not about this video, in the past I have watched what I believe is straight MAPP gas to braze with using 15% silver? Is that correct?

  • @123412144
    @123412144 4 роки тому

    Love your videos!

  • @sergioaguirrevalle6212
    @sergioaguirrevalle6212 4 роки тому +3

    I've watched you actuate the contactor with your finger in alot of videos. Dude that's such terrible practice in general. You have a meter, use it. Some bozo is gonna watch this and think it's okay. If you practice good habits then it doesn't matter if its single phase 240 or 3 phase 460 you can have the peace of mind that you won't get shocked.

  • @hvacwonders7081
    @hvacwonders7081 4 роки тому

    why didn’t you put a hard start kit on it ?

  • @ovalman
    @ovalman 4 роки тому +6

    I have ran into capacitors feeding back voltage. That’s what I thought it was..... but no nope. She’s toast. I hope they bought a new unit from you, a new compressor in that thing is not worth it.

    • @RiceRiceBaby54
      @RiceRiceBaby54 4 роки тому

      I don’t think I would even entertain replacing the compressor in that thing.

    • @speckulator7516
      @speckulator7516 4 роки тому +1

      If you change the compressor you still have 20 YO R22 unit.

  • @HVACingMyWay
    @HVACingMyWay 4 роки тому

    Changed a couple of those package units lately

  • @rfbedell347
    @rfbedell347 4 роки тому

    Here is a prime example of "lack of maintenance", resulting in this situation. Another reason why I don't like single pole contactors.

  • @saulsanchez9531
    @saulsanchez9531 4 роки тому +1

    you're very honest guy like me

  • @E150GT
    @E150GT 4 роки тому +2

    If only the discount tire guys wouldnt need to move my seat forward just to drive my car 6' into the bay and then leave it that way the world would be a better place

    • @JasperJanssen
      @JasperJanssen 4 роки тому

      They can’t put it back the way they found it, that’s a matter for personalized adjustment.

  • @MrAniven
    @MrAniven 4 роки тому +2

    That pretty dangerous putting your hand on the contactor like that

    • @luisboiso4961
      @luisboiso4961 4 роки тому +1

      Thought the same thing. Did that last week and the thing arc flashed on me luckily I pushed it in with a insulated screwdriver still scary ass hell. I learned from a old journeyman that the only thing you find out by bumping in the contactor is it will turn on.

    • @speckulator7516
      @speckulator7516 4 роки тому +1

      Andrew, he swears he been doing it his whole career and never been bit!

    • @speckulator7516
      @speckulator7516 4 роки тому

      Luis Boiso will it start up? is all you’re trying to find out when you stick the contactor.

  • @marionaiken9299
    @marionaiken9299 4 роки тому

    When I see those units old Goodman’s rather Ac call or heat call I’m
    Checking heat exchangers

  • @ismackherbiehind
    @ismackherbiehind 4 роки тому

    Yea I would say it’s time for a new one, they got their money’s worth out of that one.

  • @russellhancock9765
    @russellhancock9765 3 роки тому +1

    I like Steve Lav and Your Videos, but the young guys, I don't care much for. I guess it is because I am an old guy too.

  • @97Napkins
    @97Napkins 4 роки тому

    Lol sorry phone overheated AKA I'm not doing nothing else cuz I know its toast. I woulda prob looked at compressor terminals.

  • @ss03pp1
    @ss03pp1 4 роки тому

    You don't need your drill. Spin thos 5/16s out by hand

  • @damarcojackson1005
    @damarcojackson1005 4 роки тому

    All new techs....DO NOT PUSH CONTACTOR IN WITH YOUR FINGERS....DONT BE A TOUGH GUY...😏

  • @donnierobertson3088
    @donnierobertson3088 4 роки тому

    Good job

  • @mdovideo1414
    @mdovideo1414 4 роки тому

    That contactor looks burnt.

  • @joecorbin5158
    @joecorbin5158 4 роки тому +1

    Holding power......???? Geez. That noise you hear is the anticipation timer for the skin on your right arm up to your elbow.....if your lucky you have safety glasses on so when a motor terminal fails with you in front of the old Bristol.....you won’t lose anything that won’t grow back. Why don’t you just wedge a piece of # 16 into the armature when you get on a job. New techs need to start with a meter not resetting protective circuit breakers

  • @IslandbreezeMechanical
    @IslandbreezeMechanical 4 роки тому +2

    Sorry but I won’t watch Johns channel, and you know why. I am not going to get into it here.

    • @TedCookHVAC
      @TedCookHVAC  4 роки тому +1

      I assume you gave money like I did... we were all mad... I just decided to let it go.

    • @IslandbreezeMechanical
      @IslandbreezeMechanical 4 роки тому +3

      Anti DIY HVAC I did not and knew he was a scammer

  • @sziltner
    @sziltner 4 роки тому

    Trane time! 👍🏻 😉

  • @genedrawdy9679
    @genedrawdy9679 4 роки тому

    Good man HVAC hack job the HVAC should not do their own wiring is what you did. Two wires in a Romeo connector and NO cover on you cutoff switch!!!!

  • @steveblake8766
    @steveblake8766 4 роки тому

    #10 thumbs up

  • @bart1meuz
    @bart1meuz 4 роки тому

    They getting a second opinion I am guessing?

    • @danmuehlbauer2602
      @danmuehlbauer2602 4 роки тому

      I hope so. Fan running slow.....looks like a lost leg and that was never checked

  • @doubledose3650
    @doubledose3650 4 роки тому +1

    manufactured october of 2000.

  • @genedrawdy9679
    @genedrawdy9679 4 роки тому

    Not safe and does NOT meet NEC code!!!

  • @genedrawdy9679
    @genedrawdy9679 4 роки тому +1

    Not Qualified for electrical.

  • @douro20
    @douro20 4 роки тому

    Never heard anything good about Goodman.

  • @michaelhaiden6718
    @michaelhaiden6718 4 роки тому

    I dot like to lisencd to people with vulgar mouths

  • @danielmorrow8881
    @danielmorrow8881 4 роки тому

    I know how a work and the only reason why you don't want people working on there system is because you want money

    • @bobgallo2178
      @bobgallo2178 4 роки тому +1

      That is bull___. For starters, ya must be certified to handle refrigerants. There are some parts in different units that hold a charge, even after the power is off. Best left to the professional. In the last 35 yrs. I have seen what not understanding how the equipment can result in.

  • @mechanictaft4848
    @mechanictaft4848 4 роки тому

    Ok doesnt make sense compressor is $80 bucks really oh wait i forgot you cant be out in heat more than 5 mins you will wither away wow

    • @oldhandyluke
      @oldhandyluke 3 роки тому

      dude that unit was nearly 20 years old, its done its job. Its not worth that amount of time and effort to put in a compressor.