ATS for Automatic Generator Start and Stop / The Best Video to learn all about..!

Поділитися
Вставка
  • Опубліковано 24 гру 2024

КОМЕНТАРІ •

  • @ElectroAcademyEA
    @ElectroAcademyEA  Рік тому +9

    🔔Help Electro Academy grow! 🔔
    Your support can make a big difference! 😍
    If you appreciate the efforts behind these educational videos, please subscribe - it’s free and just a click away.!🙏🏽
    Additionally, if you can contribute, you can become a patron and support our mission of sharing knowledge with students and professionals around the world: patreon.com/ElectroAcademy 🙌
    I am deeply grateful to our first sponsor! Your kind gestures motivate us to continue creating quality content. Let’s build this community together.!🏆
    THANKS .!
    - Sudarshan, Creator of Electro Academy

  • @abdiismael6138
    @abdiismael6138 Рік тому +1

    this is absolutely comprehensive videos that need to be supported in every means

  • @faridahmedrana2688
    @faridahmedrana2688 Рік тому +1

    Sir, You are the great teacher for electrician. May Allah bless you. Thanks.

  • @enochmeshullam2814
    @enochmeshullam2814 Рік тому +1

    I am very thankful to you Sir for this very informative video you have shared with those of us who are in a real need for knowledge of ATS control phenomenon. I love the video. Much thanks and great appreciation. Cheers

  • @okonkwoandrew5880
    @okonkwoandrew5880 9 місяців тому +1

    you are a teacher with teaching qualities I keep to your videos.

  • @tettehphilipkwei3905
    @tettehphilipkwei3905 11 місяців тому +1

    Sir you where my teacher you are the best 👍🔥

  • @zenebehagos3537
    @zenebehagos3537 Рік тому +1

    10q so much for taking time do this lecture and took time to upload it

  • @kamaphilemon2089
    @kamaphilemon2089 8 місяців тому +1

    Thank you Sir. You effort is much appreciated.
    Best ATS video ever

  • @davidshirindzi4653
    @davidshirindzi4653 2 місяці тому +2

    I have been looking for these , too long.

  • @morrismaneae3634
    @morrismaneae3634 Місяць тому +1

    Salute you guys..great lecture❤

  • @heartperson4987
    @heartperson4987 2 роки тому +1

    So excellent video about automation..
    Thanks for like this video from Bangladesh

  • @anaskarim7033
    @anaskarim7033 Рік тому +1

    what a wonderful explanation it was . thanks a lot to the channel

  • @WilliamsBright-z2c
    @WilliamsBright-z2c Рік тому +1

    Very clear and understanding,thanks for this information

  • @pattersonbogar6380
    @pattersonbogar6380 2 роки тому +1

    A well explained information supported with clear pictorial diagram. Thank you for dedicating your time and effort to share your knowledge on this particular topic. Thank you...much appreciated

  • @princeukomatthew5544
    @princeukomatthew5544 5 місяців тому +1

    Insightful and educative ❤

  • @mytv5921
    @mytv5921 6 днів тому +1

    Excellent describe

  • @ildarhamrayev
    @ildarhamrayev 2 роки тому +2

    Very nice and vivid current flow is illustrated. Makes everything clear how does it work. And explained simple. Much of thanks to u !

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому +1

      Thank you👍

    • @ildarhamrayev
      @ildarhamrayev 2 роки тому +1

      @@ElectroAcademyEA waiting for more videos like that. if u can make industrial machines

  • @ayojoseph4571
    @ayojoseph4571 5 місяців тому +1

    This is very clear, thanks

  • @ashokshah7388
    @ashokshah7388 2 роки тому +1

    wow nice very very usefull video thank you

  • @GAMINGYT-eg6xj
    @GAMINGYT-eg6xj 2 роки тому +2

    very good video sir thanks

  • @polyfaruk190
    @polyfaruk190 2 роки тому +2

    Very good.thank you sir

  • @NickTheHunter
    @NickTheHunter Рік тому +1

    Thank you so much, sir! A very good quality video! Much appreciated!

  • @venanciojpena1669
    @venanciojpena1669 Рік тому +1

    Very interesting & really appreciated

  • @AliShan-lv9pf
    @AliShan-lv9pf Рік тому +1

    I love you 😘 great work and very helpful diagram video sooo thanks.............

  • @agustinussonoto7794
    @agustinussonoto7794 2 роки тому +1

    The best tutorial..

  • @bijusenthil
    @bijusenthil 2 роки тому +1

    Good explanation

  • @thesportsbar7
    @thesportsbar7 2 роки тому +1

    Very clear and understanding

  • @ElectroAcademyEA
    @ElectroAcademyEA  2 роки тому +3

    Dear All,
    DPDT relay means Double Pole Double Throw Relay.
    Double pole is mispronounced here as Double port @ 1:32.
    Kindly take a note on this, when viewing/listening to the video.
    Regards,
    EA.

    • @gombanirorichard9759
      @gombanirorichard9759 2 роки тому +1

      The start connection is the one from AUTOMATIC button on generator screen?how to connect it on that relay?thank u

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      Best way is to check with the generator supplier.
      Then its easy with relative brands.

  • @abudaoud1310
    @abudaoud1310 2 роки тому +2

    Thanks for made the video🌹

  • @kingsleymakoi3343
    @kingsleymakoi3343 Рік тому +1

    Good.. nice thank you

  • @IsraelKero
    @IsraelKero 8 місяців тому +1

    Very helpful thanks man

  • @amissahjoojo7961
    @amissahjoojo7961 2 роки тому +1

    A very good tutorial 👌

  • @GAMINGYT-eg6xj
    @GAMINGYT-eg6xj 2 роки тому +2

    thanks sir,thank you so much

  • @alkararali3548
    @alkararali3548 Рік тому +2

    شكرا لك أخي الكريم على هذا الفيديو المهم استمر بالعطاء
    يا حبذا لو تعمل لنا فيديو اخر عن كيفيه اداره ATS ثلاث مراحل كهرباء الدولة الحكومية وكذالك كهرباء الاشتراك في الحارة وكهرباء مولد البيت في الداخل كيف الىبط بينهما

  • @anhtuannguyen2248
    @anhtuannguyen2248 Рік тому +1

    Very good, thanks.

  • @kamikazeray4866
    @kamikazeray4866 2 роки тому +1

    Thanks a lot
    It's very useful 👍💕

  • @JimmyHorope-fq5zx
    @JimmyHorope-fq5zx 7 місяців тому +1

    That was helpful.

  • @sheriffdeen175
    @sheriffdeen175 2 роки тому +1

    Thanks sir

  • @hassanhussein3703
    @hassanhussein3703 2 роки тому +1

    Thank you

  • @elohorolokpa
    @elohorolokpa Місяць тому +1

    Excellent video.
    Sir, how do i incorporate a switch to this ATS whereby when grid goes off and the generator starts, i can use the switch to put off the generator from inside the house if the generator is not needed at that time.
    Thanks

    • @ElectroAcademyEA
      @ElectroAcademyEA  Місяць тому

      You can arrange an additional two pole breaker (inside of your house) series to the generator control circuit breaker.
      It can be used for this purpose.
      However, for these type of work you need to get help from a good electrician.

  • @sandyfortuno3194
    @sandyfortuno3194 Рік тому +1

    nice

  • @Akolkar2
    @Akolkar2 Рік тому +1

    Pl show timer s T1 T2 in video with colour animation. Thanks again for video,👌👌👌👌👌

  • @adammangal8530
    @adammangal8530 Рік тому +1

    Hello, where do we get the neutral for the load from? How do we ensure there is always a neutral cable from both supplies without them interconnecting?

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      From the generator supply, you get separate neutral cable.
      So, the two neutral cables need to be connected separately, as shown on the video.

    • @adammangal8530
      @adammangal8530 Рік тому +1

      @@ElectroAcademyEA It only shows the 3 active wires going to the load, how does the neutral wire connect to the load?

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому +1

      Sorry for that I have not shown it in the video.
      As done for the 3 power lines, you need to get two neutral lines separately from the grid and from the generator to the junction box, and connect it.
      From the junction box, only one neutral line to the load.
      3 pole contactors on grid side and generator side, need to be changed with 4 pole contactors to provide neutral wire through it.

    • @adammangal8530
      @adammangal8530 Рік тому

      @@ElectroAcademyEA 4 pole contactor! okay thank you very much

  • @michaelisongekwere1402
    @michaelisongekwere1402 2 роки тому +2

    This was an explanation thank you Sir please what are components that make up this design and connection? I know 2 magnetic contactor, 1 phase failure relay, 3 Double pole double throw 8 relay, 2 AC double pole breaker, 5 Timers
    Secondly on the battery relays you connected port 1 and 3 of start and port 1 and 3 of stop to what components is it 1 and 2 start- push and 3 and 4 stop-push components?

  • @renebangura8138
    @renebangura8138 Рік тому +1

    OK but I have a question how would this design change if you you wanted to build an ATS that changes between 3 sources. An example would be if you had grid, solar backup and generator in that priority order. Would be great to know as there's almost no info available on this specific topic

    • @JOSE-tt8tb
      @JOSE-tt8tb Рік тому

      Bro, it’s simple, just make another same set of panel and it’s out considered as second prior after the grid, for example just do this circuit with solar and generator and it’s out again do with grid supply, in this way you can make infinite number of power sources 💪😉

    • @ElectroAcademyEA
      @ElectroAcademyEA  Місяць тому

      Building an Automatic Transfer Switch (ATS) that can switch between three sources - grid, solar backup, and generator - in a priority order requires a combination of relays, contactors, and control logic to manage the transitions seamlessly.
      Will try to do a separate video on this, when time permits.

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 Рік тому +1

    Please sir, the relays and timers for the gen auto start are they DC or AC?

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      Battery connected relays and timers are DC.
      All others are AC.

  • @SivaKumar-zi3dd
    @SivaKumar-zi3dd 11 місяців тому +1

    ❤❤

  • @said_words
    @said_words Рік тому +1

    great work ,which software have you used

  • @YJTECH85
    @YJTECH85 27 днів тому +1

    ♥️♥️

  • @rolandtoophanie5185
    @rolandtoophanie5185 2 роки тому +1

    Hey sir what type of timer relay used. Is all the timer relay ON DELAY?

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому +1

      All the timer relays used here are ON DELAY type.
      Actually we can use ON DELAY timer relays for average OFF DELAY functions also, by using NO and NC contacts properly.

    • @rolandtoophanie5185
      @rolandtoophanie5185 2 роки тому

      Ok thank you. I'm going to build a system exactly like this soon for backup system

    • @rolandtoophanie5185
      @rolandtoophanie5185 2 роки тому

      Is there any other way I can get in contact with you to get some more information about the parts to be purchased?

  • @SlaviTerziev
    @SlaviTerziev Рік тому +1

    great

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 Рік тому +1

    Thanks for the lessons, please can I apply this to a single Phase? And can I have the circuit diagram for this video, thanks
    Thanks in anticipation

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому +1

      Thank you.
      You can use this for single phase generator wiring too.
      Instead of 3 phase 3 wires on power side of two contactors, use live wire and neutral wire on L1 and L3 terminals.
      Keep L2 terminal empty.
      Control wiring is the same as shown in this video.

    • @elohorolokpa
      @elohorolokpa Місяць тому

      ​@@ElectroAcademyEASir, if this procedure for single phase Is followed accordingly for a generator with battery and key starter, will the generator turn on automatically when the grid supply is restored

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 Рік тому +1

    Thanks for the lessons, please can I apply this to a single Phase? And can I have the circuit diagram for this video, thanks

  • @kyawzin2639
    @kyawzin2639 8 місяців тому +1

    thank

  • @cabs79
    @cabs79 Рік тому +1

    Is this diagram can be in actual wiring of the ats panel?

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      Yes. Basic arrangement is this.
      Changes are there according to the different models and brands.

  • @dominicthure5943
    @dominicthure5943 2 місяці тому +1

    Very educational platform, how would I get live discussion

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 місяці тому

      Thank you.
      We have not done a live discussion yet, but will be hoping to do some very soon.

  • @adamsoladipupo3390
    @adamsoladipupo3390 Рік тому +1

    Well done sir, pls how will one connect the ats for single phase generator to auto start/stop

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      For single phase generator, same two magnetic contactors can be used.
      Instead of three phase lines, live wire and the neutral wire can be taken through it. One terminal on both contactors will be empty.

  • @faryazch
    @faryazch 2 роки тому +1

    This design is suitable for Single Phase Gride and Single Phase Generator?
    and how many self start attempt?

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      Yes. You can use it on single phase grid with single phase generator.
      Normally, generator should start with one start attempt.
      If there are dificulties with starting, we need to check and correct it first.

  • @irshadumerfarooq7901
    @irshadumerfarooq7901 2 роки тому +1

    Great Sir, Do you have 3 power source ATS model

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      Generally, control circuit needs only a single phase supply or direct current supplied through a battery, to operate magnetic contactors.

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 Рік тому +1

    Thanks sir, please can i see how the start and stop connection is done physically, with stop and start button.
    I will be grateful if granted.
    Thanks

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      Please try the video on below link.
      ua-cam.com/video/_6WhieL50GI/v-deo.html&feature=share9

  • @lenardfritz1020
    @lenardfritz1020 2 роки тому +1

    Very Nice . Can we have a ladder diagram of the ATS explained above?

  • @ousmanfadera8310
    @ousmanfadera8310 2 роки тому +1

    great lectures credible and amazing. any chance of scholarships on electrical and electronic engineering into your reputable and renowned Electro Academy..

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      We currently teach only through UA-cam media.
      We may consider this when we start our learning center soon.

  • @michaelisongekwere1402
    @michaelisongekwere1402 2 роки тому +1

    Please if am to design this ATS for a load wattage of 25,000watts in facility what is the the size of panel by millimeters I should request to buy? That would contain these components

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      Actually the size of the panel is to be decided according to the component sizes and the relevant wiring work too. Some component sizes might be different according to their brands also.
      If you are not an Electrician, better to get help from one to get good idea on sizing of the panel board.

  • @ibekwechidithompson4853
    @ibekwechidithompson4853 Рік тому +1

    Thanks for the video, but please can I see its physical build-up

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      Thank you.
      Standard arrangement is shown here with current flow animation, mainly for the ones who need to understand the automatic starting of the generator easily.

  • @seiduafataw9821
    @seiduafataw9821 Рік тому +1

    After that how does the generator start if the grid is out.

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      Through battery power

    • @seiduafataw9821
      @seiduafataw9821 Рік тому

      And what? Meaning the the battery have to be charge right?

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      Yes. You need to have a battery charger (powered by grid side) to keep the battery fully charged, in order to start the generator during a power outage.

  • @peterloulee8845
    @peterloulee8845 Рік тому +1

    Are you doing relay switch for video

  • @lappyajay1
    @lappyajay1 2 роки тому +1

    Can we common all the neutral...??

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому +2

      No.
      Grid and generator side neutral lines need to be kept separated, to enable safety features like RCDs to work correctly.

  • @sarmadali1991
    @sarmadali1991 2 роки тому +1

    Can you explain how connect swich of generator to run and stop generator auto. Please draw wiring diagram for connections

    • @earthenergyhex
      @earthenergyhex 2 роки тому +1

      yes I would like to see the same

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      Generator manual start button wires need to be connected to the two green points marked as start connection on the diagram for automatic starting.
      Generator stop button wires need to be connected to the two red dots marked as stop connection for auto stopping of the generator.
      If you need an auto - manual switch for generator, connection from the battery can be provided through a 2 pole breaker.
      This breaker OFF position will act as generator on manual starting only, still the power will automatically change over after you start the generator manually.

    • @sarmadali1991
      @sarmadali1991 2 роки тому

      @@ElectroAcademyEA
      I didn't understand you can you draw wiring diagram to explain that
      Thank you ❣️❣️❣️

  • @marounabimoussa4374
    @marounabimoussa4374 2 роки тому +1

    Excellent explanation! Just one question though: contactors have 3 main poles and 2 accessory poles?? The ones I usually see have just one accessory...

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому +1

      Normally contactors have 2 auxiliary contact points, NO and NC.
      But, according to the requirement, you can purchase heavy duty contactors with 4 auxiliary contact points, two NO and two NC points.
      There are contactors where you can add more auxiliary contact points on to it also.
      Additional contact points can be slide on to the contactor top and lock it.
      It should be done according to the manufacturer recommendations only.

    • @michaelisongekwere1402
      @michaelisongekwere1402 2 роки тому +1

      @@ElectroAcademyEA good please should I use stop push and start push buttons to manually switch off and on generator?

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      @@michaelisongekwere1402 Yes.
      Further, you can use a 2 pole breaker when wiring 12 volt power from the battery to this system.
      Breaker "ON" position is your generator automatic start/stop operating position.
      Similarly, breaker "OFF" position will act as generator manual start/stop position.
      In both these positions power transferring will be fully automatic, although you have to start the generator manually, in breaker "OFF" position.

  • @marcelogallelli5548
    @marcelogallelli5548 2 роки тому +1

    Que buen tutorial ... Lo malo es que no se hablar ingles 🤦‍♂️...

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      Gracias.
      Puede ver este video en español usando el siguiente enlace.
      ua-cam.com/video/rgtEnNUYTto/v-deo.html

  • @GAMINGYT-eg6xj
    @GAMINGYT-eg6xj 2 роки тому +1

    sir please make next video on latching relay plz.

  • @selimmahmud1616
    @selimmahmud1616 Рік тому +1

    all ok.
    When my grid off then 3 hours Later generator start.
    How to set the time

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      Hope you can get help from an electrician to correct this fault.
      Necessary timer settings are described in the video.

  • @sahanshrestha738
    @sahanshrestha738 2 роки тому +1

    Please explain how Manual and Auto mode is achieved in ATS

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому +1

      Introduce a two pole Isolator or a breaker and take battery wires to the auto start and stop connections through it.
      Isolator "ON" position will act as "AUTO" mode.
      Isolator "OFF" position will be the "MANUAL" position.
      When Isolator is at OFF position, you need to start the generator manually when grid power is not there.
      It will supply power to the contactor top and generator side control line breaker, allowing power to transfer automatically to the load.

    • @sahanshrestha738
      @sahanshrestha738 2 роки тому +1

      @@ElectroAcademyEA thanks for your prompt response

  • @GAMINGYT-eg6xj
    @GAMINGYT-eg6xj 2 роки тому +1

    make the video two pump controlled by latching relay plz

  • @Ayx12114
    @Ayx12114 9 місяців тому +2

    Sir can you provide schematic diagram for this system

  • @DS-it3xd
    @DS-it3xd 2 роки тому +1

    How to emergence stop button. Sir..

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      Emergency stop button should come with the generator itself.

  • @CR7FanBoyy
    @CR7FanBoyy Рік тому +1

    On the grid side you used two timer relays
    Can’t one timer relay do the job

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      Timer 1 is there to make generator to run on load for 2 to 3 minutes even after grid power is available.
      If grid power goes off again within this period, generator is on load and power supply will not be interupted.
      Although recommended, you can omit this timer if intermittent power disturbances are minimal.

  • @mackstone2912
    @mackstone2912 2 місяці тому +1

    Sir could you kindly forward me a copy of the schematic diagram for me. Thank you

  • @geraldrice3423
    @geraldrice3423 Рік тому +1

    Too difficult to follow . Need to slow down a bit !

  • @josebravo6642
    @josebravo6642 2 роки тому +1

    No entiendo el inglés.

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 роки тому

      Por favor, consulte el canal en el siguiente enlace.
      Más videos serán agregados aquí pronto.
      ua-cam.com/users/Academiaelectrónica

  • @OsmanyellaKargbo
    @OsmanyellaKargbo 9 місяців тому +1

    Any Whatsapp group pls I want to join

    • @ElectroAcademyEA
      @ElectroAcademyEA  2 місяці тому

      Sorry, We don't have a WhatsApp group at present.

  • @sersiobordios
    @sersiobordios Рік тому

    your sub-title covers the timer socket wiring configuration, it's bad video.

    • @ElectroAcademyEA
      @ElectroAcademyEA  Рік тому

      You can stop subtitles by clicking the "CC" icon on the screen.

  • @manojmule8624
    @manojmule8624 2 роки тому +1

    Thank you sir