Installing EG4 12v WP Lithium Batteries in Ryobi RM480e
Переглядів 3033 місяці тому
Parts List: Required 100 Amp continuous discharge - signaturesolar - G4 WP Lithium Battery | 12V 100AH Affiliate Link - signaturesolar.com/eg4-wp-lithium-battery-12v-100ah/?ref=M12gk_2DtiVacN * Required (Turnkey) - Amazon - GAEYAELE Delay on Time Relay Electronic 16A 1SPDT Adjustable Timer Delay Relay Din Rail Modular with CE CB Certificate (GRT8-A1,AC/DC12V-240V) * Required (Battery Safety) - ...
Max 0.9-1.1 C discharge test 90-110 amps), EG4 12v battery capacity test using Victron Smart Shunt
Переглядів 1895 місяців тому
1. waking a 12v battery after a current inrush fault with a 12v charger. 2. Testing the capacity of a 12 volt EG4 waterproof battery. 3. Realizing that I only have a 1C load. 4. Setting Victron shunt for Lithium test results 100 ah at a maximum discharge rate of 0.9 C and finishing with an overcurrent fault at 111 amps. I purchased 5 of these 12V batteries for a future project (maybe a Ryobi 48...
YouTube question. Will the 6000XP automatically restart after overload?
Переглядів 8065 місяців тому
Another UA-cam Question. Was Rodney's 6000XP overload comment correct about needing a manua restart accurate? ua-cam.com/video/YnSaHglBTPo/v-deo.htmlsi=Jttn8HupMxXUg1jZ&t=108 Sorry Rodney, but you got this one wrong The 6000XP will restart after a 5 minute delay if the system overloads. If your system is subject to overloads like Rodney's, you should wire in the grid. Affiliate links below (I'm...
Question, What is the noise at idle, 400 & 5,000 watt load. Answer 35-65 dB measured at 0-15 feet
Переглядів 6035 місяців тому
UA-cam Question. What is the noise level at idle, 400 watt load 20% and 70% fan speed. Answer 35-65 dB as measured at 0-15 feet Affiliate links below (I'm Brand new to this affiliate stuff) Using links below will (I hope) support my Solar Addiction. Signature Solar Site - signaturesolar.com/?ref=M12gk_2DtiVacN EG4 Communication HUB - signaturesolar.com/EG4-LiFePOWER4-Communications-Hub?ref=M12g...
Excited for this 6000XP firmware update. This update added Generator Boost/Assist
Переглядів 4,4 тис.5 місяців тому
Beyond excited for this update. Generator Boost allows you to use under sized 240v generators to charge and power loads without overloading the generator. Affiliate links below (I'm Brand new to this affiliate stuff) Using links below will (I hope) support my Solar Addiction. Signature Solar Site - signaturesolar.com/?ref=M12gk_2DtiVacN EG4 Communication HUB - signaturesolar.com/EG4-LiFePOWER4-...
EG4 6000XP, Explaining how the generator settings work.
Переглядів 4,3 тис.6 місяців тому
EG4 6000XP Generator Settings via Website and Inverter Screen Affiliate links below (I'm Brand new to this affiliate stuff) Using links below will (I hope) support my Solar Addiction. Signature Solar Site - signaturesolar.com/?ref=M12gk_2DtiVacN EG4 Communication HUB - signaturesolar.com/EG4-LiFePOWER4-Communications-Hub?ref=M12gk_2DtiVacN 18Kpv AIO - signaturesolar.com/eg4-18kpv-hybrid-inverte...
1977 VW Bus Westfalia Camper. 2023 Recap
Переглядів 3417 місяців тому
The Bus had a reliable year. Four car shows, one 400 mile round trip 3 day camping trip and lots of smiles. The Bus even participated in Halloween, the kids and adults loved it! Nothing new broke, except it still has a stripped out cylinder head temperature CHT sensor that likes to fall out. BTW the CHT is a vital component of the fuel injection system and it won't run long without it. Like awa...
EG4 Comm HUB + Solar Assistant + Closed Loop Comm w/18Kpv & 6000XP Inverters at the Sametime.
Переглядів 1,8 тис.7 місяців тому
Another DIYSOLAR Forum Question. "Can the EG4 Communication Hub coonect with Solar Assistant and simultaneously allow closed loop communication between the LIFEPOWER4 Batteries and Inverters?" Bonus: Hub also enables sharing closed loop data with multiple inverters. Affiliate links below (I'm Brand new to this affiliate stuff) Using links below will (I hope) support my Solar Addiction. Signatur...
DIY Solar Forum Question. Will the EG4 6000XP work from a single 120v generator or Grid connection?
Переглядів 6 тис.7 місяців тому
DIY Solar Forum Question. Will the EG4 6000XP work from a single 120v generator or Grid connection? Short Answer Nope. Affiliate links below (I'm Brand new to this affiliate stuff) Using links below will (I hope) support my Solar Addiction. Signature Solar Site - signaturesolar.com/?ref=M12gk_2DtiVacN EG4 Communication HUB - signaturesolar.com/EG4-LiFePOWER4-Communications-Hub?ref=M12gk_2DtiVac...
Winter Storage - Removed Lithium batteries from the RV.
Переглядів 597 місяців тому
Nothing major to see, just the annual RV House battery removal.
2 - EG4 6000XP Provide Grid Connection to 18Kpv. 6XP had no issue absorbing Surge/Dump. 24K Watts?
Переглядів 3,2 тис.7 місяців тому
2 - EG4 6000XP Provide Grid Connection to 18Kpv. 6XP had no issue absorbing Surge/Dump. 24K Watts?
Max Continuous on a single Leg with one 6000xp (30 Amp RV Load)
Переглядів 8397 місяців тому
Max Continuous on a single Leg with one 6000xp (30 Amp RV Load)
Warning ⚠️ Loud fan noise! EG4 Parallel 6000xp Overload demonstration with Grid bypass.
Переглядів 3,8 тис.8 місяців тому
Warning ⚠️ Loud fan noise! EG4 Parallel 6000xp Overload demonstration with Grid bypass.
6000xp Parallel Communication Cable routing and experimenting.
Переглядів 9558 місяців тому
6000xp Parallel Communication Cable routing and experimenting.
Learning how Charge from Grid setting(s) work, EG4 6000XP (Lead Battery)
Переглядів 3,2 тис.8 місяців тому
Learning how Charge from Grid setting(s) work, EG4 6000XP (Lead Battery)
EG4 6000XP wirebox modification
Переглядів 3,2 тис.8 місяців тому
EG4 6000XP wirebox modification
18Kpv User Question. Can you limit battery discharge when grid connected?
Переглядів 5328 місяців тому
18Kpv User Question. Can you limit battery discharge when grid connected?
How the EG4 18Kpv Quick Charge feature works.
Переглядів 2,2 тис.8 місяців тому
How the EG4 18Kpv Quick Charge feature works.
More sound testing (52-57 dB) at 50% Solar 60% Load and MPPT 460 VoC
Переглядів 1,8 тис.8 місяців тому
More sound testing (52-57 dB) at 50% Solar 60% Load and MPPT 460 VoC
Two EG4 6000XP (Parallel) 1st test. Fan speed adjustment.
Переглядів 6 тис.8 місяців тому
Two EG4 6000XP (Parallel) 1st test. Fan speed adjustment.
EG4 6000XP, 15 Minutes of max load, single leg overload, fan settings, and rambling about 18Kpv
Переглядів 4,5 тис.8 місяців тому
EG4 6000XP, 15 Minutes of max load, single leg overload, fan settings, and rambling about 18Kpv
Using a Pencil as a precharge resistor.
Переглядів 3578 місяців тому
Using a Pencil as a precharge resistor.
EG4 6000XP Idle Load - NO Solar/Grid
Переглядів 2,2 тис.8 місяців тому
EG4 6000XP Idle Load - NO Solar/Grid
Quick 30-second overview - Fixing my mistake - EG4 Chargeverter
Переглядів 2769 місяців тому
Quick 30-second overview - Fixing my mistake - EG4 Chargeverter
Setting up my virtual desktop. Quest 3, TIGO, Solar Assistant and DIYSolar
Переглядів 2229 місяців тому
Setting up my virtual desktop. Quest 3, TIGO, Solar Assistant and DIYSolar
Why I like using the EG4 Lifepower4 Communication Hub with my 18kPV
Переглядів 1,7 тис.11 місяців тому
Why I like using the EG4 Lifepower4 Communication Hub with my 18kPV
EG4 LiFepower4 Comm Hub Firmware Update (Optional) **Do Not update unless directed by SS/EG4**
Переглядів 1 тис.11 місяців тому
EG4 LiFepower4 Comm Hub Firmware Update (Optional) Do Not update unless directed by SS/EG4
EG4 LiFePower4 Battery Rack 2022 vs 2023
Переглядів 7 тис.11 місяців тому
EG4 LiFePower4 Battery Rack 2022 vs 2023
Modifying EG4 Lifepower4 Battery (USB) Communication Cable. Going from Pin 78 to Pin 12
Переглядів 1,5 тис.Рік тому
Modifying EG4 Lifepower4 Battery (USB) Communication Cable. Going from Pin 78 to Pin 12

КОМЕНТАРІ

  • @houstonstarbuck
    @houstonstarbuck 13 годин тому

    Will this only work if you are off grid? I'm trying to figure out if this can work when the grid is connected and it would seem like the answer is no. Still would be a great solution for me here in Houston when the grid goes down. In that event, if I follow the video...I could hook up my 15,000 watt generator...set the 18k to say...pull 12,000 watts...and then when my load exceeds 12,000 it would pull from PV and batteries. Am I thinking about this the right way?

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 12 годин тому

      Yes that's how it normally works.

    • @houstonstarbuck
      @houstonstarbuck 9 годин тому

      @@theadventuresofarenaissancman the reason I ask is that an eg4 tech in one of the forums says the total AC output remains the same for either unit...just changes the mix...i.e. from a generator. i was hoping it would increase the capacity on the AC bus side so I can pull larger loads (in a grid down situation where normally the grid bypass would be the way to handle larger loads).

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 9 годин тому

      I haven't tested a scenario like that.

  • @electronicwizardsolartech
    @electronicwizardsolartech 2 дні тому

    Hi, have you connect the 6000Xp to a single phase 240 volts ?

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 дні тому

      Yes but that was 6 - 8 months ago. I haven't tried recently.

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 дні тому

      If my memory is accurate the XP checks for voltage at L1 to N, L2 to N and L1 to L2 and will disconnect from grid if either voltage is out of range.

  • @johnkese8953
    @johnkese8953 8 днів тому

    Thank for the video! BUT, it is hard for me, a first time owner of a 6000EP, to FOLLOW what you are doing and what is happening on the screen. It would be very helpful if you explained what was on the screen and what you are doing when you keep pressing the buttons and the screen keeps changing, without any explanation as to why and what the items are that appear, especially at the top of the screen that you gloss over. Appreciate the video and gave “thumbs up” for doing it…..BUT, I’m more confused than when I started.😂

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 8 днів тому

      Thank you for the feedback. I think the generator settings have changed since this video was released.

  • @tjmooney4181
    @tjmooney4181 19 днів тому

    Seems like these should be preset at 90% start 95% stop 🤔

  • @tjmooney4181
    @tjmooney4181 20 днів тому

    Awesome thanks for the update, I swapped my 2 6000xps for the 18kpv today and charged my tesla on 40 amps for 3 hours as it's break in test lol

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 20 днів тому

      I normally charge my car between 20-40 amps. 20 if I'm running other loads and 48 if I need to drain the batteries to make room for solar.

  • @jolee6751
    @jolee6751 21 день тому

    Can you look at my JD LX 176 Please, it was never maintained But I mowed yesterday

  • @paulbuckley7607
    @paulbuckley7607 21 день тому

    I appreciate the videos you are posting. Just tried to do this on my inverters have two eg4-18KPVs have a grid connected and lowered them both down to to 10 amps but I did not see anything being pulled from the grid side? Is there another setting I need to use? Thank you

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 21 день тому

      Do you have "off grid" enabled?

    • @paulbuckley7607
      @paulbuckley7607 21 день тому

      Good morning, Yes off grid is enabled. I do not have an agreement with my utility company to back-feed the grid? If I disable that will I back-feed the grid?

  • @michaelambrosia
    @michaelambrosia 25 днів тому

    Thanks for sharing. I wish they would put this on their website or in the manual, because I just found out the same thing after spending a lot of money on this stuff. Next i'm thinking about using a transformer... Have you went down that route?

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 25 днів тому

      No, but I heard someone used a 3000 watt 120 to 240 transformer from Amazon.

    • @michaelambrosia
      @michaelambrosia 11 днів тому

      ​@@theadventuresofarenaissancman trying the transformer and no response. Apparently, it needs to receive split phase. Trying to figure this out after signsture solar tech lacked the knowledge to help with a solution.

  • @koskos758
    @koskos758 Місяць тому

    Garbage video. Good idea - bad implementation. Jumping over menus like a monkey.

  • @ShaneS071
    @ShaneS071 Місяць тому

    what are you using for a fan exhaust deflector ?

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman Місяць тому

      Just a heat/AC vent deflector. You can buy on Amazon or BigBox store.

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman Місяць тому

      Not the exact one but the same concept. Eureka Air Adjustable Deflector... www.amazon.com/dp/B08QH49RWB?ref=ppx_pop_mob_ap_share

  • @mosfet500
    @mosfet500 Місяць тому

    I lost communication when I updated the battery firmware. I just switched the baud rate from 9600 to 19200 and now my communication is good. I'm not using their inverter so I'm not worried about the boot failure. I'll leave it at 19200.

  • @jamesk5600
    @jamesk5600 Місяць тому

    There seem to be quite a few LiFePo4 battery conversions on youtube that do not include a pre-charge circuit and are reported to work fine. I'm currently sourcing batteries for my conversion and I don't want to make extra work for myself if not necessary. I'm curious if you added the pre-charge circuit because you were experiencing trouble with BMS tripping, or you simply thought it would be a good idea? Pre-charge resistors are common for inverters, but I have to wonder if the inverters might have larger capacitors leading to higher inrush currents. If nothing else, the pre-charge circuit might extend the life of the main contactor, although many contactors have a separate hardened contact intended to deal with arcing when opening or closing the contactor.

  • @vdawger
    @vdawger Місяць тому

    thank you for this video.

  • @FredDavey-gt7py
    @FredDavey-gt7py Місяць тому

    May I suggest a large C-Clamp….

  • @costachristoo
    @costachristoo Місяць тому

    thanks for the video, i have a question , is this bar gets old ? and what is the felling changing it , left -right stability or suspention ? thank you again

  • @costachristoo
    @costachristoo Місяць тому

    I own an T2 ab , there was a squik squik in the front system , i thought it was greese, or absorvers, , i got unter the car and i realise that the steering absorver is missing, Or stolen , or the mechanic forgot it somewhere on the proses, anyway thanks , this little video helped two T2 (me and a friend) to change the absorver, they were asking 100 euros for this, but couse of you we only paid for the part (45 euros) The squick did not go away, but anyway probably thats the rea son i got the problem in the first place , anyway thank you again from Athens

  • @AdamDeLay07
    @AdamDeLay07 Місяць тому

    Glad to hear things are still running smoothly for you! I'm still shocked when I look at my usage numbers and think..."wow we produced (and used) that much power!"...crazy!

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 дні тому

      In general, I just wish the conversion rates were higher and lower idle consumption. Someday the technology will get us to 99% in all conversations.

    • @AdamDeLay07
      @AdamDeLay07 2 дні тому

      @@theadventuresofarenaissancman oh yeah, I completely agree! I’m sure we’ll get there at some point.

  • @DaRoach5882
    @DaRoach5882 Місяць тому

    Hey, I know this is from 5 months ago but I was able to get 120v charging to work with mine I don't know if it was a firmware change or not but its working now. Connection I used was Hot on line 2 and Neutral on Line 2. and I was able to charge. Note that the output while on the grid was not correct as it was only 60 volts from line to neutral. The other thing that I noticed was that I needed around 650 watts or more of charging to get it to work

    • @michaelambrosia
      @michaelambrosia 25 днів тому

      Hot online 2 of grid?? And neutral online 2 of generator? I'm currently trying to figure this problem out as well

    • @michaelambrosia
      @michaelambrosia 11 днів тому

      trying the transformer and no response. Apparently, it needs to receive split phase. Trying to figure this out after signsture solar tech lacked the knowledge to help with a solution.

    • @michaelambrosia
      @michaelambrosia 2 дні тому

      Transformer did not work because this inverter requires split phase.

  • @sreimert
    @sreimert Місяць тому

    I think this would work if you wired it like this: The generator's 120V output (hot wire) would be connected to both the L1 and L2 input terminals on the EG4 6000XP. The generator's neutral wire would be connected to the inverter/charger's neutral input terminal. The generator's ground wire would be connected to the inverter/charger's ground input terminal.

  • @somedudeandacomp
    @somedudeandacomp 2 місяці тому

    Wow, thanks you got me unstuck, i updated my batteries before setting up the hub you and you really helped me out. Changing baud rate to 19200 worked great

  • @jasperthomas8048
    @jasperthomas8048 2 місяці тому

    When the inverters bypass to grid, how many watts/amps will the 6000XP's in parallel bypass. Is it a total of 50 amps per unit? If it goes over that does it disconnect from the load completely, or is that the breaker size that limits the output?

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 місяці тому

      Grid input Breaker size needs to be the limiting factor. My personal opinion. 40 amps pass through plus 10 amps reserved for DC battery charging is safe. Total grid input breaker can be up to 50 amps for each inverter. The manual says 50 amps pass-through. So two 6000XPs could provide 100 amps of pass through.

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 місяці тому

      I tested a single 6000xp up to 60 amps. 12,000 watts pass-through and the AC battery charging was automatically throttled by the inverter when the pass-through load exceeded 40 or 50 amps.

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 місяці тому

      The internal breakers of the 6000xp are rated for 62 or 63 amps. 80% of 62 is 49.6 amps. Breakers are only designed to support 80% for continuous loads.

  • @tjmooney4181
    @tjmooney4181 2 місяці тому

    Is there a setting for making sure the generator only charges the batteries when my battery soc is low and i manually start it? I am using 1 6000xp, 1 powerpro battery and honda 6500 generator for reference 🤔

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman Місяць тому

      No, I don't think so. I'll take a look later today.

    • @tjmooney4181
      @tjmooney4181 Місяць тому

      The client I installed a 240v honda 6500 generator to the gen input of the inverter called today saying his powerpro wallmount hit 20% so he started the generator but when his generator would idle down every once in a while the TV would turn off? Still confused over what could cause this 🤔

  • @tjmooney4181
    @tjmooney4181 2 місяці тому

    Can i wire a honda 6500 240v generator into the generator input of the 6000xp to avoid using a chargeverter?

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 місяці тому

      Sure, one question does the Honda have that weird setting where it can parallel the two outputs in to a single 120v?

    • @tjmooney4181
      @tjmooney4181 2 місяці тому

      @theadventuresofarenaissancman nope just a 14-30 4 prong twist lock I planned to cut one end off the extension cord and wire into the gen input but couldn't figure out if it would work correctly if I just turned it on and off when I choose instead of hooking up the auto start dry contacts

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 місяці тому

      @@tjmooney4181 sounds like it should work. I don't remember if the 6000xp will default to charging batteries with the newest firmware. You may need to adjust the XP generator settings so it will always charge when the generator is running. But that's easy.

    • @tjmooney4181
      @tjmooney4181 2 місяці тому

      @theadventuresofarenaissancman thanks so much for the quick responses I planned to follow your other video about generator settings to set at 5000 watts for this generator. I am using 1 6000xp and 1 powerpro for this project

    • @michaelambrosia
      @michaelambrosia 11 днів тому

      trying the trandformer and no response. Apparently, it needs to receive split phase. Trying to figure this out after signsture solar tech lacked the knowledge to help with a solution.

  • @tjmooney4181
    @tjmooney4181 2 місяці тому

    Thank you so much for posting these videos, I'm connecting a honda 6500 to a clients tomorrow 🙌

  • @dr.projectx5142
    @dr.projectx5142 2 місяці тому

    great video. These are nice set up, pairing these up with lev60 cell bank would be great 55 kwhr energy storage and charge at supper off peak at .03 a kwhr would be a steal, plus when selling for .08 back making .05 kwhr of power purchased. .08 sell back and .03 buy back from 11 pm to 5 am is a killer deal. Thanks for the video for showing us how to navigate through the menu.

  • @stifflerjj4
    @stifflerjj4 2 місяці тому

    I purchased the 46500 brand new in the box still signature solar is willing to give you $1,200 bucks back to switch over to the 6000 the issue I have is it will my Westinghouse 4500 watt inverter generator that is only single phase but 30 amp will that generator work on the 6000 XP for at minimum to charge the battery Bank I seen one of your comments said you'd use a small generator as well I was just wondering if you can use a 120 single phase inverter generator and maybe make a jumper wire to provide 110 to both legs enough to charge the batteries or there's a switch to switch the generator input to 120

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 місяці тому

      No, you can use the ChargeVerter.

    • @stifflerjj4
      @stifflerjj4 2 місяці тому

      @@theadventuresofarenaissancman I was trying to avoid using another source to charge battery Bank backup kind of defeats the purpose of an all-in-one if I have to segregate all my stuff would you recommend me updating to the 6000 or do you think the 6500 the better candidate

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 місяці тому

      6500ex can work with 120v. 6000xp needs 240v split phase

    • @stifflerjj4
      @stifflerjj4 2 місяці тому

      @@theadventuresofarenaissancman so the next question would be if using a charge inverter to charge the battery is back up with my 110 generator am I still able to utilize the dry contact Jenny start stop feature built into the XP and maybe a changing the setting so that once it reads the battery level at a certain level it opens the circuit back up just send the signal to turn off the generator and back on based on battery level

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 2 місяці тому

      You can but I don't believe that your generator supports a two wire start.

  • @Espiritiv
    @Espiritiv 2 місяці тому

    Damn so you cant make a portable generator cart with the 6000XP like you can with the 3k and just charge it with 120V 20A plug? I was hoping i could so some slow charging on my wall outlet and then have 240V available for running some loads in a pinch. Sounds like i am going to have to pick up the 3K instead

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 25 днів тому

      That sure would be nice. Someone mentioned using 2,000 or 3,000 watt 120/240 transformer and setting AC charge at a lower amperage

  • @AndersVestlund
    @AndersVestlund 3 місяці тому

    Thank you!! Been struggling with my 73 that I can’t fill up with fuel completely because of this. Never knew there was a piece of hose there, thanks!!

  • @Darren-C
    @Darren-C 3 місяці тому

    Hey boss. These are just the calculations I needed. Thanks for the explanation! I’m building a larger electrical mobile unit out of an enclosed trailer I’ve converted to be powered by the 6000xp with 10.2kwh server no alternator charge tied. My biggest question is grounding the system in a mobile application with no grid tie. Is grounding to the frame fine because of wood blocks and rubber tires. Or do I need to tie the ground to a rod at every location. I’m worried times I’ll be around pavement only. Thanks again boss!!

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      Grounding will change if you plug in to shore power.

    • @Darren-C
      @Darren-C 3 місяці тому

      @@theadventuresofarenaissancman Yes sir. I understand it will be grounded when connected to the grid. Just didn’t know when off grid, if grounding to the frame would be suffice

  • @christophersmolinski6194
    @christophersmolinski6194 3 місяці тому

    Did you try a jumper between L1 and L2? Some units simply need to see 120v OR, does it need to truly be a split phase 240v?

  • @jtmg11
    @jtmg11 3 місяці тому

    Is it possible in any way to simultaneously use grid and battery with a single or parallel 6000xp?

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      6000xp is not approved as a grid interactive inverter.

    • @jtmg11
      @jtmg11 3 місяці тому

      Looks like this will be the dealbreaker of choosing two of these paralleled versus a single 18k. I need 24/7 grid as a source potential only without any selling back at all.

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      @jtmg11 blending of grid and Battery at the same time...no. but when the battery SOC drops below your predetermined %. The inverter with switch over to grid. Your original question implied that you want Battery and Grid blended at the same time.

    • @jtmg11
      @jtmg11 3 місяці тому

      @@theadventuresofarenaissancman sorry for any confusion. Blending capability was my question exactly. I could still make it work, but I would be concerned about switching too often, causing excessive wear on the inverter (may be miss placed fear)

  • @AdamDeLay07
    @AdamDeLay07 3 місяці тому

    Nice little project!

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      It sure is! Waited years for this. Hindsight, don't buy the batteries 8 months before finding the mower.

    • @AdamDeLay07
      @AdamDeLay07 3 місяці тому

      @@theadventuresofarenaissancman 🤣🤣 How's the mower working overall? What's your runtime like?

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      @AdamDeLay07 run time, I'm estimating 4 hours. Average amp draw is 20-25.

    • @AdamDeLay07
      @AdamDeLay07 3 місяці тому

      @@theadventuresofarenaissancman Not too bad, thanks!

  • @sia3540
    @sia3540 3 місяці тому

    Does the general have to be an inverter generator

  • @watchman1982
    @watchman1982 3 місяці тому

    I assume your two 6000XP’s are wired in split phase? If so, is only one dedicated to Grid, Gen, Battery and PV input?

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      The inverters provide split phase. They are wire in parallel. Inv1 L1 and Inv2 L1 share the same subpannel bus. Inv1 and Inv2 L2 share the same bus.

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      They have to share the same generator and Grid. Solar PV will function independently.

  • @DONL11233
    @DONL11233 3 місяці тому

    I just got my second server rack of 6. Any input on the best way to wire them together? I’m new at this. Thanks

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      Originally I had mine wired independently, but I noticed that my new rack was lagging. Last month I switched to a single run positive top left side stack and Neg Top right side rack. Connected the two racks Busbars at the bottom.

  • @varman001
    @varman001 3 місяці тому

    Dude wire the neutral(white) to the neutral bus bar NOT to L2, it will work! also it will work if you get an extensions from each leg(that would be 2 extension cords) and connect them together, you will see 240v.

  • @chicagoterence
    @chicagoterence 3 місяці тому

    Well, this is wired wrong. If you wire correctly it will show 120V... however still does not charge... and yeah, signature solar assured me it would. Needs to be true 240 split phase too btw.

    • @michaelambrosia
      @michaelambrosia 25 днів тому

      I'm wondering if it would work with a transformer running two forty single phase?

  • @roysylvester5723
    @roysylvester5723 3 місяці тому

    hey renaissance man im learning alot from u but question... can i not have grid connection and generator connection at the same time,because when i do i cant get 6000xp to pull from generator... any thoughts....

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      You would need to turn off the grid breaker for Generator to work.

    • @roysylvester5723
      @roysylvester5723 3 місяці тому

      @@theadventuresofarenaissancman yup i got it figured out.. thanks man

    • @roysylvester5723
      @roysylvester5723 3 місяці тому

      well i thought i had it... flipped ac in breaker off, flipped gen in breaker on and it clicked clicked clicked several times and something popped inside and it shut down... not sure what happened but it is still working right now... kind of afraid to try it again....

    • @roysylvester5723
      @roysylvester5723 3 місяці тому

      not sure what i did wrong... i wired up a floating neutral inverter generator to it but i only wired 2 hots and the ground... what u think happened...

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      That doesn't sound good

  • @jasonweb9720
    @jasonweb9720 4 місяці тому

    I cant get my generator a 5.5 kw generac to connect to the inverter. Just show the voltage and hz on the screen of the inverter and clicks on once every five mins for 4 seconds. The 18k just does not like it. Gen has a floating neutral and floating neutral wired on the inverter and bonded neutral in the main power panel. Cycles hz and voltage is in spec. Perimeters are set wide enough for the cycles and volt fluctuation. My head is going crazy on this.

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      Bummer, is your generator a true 240v? Or one of those generators that has a switch that goes from 120 to 240?

    • @jasonweb9720
      @jasonweb9720 3 місяці тому

      @@theadventuresofarenaissancman true 240v. Generac 55 quiet pack

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 3 місяці тому

      Do you have the newest firmware installed on your 60000xp?

    • @jasonweb9720
      @jasonweb9720 3 місяці тому

      @@theadventuresofarenaissancman yes

  • @killerdeamonking
    @killerdeamonking 4 місяці тому

    What did you do with the other gauges?

  • @damondeane11
    @damondeane11 4 місяці тому

    I sure hope there is something insulating between those two pcbs

  • @xWildz
    @xWildz 4 місяці тому

    RIP screen, I like to leave the plastic on it make a good screen protector

  • @Valor4Christ
    @Valor4Christ 4 місяці тому

    How do i set it up to As long as there is sun and battery, i dont want to use gird, But inwant the gird to kick automatically when those dont exist. How doni set it up to do that. Right now if i have the gird breaker on, it is charging the. Battery from the gird, and powering my load from the gird. Help

  • @Valor4Christ
    @Valor4Christ 4 місяці тому

    First video i saw going through the settings on the screen

  • @Fawkes-ent
    @Fawkes-ent 4 місяці тому

    Probably would have been a little bit safer if you turned it off or done it before installation 😂

  • @Moes_Prep_and_Tech
    @Moes_Prep_and_Tech 4 місяці тому

    Those fans are loud. Before this video I was seriously contemplating on getting one installed in the bedroom closet

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 4 місяці тому

      That room is only 5 feet by 7 feet.

    • @johndoe-oi7bq
      @johndoe-oi7bq Місяць тому

      You could probably install some Noctua computer fans if they're compatible. Cheap fans are loud. You shouldn't need a lot of cooling capacity being in a climate controlled house, just make sure you have enough clearance if the closet is small.

  • @user-om4oy6rh5w
    @user-om4oy6rh5w 4 місяці тому

    What's a communication hub

  • @user-om4oy6rh5w
    @user-om4oy6rh5w 4 місяці тому

    What's a communication hub

    • @theadventuresofarenaissancman
      @theadventuresofarenaissancman 4 місяці тому

      It's a device that enables communication between Lifepower4 batteries and EG4 inverters. Specifically it was vital prior to EG4 updating the battery firmware. It also makes communication between the batteries and 3rd party inverters.

  • @danb2160
    @danb2160 4 місяці тому

    Thanks for the video. So the eg4 hub is allowing you to use both it And SA to monitor the batteries? Would you be able to run it the same way with out the eg4 hub?

  • @solarcharging9743
    @solarcharging9743 4 місяці тому

    Better hope you don't have cold solder joint or any micro fractures that can lead to hot spots in your solar module cells that will cause arcing and roof fires running at such a high OC DC voltage. I've seen the results of plenty of module fires over the past 25 years.