76-Downfeed & indirect water supply system for high rise building,rooftop water tank & booster pump

Поділитися
Вставка
  • Опубліковано 26 лис 2024

КОМЕНТАРІ • 37

  • @Refresher_Claps
    @Refresher_Claps Рік тому +2

    Thanks for your video sir. Can you share a video of pipe sizing of the water supply system (ppr piping). Thank you

  • @Vicky32334
    @Vicky32334 2 місяці тому +1

    How did u know 0.33 bar pressure for each floor without booster pump? Any formula ot refrence, somewhere u me tioned 0.433psi per feet and here 0.33 bar per floor. Plz clarify

  • @paulakoh4870
    @paulakoh4870 Рік тому

    Hi, thanks for the tutorial. Here are my questions
    1. How do you know the number of floor where the min required pressure won't be available.
    2. Is the 1.5bar min pressure the required pressure of any fixture in the floor? Lets say WC flush tank
    3. How did you arrive at 1.6bar for the floor with gravity supply

    • @ncengineeringtechnology3376
      @ncengineeringtechnology3376  Рік тому

      First calculate required pressure for each floor.
      Check the required pressure for fixtures and appliances from catalogue. Consider maximum pressure fixture .if you have water tank on roof then calculate pressure by gravity at each floor in the riser. if riser pressure is less than required then you need to supply this floor by booster.
      Please watch this video again, I think you will understand. then for any doubt you can write me, here or can send email also. I will clarify you.
      For each feet riser you need 0.433 psi pressure.

    • @paulakoh4870
      @paulakoh4870 Рік тому

      @@ncengineeringtechnology3376 thank you very much. I will revit back if need be

  • @johnjoseph1789
    @johnjoseph1789 Рік тому

    Thanks sir god bless you

  • @johnphilip7084
    @johnphilip7084 Рік тому +1

    14 floor u added (.33 +1.5 ) bar how this got

    • @ncengineeringtechnology3376
      @ncengineeringtechnology3376  Рік тому

      we selected terrace booster pump at 1.5 bar, it is the minimum pressure required for top floor,
      as we go down the pressure in the network will be = booster pump pressure +pressure by gravity duty level difference.
      at 14th floor 0.33 bar is pressure due to level difference & 1.5 bar is by booster pump.
      Floor height =11 ft
      pr to lift water 01ft = 0.433 psi
      Pressure for 11ft = 0.433x11= 4.763 psi
      = 0.328 bar
      = 0.33 bar

  • @johnphilip7084
    @johnphilip7084 Рік тому

    hi for booster pump of 1.5 bar how we decide, is there any calcalculation for that,for feeding 3 floor of 5 flats each.

    • @ncengineeringtechnology3376
      @ncengineeringtechnology3376  Рік тому

      1-calculate pressure required for each floor.
      2- check if pressure available by gravity is less than required, then feed this floor by booster,
      3- Booster pump pressure = max. difference between required pressure & available pressure by gravity at any floor.
      It is generally pressure required at top floor, as at this level pressure due to height difference between water tank and floor is negligible.

  • @johnphilip7084
    @johnphilip7084 Рік тому

    hi dear have some doubts redarding this , assuming 1.8 as peak factor and duration all this from where this is added from.

    • @ncengineeringtechnology3376
      @ncengineeringtechnology3376  Рік тому

      Peak factor is different for different area.
      For your area you can consult water supply authority or you can do your own observations.

  • @pakcivilsurveyor9682
    @pakcivilsurveyor9682 Рік тому

    Thank you sir . Sir kindly agr ap k pass table ho ya excel sheet ho k Kitne gpm k leye Kitna pipe size caheye . To sir ye sheet description me dalde . Shukria

    • @ncengineeringtechnology3376
      @ncengineeringtechnology3376  Рік тому

      You can contact us on email given in channel description,
      try to learn, I have uploaded complete tutorial for domestic water supply system, after that you can ask if some thing is not clear to you, or you need any specific table or chart.

  • @akhilchalla241
    @akhilchalla241 2 місяці тому

    thank you sir

  • @shuhaibop9108
    @shuhaibop9108 11 місяців тому

    peak factor is constand in all cases,if not how it varies

    • @ncengineeringtechnology3376
      @ncengineeringtechnology3376  11 місяців тому +1

      No, peak factor is the ratio of peak demand to mean demand.
      Observe the peak demand in a day and calculate total demand for one day, this ratio will give you peak factor.
      If people living in a building are working, then in morning and evening more people use water,peak factor will be higher, if non working then all people will not use water simultaneously, peak factor less.

  • @hirzellabakhiet8835
    @hirzellabakhiet8835 8 місяців тому +1

    how to calculate available pressure by gravity at any floor please

    • @ncengineeringtechnology3376
      @ncengineeringtechnology3376  8 місяців тому

      0.434 psi for 01 ft water riser height,
      you can watch this video ua-cam.com/video/ttOc0fmkgdU/v-deo.html

    • @Vicky32334
      @Vicky32334 2 місяці тому

      @@ncengineeringtechnology3376 hi bro, if we have riser height of 30feet let say , so we will simply find riser pressure by multiplying (35feetx0.434 psi) means 15 psi total pressure which is equivalent to almost 1 bar. Like this or anythng else plz let me knw.

  • @johnphilip7084
    @johnphilip7084 Рік тому

    from total fixture units is 9400, water peak demand is 754 gpm how this is found from the chat or formula

    • @ncengineeringtechnology3376
      @ncengineeringtechnology3376  Рік тому

      Please watch this video,
      carefully and repeat if some thing you don't understand, then you will know.

  • @nizamuddinz4392
    @nizamuddinz4392 9 місяців тому

    From where you get peak demand and demand factor. Reference pls in ipc

    • @ncengineeringtechnology3376
      @ncengineeringtechnology3376  9 місяців тому

      Peak factor is different for different locality, you can ask your municipality department for it,
      as general practice for medium city we consider it 1.5
      for small projec you can calculate your daily water demand by per capita method, you watch our video
      ua-cam.com/video/NWRCSV1gYgc/v-deo.htmlsi=yRoQwS4bOSxakl4c

  • @KaezLopez-zu1ox
    @KaezLopez-zu1ox 8 місяців тому

    is this free?
    pls answer....

  • @enochnyanney8670
    @enochnyanney8670 Рік тому

    Kindly, how do I get the Excel sheet

  • @naturetube8298
    @naturetube8298 5 місяців тому

    please share excel sheet

  • @johnphilip7084
    @johnphilip7084 Рік тому

    can i have this excel file,

  • @arunborgave6640
    @arunborgave6640 9 місяців тому

    pl share excel sheet sir

  • @gangadharpatneedi1152
    @gangadharpatneedi1152 11 місяців тому

    sir, can u plz send excel file for preparation purpose

  • @dashratghadage9941
    @dashratghadage9941 Місяць тому

    Hind me bole ga tu samjme ayga

  • @johnphilip7084
    @johnphilip7084 Рік тому

    hi dear i sent u mail for excel file