Daikin VRV 6 / My First Time Connecting the Type 4 Checker to a Daikin VRV R

Поділитися
Вставка
  • Опубліковано 7 січ 2025

КОМЕНТАРІ • 29

  • @mark111943
    @mark111943 3 місяці тому +1

    As a customer I would want you warranty it otherwise it will cost me money in the future! Maybe when you add the other heads.
    Thanks for all your informative vids.

    • @hvacraustralia
      @hvacraustralia  3 місяці тому +1

      I flagged it with the office and a warranty call has been lodged with Daikin. I meant more what I could do about it in the mean time. It’s an odd decision by Daikin that’s for sure.

  • @Jim-yk9zw
    @Jim-yk9zw 3 місяці тому

    Did a compressor change out a few weeks ago on one of these systems. After charging back up with 40kg of gas found a leaking ball valve that we missed and had to recover all the refrigerant. So painful.

  • @alexandergorelov2515
    @alexandergorelov2515 3 місяці тому +1

    Thank a lot for video. Very interesting 👍

  • @michaelburns5680
    @michaelburns5680 3 місяці тому

    You can put it in charge mode (mode 20 and shut the liquid line service valve)
    and charge it down the liquid line straight from the bottle. So no chance of any liquid getting back and much faster if you’re chucking in a lot of charge.
    Also if you put it through test mode before chucking in the additional charge it may judge the line lengths wrong and get its target pressures wrong. Charge mode lets you fire it up before test mode too.

    • @hvacraustralia
      @hvacraustralia  3 місяці тому

      Thanks mate. I took a stab and thought 960g wouldn’t make much difference so I didn’t do another test mode. If I go back once the additional 3 head have been added I’ll put the system through another test mode then.

  • @JesseDoesHVAC
    @JesseDoesHVAC 3 місяці тому

    Condenser is very quiet im actually impressed (yes i know its technically not at 100%)
    Personally dont rate Daikin, fix/replace way more of them than i install 😂
    Fellow Melbournian hvacr tech 🤘

    • @hvacraustralia
      @hvacraustralia  3 місяці тому +1

      It was pretty quiet overall. I look forward to spending more time on them going forward. I get it 😂 my preference is Mitsubishi Electric.

    • @daniellonergan5669
      @daniellonergan5669 3 місяці тому

      I dont know what's happened to Daikin because 20 years ago when I started out they were elite, ow having nothing but issues with their inverter boards failing, I know they had a bad batch of capacitors on their smalling splits but lately I've diagnosed 10 inverter boards on vrv 4 loops that are less than 3 years old

    • @daniellonergan5669
      @daniellonergan5669 3 місяці тому +1

      Feels like they spent all their budget on designing the app than making the equipment better

  • @camerongleason2126
    @camerongleason2126 3 місяці тому +2

    Do you have a lot of sites with BS boxes mounted outside? I have never seen them outside being in Canada. As always great video!

    • @hvacraustralia
      @hvacraustralia  3 місяці тому

      This is the second one I’ve ever seen like this. Great of if I ever need to work on it.

    • @illillillillila
      @illillillillila 3 місяці тому +1

      BS Boxes should be treated as an indoor unit and should never be outside unless it's in a enclosed accessible space. I'm from Canada as well

    • @Jim-yk9zw
      @Jim-yk9zw 3 місяці тому

      You Canadians have to endure way colder winters where everything wants to freeze over which we just don't quite get in most of Australia, so that could be a significant reason why. Total exposure to the elements probably isn't ideal for the branch box though no matter where it is.

  •  3 місяці тому +2

    Any reason you charged system with vapour? I thought 410 was liquid only charge

    • @dongkaizhou9524
      @dongkaizhou9524 3 місяці тому +2

      the bottel is up side down so it still charge liquid

    •  3 місяці тому +1

      @@dongkaizhou9524 👍

    • @daniellonergan5669
      @daniellonergan5669 3 місяці тому +1

      Stub on vapour port is at the top of the bottle amd on liquid goes down to the bottom, hence turning upside on vapour will be liquid

    •  3 місяці тому +1

      @@daniellonergan5669 thanks, what about charging liquid into the suction line? Does that harm the compressor

    • @hvacraustralia
      @hvacraustralia  3 місяці тому +2

      I was charging slowly. There is a suction accumulator between the port and the compressor. I was also charging through a Schrader core. The chances any liquid makes it back are next to 0%.

  • @damowdotnet
    @damowdotnet 3 місяці тому +3

    “Not really sure what to do about that” - yeeuuup 😞

  • @NewDestinationEng
    @NewDestinationEng 2 місяці тому +1

    I guess all VRV6 are heat recovery actually
    That new service valve design is bad and will eventually leak. Why wouldn't they keep the traditional one with a cap?!

    • @hvacraustralia
      @hvacraustralia  2 місяці тому

      It’s an insane thing for Daikin to do 😂 good luck to them

  • @daniellonergan5669
    @daniellonergan5669 3 місяці тому

    Daikin come with little plastic caps that sit over the shut off valves......horrific idea 😂