Electrical Designing of High Rise Building G+10 | Electrical Design Course

Поділитися
Вставка
  • Опубліковано 8 вер 2024
  • Hey guys! Welcome back to the new video of electrical infinity.
    In this video, I attempt to explain the electrical design of high rise building G plus 10
    It consists of 5 steps
    1. Calculation of total connected load
    2. Transformer sizing
    3. Circuit breaker selection for transformer
    4. Circuit breaker selection for main meter panel and flat load
    5. Drawing of Single Line Diagram
    Thanks For Watching
    Electrical Infinity
    Like and Subscribe!

КОМЕНТАРІ • 146

  • @prasenjit_hazra
    @prasenjit_hazra 2 роки тому +6

    A Big Thanks for your magnificent job of teaching us from scrach. It often helpful to make some quality negotiation with consultant & infra individual as a "Sales Specialist".

  • @abdulkhadeer2351
    @abdulkhadeer2351 16 днів тому

    Thanks a lot for making a video of full knowledge, easy explaination, simple method.. it helps us a lot to perform best in company and to face the interviews.
    Tons of thanks to you❤

  • @user-yz5bw4dm2d
    @user-yz5bw4dm2d 10 місяців тому +2

    A very rare video on electrical design. Thank you so much for the clarity in explaining.

    • @ElectricalInfinity
      @ElectricalInfinity  10 місяців тому

      You are welcome. Make sure you subscribe and share it with your friend's and colleagues.
      Thanks ❤️

  • @abdiit5129
    @abdiit5129 3 роки тому +5

    Great, thank you! Can we consider socket outlet power consumtion as a common connected load? And also please share us electrical design for residential house G+3 with all connected load like kitchen, lighting, washing machine, Iron, sockets, water pumps, oven , etc. Thanks bro.

  • @salahuddinbangash4785
    @salahuddinbangash4785 Рік тому +3

    Damn Nice bro, I thought it will be difficult but this is just basic electrical engineering 🔥🔥

    • @ElectricalInfinity
      @ElectricalInfinity  Рік тому +2

      Yeah much easier than engineering theories. But on Job it is a challenge to deal with complexity of projects. This was just a basic sample to make it easier for audience to understand.

  • @mdshadaabalam2612
    @mdshadaabalam2612 3 роки тому +2

    Awesome explained.....sir kindly make video on cable sizing, voltage drop, ssc, bus bar sizing, earthing and lighting arrester calculation for the same project.

  • @therealitypresenters8616
    @therealitypresenters8616 3 місяці тому

    Great, haven't found any video on any platform like this. Glad if add cable sizing calculation grounding and lightning protection system.

  • @yatinthakuryt3362
    @yatinthakuryt3362 4 місяці тому

    Thank you very much for giving such great information.

  • @salunkhesandeep
    @salunkhesandeep Рік тому

    Very well explained... Thanks so much for sharing knowledge....

  • @sultanurrahman799
    @sultanurrahman799 Рік тому

    It's helpful for technical support

  • @mobilesandcomputers5931
    @mobilesandcomputers5931 2 роки тому +2

    I am working as a deputy messenger in a good housing society in Pakistan. I have seen your video on youtube. It is important to learn building. Tell me some main points

  • @smnmj3320
    @smnmj3320 3 місяці тому

    Thanks brother..it's a very helpful video.❤

  • @saleembasha7924
    @saleembasha7924 6 місяців тому

    Thank you for the detailed video bro.,👌👌👌👍👍👍

  • @rajeevneela2861
    @rajeevneela2861 9 місяців тому

    Thank you... good knowledge given

  • @rashidchibvuri2036
    @rashidchibvuri2036 7 місяців тому

    Thank you so much sir

  • @sefatullah441
    @sefatullah441 3 роки тому

    manny many thanks sir g....outstanding video.......please continue thils topic electrical designing. upload more videos related to electrical building design..l...cable selection farmula etc.etc please

  • @gkd5421
    @gkd5421 2 роки тому

    Sir, all your vedios are very informative..I seen all your channel... waiting for next latest vedios... thank you very much...

  • @saalimbaig4896
    @saalimbaig4896 Рік тому

    Very useful information

  • @incredibleindia3572
    @incredibleindia3572 Рік тому

    Wonderful Explanation ❤

  • @emr207
    @emr207 8 місяців тому

    🎉super

  • @sagarvv4699
    @sagarvv4699 3 роки тому +2

    Thank you so much for this. Could you please if you have time just explain the above 40-floors building details as per Indian standard.

  • @_InzimamImtiazuddin
    @_InzimamImtiazuddin 4 місяці тому

    Thank you very much for this informative video. I had one question. 2BHK flats are provided with single phase supply. So when determining C.B size, for converting Watts to Amps, we should be multiplying with 8 and not 1.9 right? (Based on your G+5 electrical design video)

  • @Saichanti77
    @Saichanti77 11 місяців тому

    Thanks ❤

  • @yograjsingh3604
    @yograjsingh3604 5 місяців тому

    wow very helpfull

  • @rahulgaikwad8430
    @rahulgaikwad8430 Рік тому

    very good Explanation

  • @koala4599
    @koala4599 Рік тому +1

    first of all thank you for the great video, But please can you explain how you decide to use 7.5 kw for 3BHK ?

  • @shahbaazalam1003
    @shahbaazalam1003 3 роки тому +2

    Can you please make a video on calculation of lightning arrestor and calculation of earthing rod, pits and wire?

  • @etelanarendra9873
    @etelanarendra9873 10 місяців тому

    Excellent

  • @PraveenKumar-rh9bv
    @PraveenKumar-rh9bv 5 місяців тому

    Awesome very useful

  • @imrankhan-uf7ww
    @imrankhan-uf7ww 3 роки тому

    great work sir ❤️❤️❤️❤️

  • @Bandarofficial
    @Bandarofficial Рік тому

    Thanks you so much.

  • @9852626796
    @9852626796 Рік тому +1

    Just now I seen your video it's outstanding.
    Can I get this elaborated topic in pdf format please.

  • @engmohamedmuraase5119
    @engmohamedmuraase5119 2 роки тому

    thanks sir for your kind to explain us more I would like to ask you PART-4 for the C.B sizing for main meter panel and flats.at PANEL-1 How you got common load result in 60kw? thanks sir.

  • @dineshmehta3688
    @dineshmehta3688 Рік тому

    V good

  • @spritor6463
    @spritor6463 3 роки тому

    Good to see you upload regularly again :)

  • @davendertaneja3489
    @davendertaneja3489 3 роки тому

    Nice 👍

  • @franchettecariaga
    @franchettecariaga Рік тому

    Hello! I just saw your channel and I am so thrilled. J would just like to ask.. Is this as per australian standard?

    • @ElectricalInfinity
      @ElectricalInfinity  Рік тому

      Hi Franchette 👋,
      Thanks for watching. Yes, the design is as per Australian standards.

  • @sefatullah441
    @sefatullah441 2 роки тому

    waiting for your next video.. please upload soon

  • @roofi881
    @roofi881 2 роки тому +2

    HI Dear,
    I wanted to know that why did you assume DF as 70% while for the commercial buildings you mentioned earlier standar DF is 80-90% in India.
    please explain this point, Thanks

  • @md.gufranansari9672
    @md.gufranansari9672 3 роки тому

    Please make a video overall design parts such as cable calculation, voltage drop, short circuit, power factor.

  • @altamashsayed5264
    @altamashsayed5264 Рік тому

    I have a doubt related cb sizizing
    For 1500kva transformer Secondary side.
    Once we convert kva to amp
    1500kva*1.4 =2100A
    Should be consider 1.5 safety factor or directly select breaker from 2100A

  • @mithunmathew7965
    @mithunmathew7965 2 роки тому

    Sir, We need to consider hvac load
    for public area and corridor's,
    Firepump

  • @kobe8502
    @kobe8502 3 місяці тому

    At 11:00 how did you get those MCCB values? Why is it almost doubled when you already multiplied them by 2?

  • @sandeshdhungana2749
    @sandeshdhungana2749 2 роки тому

    Great video, thank you!! Would you make video on cable sizing considering voltage drop for high rise building.

  • @ZubairAhmed-uc7tb
    @ZubairAhmed-uc7tb 11 місяців тому

    Thanks for the Video, Can your please explain how the Multipier Value (KW - A =x1.9 ) Comes. Where as I =P/(VxPF) for Single phase and I = P/(1.732xVXPF). Kindly Correct me if I am Doing any mistake understanding Data manipulation. Warm Regards

  • @shahbaazalam1003
    @shahbaazalam1003 3 роки тому

    Can you make a video on the cable size selection from transformer to transformer's CB and from tx's CB to load' CB?

  • @sabinaktar5135
    @sabinaktar5135 Рік тому

    fab❤

  • @arunkumarthakur9679
    @arunkumarthakur9679 2 роки тому

    B+P+33 including club, stp, water supply, fire system. Provide electrical load calculation.

  • @Belive_trust_wait
    @Belive_trust_wait Місяць тому

    Sir give a link for , workout screen calculation...give a new video also sir

  • @everythingforyouonly5694
    @everythingforyouonly5694 3 роки тому +1

    Why you take 2 time demand factor
    1) for TCL and
    2) for metering panel c.b selection

  • @kv848
    @kv848 3 роки тому

    Great brother..Suppose you have 2 transfer pumps,1 is standby and other is on duty, means they will work interchangeable and both will not ON at Sam time and they are in same panel MCC,..So how will you calculate main cable to this panel, will you consider kW of both motor or only 1 ?

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому

      Total of both.

    • @kv848
      @kv848 3 роки тому

      @@ElectricalInfinity but at any instant, both will not work together, then why we consider both load ? Is it general rule to consider both ?

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому

      That's why we take 0.7 demand factor after calculating total load.

  • @Premkumark90
    @Premkumark90 2 роки тому

    Hello,
    Can I convert kw to amps by .
    First kw to kva
    Then kva to amps.
    If do like this different values coming ,what should I do?

  • @AkashSingh-jz4zo
    @AkashSingh-jz4zo 2 роки тому

    In the video, df for residential is mentioned as 0.6, but you considered 0.75, why the difference? And what are the actual standards?

  • @swapnilshiyaniya5306
    @swapnilshiyaniya5306 Рік тому

    Time 11:04 When you are calculating MCB for 2BHK load, you multiplied 5kw by 1.9 ... but wo to 3 phase ke liye aayega na ... for 1 Phase 5.43 Amp aayega na as 5 kw load is Single Phase load. Please correct me if i am wrong.

  • @seng7333
    @seng7333 Рік тому

    Nice explanation
    But
    The breaker size of 40A for 5kw load seems to be high
    Also 50A breaker is not standard size

  • @habibullah7853
    @habibullah7853 7 місяців тому

    This is very informative.
    I am here in UAE as a fresh electrical engineer and looking for job. Can anybody help me getting a job.
    Thank You

  • @Concepttalks98
    @Concepttalks98 2 роки тому

    Brother you didn't count future expansion of 20-30% why?
    Also you considered only demand factor but not diversity factor ..
    And i designed further and calculated and i got secondary current more than 1200A ...so should I take 3 runs of 1core 300sq mm cable or 3 run of 3 core 300sqmm cable.?

  • @eaknadhwilson5931
    @eaknadhwilson5931 Рік тому

    Bro it's better to share the image of those calculations thanks 👍🏻 very useful

  • @mujeebrehman7097
    @mujeebrehman7097 Рік тому

    How you find the value of 1.4 when you convert kva to amp ?

  • @sachinlandge6401
    @sachinlandge6401 Рік тому

    How to calculate electrical meter room and duct size

  • @kalingahistory
    @kalingahistory Рік тому

    But the loads you clubbed together are single-phase loads. Where as the main power supply will in three phases.

  • @KhanContent
    @KhanContent 2 дні тому

    Time 06:17 where this 1.4, 1.9 and 1.5 came from ?

  • @kobe8502
    @kobe8502 3 місяці тому

    It would be great to explain this slowly. Kind of confusing and some details were not explained properly. Why did you use 400A in 9:52?

  • @demonkiller2358
    @demonkiller2358 3 роки тому

    Can u make video on Important is and nec standards

  • @copycatonlyoriginal6585
    @copycatonlyoriginal6585 Рік тому

    Could you please provide links to reference guidelines?

  • @altamashsayed5264
    @altamashsayed5264 2 роки тому

    I need urgent help.
    Actually I got bit confused.
    I have to select cable, which load I should consider while selecting cable size from transformer to MDB
    Should it be tcl amp or peak load amp or transformer amp or circuit breaker amp.
    Pls do reply as early as possible

    • @ElectricalInfinity
      @ElectricalInfinity  2 роки тому +1

      Usually a cable between transformer and supply connection facility is provided by supply authority and is sized depending on transformer secondary side ampere setting. Supply connection facility is used by supply authority to set the current to certain required amperes depending on supply application done by electrical consultant by calculating max demand. The cable from supply connection facility is sized depending on circuit breaker setting in supply connection facility.
      I hope this answers your question.

    • @altamashsayed5264
      @altamashsayed5264 2 роки тому

      @@ElectricalInfinity appreciate your reply..

    • @anwarullakhayoom7863
      @anwarullakhayoom7863 2 роки тому

      Always cable +breaker is sized as per continous current of the Transformer + consider the derating factors for grouping depth of laying and Thermal withstand capacity. and also the voltage drop . all calculated precisely.

  • @digantpatankar3758
    @digantpatankar3758 2 роки тому

    Sir please mention cable size.....in SLD...

  • @muhammadwaqas4699
    @muhammadwaqas4699 Рік тому

    Circuit breaker calculations?

  • @AK_Entertainment26
    @AK_Entertainment26 Рік тому

    please upload video we are waiting for new video

  • @itz_tipzy5949
    @itz_tipzy5949 2 роки тому

    Where is the standard to be exact for 2bhk 5kw energy meter and 3bhk 7.5kw? I need to furnish it for a project of mine...

    • @ElectricalInfinity
      @ElectricalInfinity  2 роки тому +1

      IS 13010

    • @itz_tipzy5949
      @itz_tipzy5949 2 роки тому

      @@ElectricalInfinity thank you so much

    • @itz_tipzy5949
      @itz_tipzy5949 2 роки тому

      @@ElectricalInfinity can't find it in there... Is it mentioned explicitly that for a 2bhk this much capacity energy meter and so on... I have calculated loads of all flats individually but even after taking into diversity factor the load is quite large...

    • @itz_tipzy5949
      @itz_tipzy5949 2 роки тому

      @@ElectricalInfinity also if I could discuss it with you somwhere else..

    • @ElectricalInfinity
      @ElectricalInfinity  2 роки тому +1

      It's a general thumb rule contractor follows for considering total load. Usually it's 0-10 amps, 10-20amps and 20-30 amps energy meter rating.

  • @tamaghnadutta1644
    @tamaghnadutta1644 2 роки тому

    From where I can get the Standerd chart of Transformer , Cb e.t.c

    • @ElectricalInfinity
      @ElectricalInfinity  2 роки тому

      You can get Transformer standard sizes from supply authority and cb sizes from manufacturer manuals or datasheets.

    • @anwarullakhayoom7863
      @anwarullakhayoom7863 2 роки тому

      Buy TNEB Hand book.

  • @Aliajikar89
    @Aliajikar89 2 роки тому

    Raw power is done ...Sir plz added ups power....

  • @sefatullah441
    @sefatullah441 2 роки тому

    please make your next video at low speed

  • @AbidKhan-tj6en
    @AbidKhan-tj6en Рік тому

    Ipad kaun sa hai bhai btana lena hai mujhe

  • @mustafaidris6476
    @mustafaidris6476 4 місяці тому

    Thank u , but its very fast way so
    As you r trading from papers

  • @tharserohit
    @tharserohit 2 роки тому

    Bhai single phase meter kitna load leta he

  • @electricalconcept32
    @electricalconcept32 3 роки тому

    Sir can you tell me if load is 868KW, power factor is.0.8 and voltage is 415v and the cable length is 138meter.
    Which size cable we should chose to have maximum voltage drop of 3 percent

    • @anwarullakhayoom7863
      @anwarullakhayoom7863 2 роки тому

      Calculate VD on actual current , Not on Derated Current. Derated Current is only for cable+Equipment selection.

  • @mangeshdalvi842
    @mangeshdalvi842 3 роки тому

    Whay about shop, if considerd?

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому +2

      Well we need add total load of the shop and consider demand factor as 0.8 to 0.9 for commercial places.

  • @sherifgamal730
    @sherifgamal730 2 роки тому

    Can i have this Sheet you write in the video please?!

  • @sumanbepari609
    @sumanbepari609 2 роки тому

    How a flat will use 3 phase???

    • @ElectricalInfinity
      @ElectricalInfinity  2 роки тому

      All loads are distributed equally among each phase of 3 phase supply. Usually the loads are single phase for example lighting circuits and power loads. If it's 3 phase load then a 3 Phase supply is provided.

    • @sumanbepari609
      @sumanbepari609 2 роки тому

      @@ElectricalInfinity sir, then there are SPN inside the room which are not showing here???

    • @anwarullakhayoom7863
      @anwarullakhayoom7863 2 роки тому

      upto 3KW - 1PH /240V IS enough , >3kw opt for 3ph 415v.

  • @VijayKumar-qx1kr
    @VijayKumar-qx1kr 2 роки тому

    IN FOUR POINT HOW WILL YOU DESIGN THE PANEL?

  • @mudassariqbal8532
    @mudassariqbal8532 Рік тому

    You should explain it according to any international standard,

  • @shaneefh926
    @shaneefh926 2 роки тому

    For 19 amp y we use 40 amp breaker+

  • @mobilesandcomputers5931
    @mobilesandcomputers5931 2 роки тому +1

    ONLY I NEED YOUR ONLY FEW TIME IF POSSIBLE I WIST YOU GIVE ME POSITIVE RESPONSE

  • @outofthebox6027
    @outofthebox6027 3 місяці тому

    Sir can you share the notes??

  • @everything7790
    @everything7790 3 місяці тому

    1 KVA = 1.9 anybody explain please
    in my calculation its is 1.39 something

  • @prithivi5440
    @prithivi5440 Рік тому

    Hloo bro can you share your linked in profile?

  • @khan__123
    @khan__123 2 роки тому

    Bhai ye pen kaha se magbaye

  • @mohammedezaj1018
    @mohammedezaj1018 3 роки тому

    Where is cable sizing, voltage drop, sc calculation?

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому +3

      Will make another video for that. The video would have become lengthier if added everything you asked for.

    • @mohammedezaj1018
      @mohammedezaj1018 3 роки тому

      @@ElectricalInfinity Thank you

  • @farazuddin7160
    @farazuddin7160 9 місяців тому

    they said three lift but write only two lifts

  • @md.gufranansari9672
    @md.gufranansari9672 3 роки тому

    This video already you had made

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому +1

      Steps 4 and 5 are different. This one is for high rise building not g plus 5. Watch it full you will know the difference. 😊

  • @peopleofkpk5558
    @peopleofkpk5558 Рік тому

    Very interesting but your vedios is too much fast 🙈

    • @ElectricalInfinity
      @ElectricalInfinity  Рік тому

      Thanks and sorry for that. You can use reduce the speed to 0.8x while watching

  • @notfalcongaming7839
    @notfalcongaming7839 2 роки тому

    Hlo

  • @kashmirengineeringvision
    @kashmirengineeringvision 17 днів тому

    really helpful amir need a small help is it possible to get in touch with you that will be your most kindness