thanks so much senior we all learn from each other but at least I've got some few things from you at least and i cant fail to give you a credit in what ever ur doing man however i would like to know what rate of contactor and relays would be used in an automatic change over switch of about 250amps because currently i am using manual change over of 200amps please have some time and explain also in big power consumption, thank you so much once again for such an educative channel.
Thanks so much for this video. please how do you size these components especially the contactors, the relays and the total size of an ATS, assuming there 3 sources? utility, Gen 1 - 150kva and gen 2 - 100kva gen. Thank you
Looked at your video and suggest you learn more about this subject matter. The drawing at the end seems incomplete - need more information to best understand its dynamics. You indicated if both circuits came on together will cause a short circuit, as surely being same power value works like parallel batteries? Yes, we can connect both the mains and generator together as power station does it daily. That's providing they are synchronised first as both supply phase angles difference can be catastrophic.
Thanks very much for the lectures but after this how am I going to have the control diagram and the other thing if I can be out of what you are explaining where do you connect the wire from from the device to the generator to star outomaticaly without the manual rope dracking position?.
Thanks for watching ..... That depends on the type of the generator you have... or the generator need to have the capability to start automatically....... This video has circuit diagram at the end...... See if it helps. Then come back to me.
Thank you very much for lecture. What I want to know is that, I need a control diagram of Automatic change over (ATS) that can start generator on its own with any manual operation. When the main power fail the generator should come ON Automatically without any operator then when main restore power its should send signals to the generator in order stop. Please any knowledge about let me know OK. My regard to you Alicious Alpha Kamara. From Sierra Leone
@@electreca1 Still waiting for this video. Also what if I dont want a delay - for a backup that has Lithium or AGM batteries and a load of Internet Modems that I want an immediate 20millisecond switch from mains to backup, do I still need these timers?
Very informative. I’m a woodworking guy, and a novice in electrical automation. I am trying to automate my shop vac filter cleaning. I have a 2kw 220V shop vac, and a small 200W motor that runs the filter cleaner. I start and stop the shop vac with a remote controller. Today I run the shop vac filter cleaner manually. I would want to run it automatically with a time delay, such that it starts 5 sec after shut down of shop vac, and runs for 10-15 sec, and then shuts down. This repeats after ech time I use the shop vac. Do I need a full set of interlocking contactors, relay and timers to ackomplish my goal? Can you gaide me, or better still, could I ask you to create a UA-cam video on this topic, as I am sure I am not the only one struggling with this task.
That's very dangerous, it will be burn the Changeover switch most likely all the installation, the alternator(generator) will burn..........BUT it really had for all of the above to happen.... Because in the Changeover switch there is a protection( interlock) which locks out the contactor (which is out of phase) both electrically and mechanically. Meaning Both contactor can never engage at the sane time.
Thanx for the question........... I don't know how much you know about this .... but THE 2 CABLES GOES TO NORMALLY CLOSED OF THE MAIN RELAY.. tell me if this answers your question.
In most cases We switch power between 2 sources, the utility and backup(like generator). This is why you will have 2 contactor. You can use 3 contactor if you have 2 backup power(like gen set and solar) Were your utility power goes off and the priority backup fails, then second one comes.
Already made changeover switches can really expensive......from as low as 40k to 300k. now that price is determined by the rating, brand and mode of control... but custom made can at least cheaper than already made one.
I will definitely do that.......but for the 2cable(signal cable),first the generator can be closed or open start..... That cable goes into the main contactor relay NC for closed signal, for open signal it's the reverse
@@electreca1 thanks alot for your guidance...I have a 5kw generator that doesn't have signal points where I can input the two cables.how can I go about it
@@electreca1 I don't know much about electrical rating but my house is a 3 bedroom flat with one sitting room, i have 4 Ac unit which are 2Hp and 2 television, 2refrigerator, microwave and basic household equipment, so how much will it cost me
Your content... good knowledgeable...in easy language...... salute you
Weldone technician. Please can you tell us the EXACT NAME OF THAT RELAY AND ITS FULL VIDEOS AD PICTURES.
I hope to hearing from you soon. Thank you
Your contents are very excellent. Keep it up.
Is possible to use only one timer in an automatic changeover switch?
It's good to have timers at both side, but if have one then use it on generator circuit.
thanks so much senior we all learn from each other but at least I've got some few things from you at least and i cant fail to give you a credit in what ever ur doing man however i would like to know what rate of contactor and relays would be used in an automatic change over switch of about 250amps because currently i am using manual change over of 200amps please have some time and explain also in big power consumption, thank you so much once again for such an educative channel.
very good & inspiring electrical lectures,be blessed more,i need 2 be fully in touch with u,thanx 🤣🤣🤣🤣👍👍👍👍
Very nice and I'm appreciate u. Can explain the the terminal numbers for the contractors, auxiliary block, timer, relays and face failure
quite informative. looking forward to more videos
Thank you...........more video are coming.
Thanks alot, the video of the wiring of these devices and the full detailed schematic for it.
Good lecture, looking forward for the circuit diagram
Mr engineer your videos are helpful to me, thanks you for sharing,i want to know how to control a traffic lights using timer and contactor thanks you
Hey ... Can we have conductor been control by the relay and timer
Good work, if possible get all the devices and connect the entire circuit for demonstration
I actually made a video here ua-cam.com/video/ITLfk06nIy4/v-deo.html
@@electreca1 OK thanks I will check on it
Thanks so much for this video. please how do you size these components especially the contactors, the relays and the total size of an ATS, assuming there 3 sources? utility, Gen 1 - 150kva and gen 2 - 100kva gen. Thank you
the information is very user friendly.
Thank you
How do you connect battery charge with the ats
Looked at your video and suggest you learn more about this subject matter. The drawing at the end seems incomplete - need more information to best understand its dynamics. You indicated if both circuits came on together will cause a short circuit, as surely being same power value works like parallel batteries? Yes, we can connect both the mains and generator together as power station does it daily. That's providing they are synchronised first as both supply phase angles difference can be catastrophic.
Thanks very much for the lectures but after this how am I going to have the control diagram and the other thing if I can be out of what you are explaining where do you connect the wire from from the device to the generator to star outomaticaly without the manual rope dracking position?.
Thanks for watching ..... That depends on the type of the generator you have... or the generator need to have the capability to start automatically....... This video has circuit diagram at the end...... See if it helps. Then come back to me.
@@electreca1 Sir, can 8kva and 3.5watt generator off and on automatically?
Hello, I need to know more on remote start on Perkins generator
Weldone sir, please can I use a voltage monitor for a single Phase changeover instead of a 3Phase monitor
Most phase monitor work for both 3 and single phase.
Thanks it's very good explanation
Congratulation 4 the cool videos uko county gani?
Thankyou sharing your knowlage for others❤🎉😮
Thank you for your lecture which is good for me too
Thank You Very Much, Sir.
5 Stars = 🌟🌟🌟🌟🌟
👍
Very nice
Thank you very much for lecture.
What I want to know is that, I need a control diagram of Automatic change over (ATS) that can start generator on its own with any manual operation.
When the main power fail the generator should come ON Automatically without any operator then when main restore power its should send signals to the generator in order stop.
Please any knowledge about let me know OK.
My regard to you
Alicious Alpha Kamara.
From Sierra Leone
No problem .....That's video is coming soon.
And thanx for watching.
@@electreca1 Still waiting for this video. Also what if I dont want a delay - for a backup that has Lithium or AGM batteries and a load of Internet Modems that I want an immediate 20millisecond switch from mains to backup, do I still need these timers?
Thanks
Thx for giving us some experience,
Nice Video.. Keep up the great work 👍u av just earned a subscriber 🙏
Awesome, thank you!
Pls kindly show how the component are being wire to make up a automatic change over
Very informative. I’m a woodworking guy, and a novice in electrical automation. I am trying to automate my shop vac filter cleaning. I have a 2kw 220V shop vac, and a small 200W motor that runs the filter cleaner. I start and stop the shop vac with a remote controller. Today I run the shop vac filter cleaner manually. I would want to run it automatically with a time delay, such that it starts 5 sec after shut down of shop vac, and runs for 10-15 sec, and then shuts down. This repeats after ech time I use the shop vac. Do I need a full set of interlocking contactors, relay and timers to ackomplish my goal? Can you gaide me, or better still, could I ask you to create a UA-cam video on this topic, as I am sure I am not the only one struggling with this task.
Okay, thanks, can you take me through or send me a wiring diagram of an automatic changeover that comprises on 1 relay and 2 contactors, kindly....
Bro can you give me a diagram for ats to connect my single phase generator and the component
Hello bro, I hope you are okay, can you kindly explain how to wire a star Delta with a soft starter
He's I will on that
Thanks for watching.
Thanks..and please what can happen if main supply and generator releases power at the same time.?
That's very dangerous, it will be burn the Changeover switch most likely all the installation, the alternator(generator) will burn..........BUT it really had for all of the above to happen.... Because in the Changeover switch there is a protection( interlock) which locks out the contactor (which is out of phase) both electrically and mechanically.
Meaning Both contactor can never engage at the sane time.
Okay thank you
Also you are going to electrocute someone maybe working on the main line
Nice one
Understood next please i want to watch practical
In a 3 way automatic changeover switch do I still need an interlock with 3 contactors
yes
Can one use single phase generator for automatic changeover
Ooh Yes.
Thanks for watching.
@@electreca1 Alright sir, thanks a lot
Am grateful to you sir.
I applicate that 👍
The two cable you say we have to connect from the to start the gen. Where exactly is going to connect for the gen
Thanx for the question........... I don't know how much you know about this .... but THE 2 CABLES GOES TO NORMALLY CLOSED OF THE MAIN RELAY.. tell me if this answers your question.
how do u you connect a signal cable to start the generate for the case of this change over you have made
The Mains(Grid) relay controls the signal.
Please can you?give the complete wiring diagram.
Sir please I want demo and digram LP/HP pressure switch and oil pressure switch conet to compressor Ammonia gram comp
Hi, most cases i have seen three contacters inside the board but you said we only need two contacters, why?
In most cases We switch power between 2 sources, the utility and backup(like generator). This is why you will have 2 contactor.
You can use 3 contactor if you have 2 backup power(like gen set and solar) Were your utility power goes off and the priority backup fails, then second one comes.
@@electreca1 okay, no wonder i saw 3 contactors there because their mains, 150kva lister, and 8kva single phase were all connected to the contactors
Where are you from
How can I get the full connection
soon
OH,does good
How much is an automatic change over in Kenya? And where can I buy
Already made changeover switches can really expensive......from as low as 40k to 300k.
now that price is determined by the rating, brand and mode of control...
but custom made can at least cheaper than already made one.
Hi.kindly show us how to incorporate all this into working and also where to put the two cables from panel to generator starter
I will definitely do that.......but for the 2cable(signal cable),first the generator can be closed or open start..... That cable goes into the main contactor relay NC for closed signal, for open signal it's the reverse
@@electreca1 thanks alot for your guidance...I have a 5kw generator that doesn't have signal points where I can input the two cables.how can I go about it
@@eliudkariuki.3083 Whats the brand of your generato?
@@electreca1 it's a wasp generator
Hey bro.still hoping to hear from you
gud how can i get yuh contacts
There is an Email on channel bunner
Where is your school
Are you in Ghana?
No, Kenya
How do I get in contact with you, can you build one of this for me and what will be the cost
The cost depends on the rating.
@@electreca1 I don't know much about electrical rating but my house is a 3 bedroom flat with one sitting room, i have 4 Ac unit which are 2Hp and 2 television, 2refrigerator, microwave and basic household equipment, so how much will it cost me
hello
Good🎉
Kindly make a practical video for the change over installation. I wish to know the meaning of all terminals in the contactactors. Kindly help bro.
Ok no problem I'll
Super
Quite interesting
Thank you
Hi bro,can u send me wiring diagram pls!
Find the wiring circuit at end of the video
Hi bro thks 4 ur reply,but i cant see the wiring diagram clearly can u sent it to me wiz all the detail by mail pls
Oh Thanks
Congrats
Are you Kenyan
@@merlinmartin7065 Nop though I live here.
@@electreca1 where is your work shop I would love to visit you if you don't mind
thanx for the the lecture
can i get your contact info
electreca.workshop@gmail.com
Good lake
Good job sir can I learn electrical panel from u sir Maybe on WhatsApp
Hello
Ya Know.... sometime you have to get hit over the head to understand...Thanks
Skip...
Your welcome Skip