Electrical Designing of G+5 Building with calculations & Single Line Diagram |Total load calculation

Поділитися
Вставка
  • Опубліковано 21 жов 2024

КОМЕНТАРІ • 241

  • @ElectricalInfinity
    @ElectricalInfinity  3 роки тому +3

    Also watch the designing of High Rise Building G plus 10
    ua-cam.com/video/z6_7jpO8zPE/v-deo.html

    • @abdulkadirxussein6277
      @abdulkadirxussein6277 2 роки тому

      Thanks for your response 👍 teacher

    • @demo7790
      @demo7790 Рік тому

      Isn't 0.8 a poor power factor?? while calculating Transformer size??

  • @idrismaialiyu7387
    @idrismaialiyu7387 4 роки тому +3

    I don't even know how to thank you. I'm very grateful for this. My God bless you.

  • @shahbaazalam1003
    @shahbaazalam1003 3 роки тому +5

    I don't have word to express my feelings after watching this video... thank you so much sir....

  • @imran5213
    @imran5213 4 роки тому +3

    Fabulous ,your clearing more n more doubts and making MEP field and design engineers are proud and
    Are very thankful to u.

  • @marlarthan5510
    @marlarthan5510 4 роки тому +3

    I am here with attitude of gratitude for your sharing video. Thank you so much.

  • @vaibhavmandlekar2576
    @vaibhavmandlekar2576 Рік тому

    Thank you sir I am Karnataka I were searching this kind of video from 2 years know I got it and I want to learn more from you sir an also I am doing more hardwork on the work electrician to achieve my goal thank you 😘✌️❤️🙏

  • @AravindKumar-lj7kx
    @AravindKumar-lj7kx 4 роки тому +3

    Sir,this is a simple at the same time a brillant video,keep doing this great work..I am from electrical Bim industry..it will be very useful for my interviews.thank you so much...!!!

  • @tenkasi_tourism
    @tenkasi_tourism 3 роки тому

    Woww superb ji.. no words to say .. my doubts all are cleared.. thankyou so much ..... 🎉🎉🎉 Keep your service.. god bless you

  • @rohanrathodvlogs4045
    @rohanrathodvlogs4045 7 місяців тому

    What a video sir The way you explained all the terms Mind blowing sir ❤️❤️❤️

  • @gurushankars9046
    @gurushankars9046 3 роки тому +3

    First time I visited your channel , great technical knowledge,keep posting new things,we will follow and keep supporting you,more over it was helping us to gain a practical knowledge as an electrical engineer I failed to learn all this thing's from my college, finally thank you keep going 🙏🙏

  • @tanveeralam9974
    @tanveeralam9974 2 роки тому

    Thank you this is very useful for all

  • @priyankkayasth6661
    @priyankkayasth6661 2 роки тому

    Thank you for this informative video. Its Really Helpful and clearing all basics doubts.

  • @happinessinsmallthings4514
    @happinessinsmallthings4514 4 роки тому +3

    u r perfectly posting videos i have inspired technically from ur talent

  • @AbdulWahid-ds7zz
    @AbdulWahid-ds7zz 2 роки тому

    It's makes very easy to be understand the procedure of eliminating power load step by step thanks sir ,,,i requesting you to please make video on designing

  • @MithileshKumar-cx5ec
    @MithileshKumar-cx5ec 2 роки тому

    This video is very useful .
    Thank you so much for making this video

  • @shaharafat9290
    @shaharafat9290 3 роки тому +4

    It's clear and informative. Good job. Can you share more for commercial buildings, Industries?

  • @Ravi-rp3sb
    @Ravi-rp3sb 3 роки тому

    Thanks a lot man.. You are the real engineer

  • @sayalik7568
    @sayalik7568 3 роки тому

    Very very nicely explained.... thank you sir

  • @abdulkasim3592
    @abdulkasim3592 3 роки тому

    Very good valueble inpermation thank you sir🙏🙏

  • @altamashsayed5264
    @altamashsayed5264 2 роки тому

    Please make a video for G+3 floor commercial + 30 floor residential.
    With complete load calculations and cable size selection.
    Hope to see the detail video soon.
    Apart that ur videos are really informative and neatly explained with detailed information

  • @Shane-hq8jl
    @Shane-hq8jl 3 роки тому

    thank you!!!!! saved my day

  • @digitalcreator1793
    @digitalcreator1793 2 роки тому +1

    Woow sir..... Super explain 🙏... Regarding this Notes please upload or send me.. 🙏🙏
    Transformer rating Calculate table
    Mccb mcb table....

  • @sanjaygaikwad9104
    @sanjaygaikwad9104 6 місяців тому

    Thanks sir very useful information 👍

  • @topworldfacts2837
    @topworldfacts2837 4 роки тому

    sir, can i ask to you, what type smartphone you use ? very usefull aplication. big thanks, please answer sir

  • @navyaramanathan5635
    @navyaramanathan5635 6 місяців тому

    Thankyou man.. i cleared my interview

    • @ElectricalInfinity
      @ElectricalInfinity  4 місяці тому

      Great 👍. I am very happy you cleared your interview. All the best with your job.

  • @Shakeel_Mirza
    @Shakeel_Mirza 9 місяців тому

    Best ever explaination you are amazing sir

    • @ElectricalInfinity
      @ElectricalInfinity  9 місяців тому

      Thanks a lot 😊

    • @Shakeel_Mirza
      @Shakeel_Mirza 9 місяців тому

      @@ElectricalInfinity sir can you please make a video that how we can make the SLD in software. Or please suggest me any software in which I can design these SLD

    • @ElectricalInfinity
      @ElectricalInfinity  9 місяців тому

      You can use Powercad for Sld designing. Or AutoCad for drafting sld.

    • @Shakeel_Mirza
      @Shakeel_Mirza 9 місяців тому

      @@ElectricalInfinity thank you

  • @altafali8794
    @altafali8794 2 місяці тому

    Good Information sir

  • @vinodhvinodh4975
    @vinodhvinodh4975 3 роки тому

    Sir, god bless.. thank you a lots...

  • @MH-gw9jk
    @MH-gw9jk 3 роки тому

    Very useful. Thanks you very much

  • @santoshkute703
    @santoshkute703 4 роки тому

    Easily explained video... Thanks brother...

  • @electricaldesignsolutions5595
    @electricaldesignsolutions5595 3 роки тому

    Superb class .thank u so much

  • @sarveshrao1042
    @sarveshrao1042 4 роки тому

    Thanks sir for providing valuble knowledge

  • @sudhachaudhari6058
    @sudhachaudhari6058 3 роки тому

    Very useful video 👍

  • @sadeedahamedkk9784
    @sadeedahamedkk9784 2 роки тому

    Great videos, Really well explained. Appreciate the efforts mahn.

  • @ravichandraba
    @ravichandraba 2 роки тому

    Sir will you undertake load calculation and Transformer sizing and MCB sizing for private building.. we will provide all details

  • @sefatullah441
    @sefatullah441 3 роки тому

    so useful... Plzz keep it up Sir G

  • @PraveenKumar-rh9bv
    @PraveenKumar-rh9bv 6 місяців тому

    Could you please clarify why do we need multiple with 2 for CB sizing for load

  • @zakirhussain8150
    @zakirhussain8150 2 роки тому

    Sir i hava doubt we have 15nos 3 bhk then we use 15 nos 63amp circuit braker for each 3 bhk ? Am i right ?

  • @projectengineer1839
    @projectengineer1839 4 роки тому +5

    Very much Impressive sir, I'm from Execution site but your all video made me keen interest in designing too, it clears each doubt and very very closed to the practical usage too!
    I think none of UA-cam channel provide perfect video like you. Keep updating and please provide your contact information like email id so that we can approach you.
    Thanks for making my lock down period worthful !
    Thanks again sir 🙏

    • @ElectricalInfinity
      @ElectricalInfinity  4 роки тому +2

      Thanks for appreciation. Such comments inspire me to make more videos ❤

  • @abdulgaffar9590
    @abdulgaffar9590 4 роки тому

    Thank you sir you are sharing great knowledge with us

  • @gourangasasmal8815
    @gourangasasmal8815 Рік тому

    We learning many things from your video. thank you
    I request to you please upload a video -G+22

  • @swapnilshiyaniya5306
    @swapnilshiyaniya5306 Рік тому

    Hello sir, on base you selected multiplying factor for 3 phase Ampere current . Multiplying factor 1.9

  • @ashishmisal9282
    @ashishmisal9282 4 роки тому

    very nice explain

  • @shaifsiddique4842
    @shaifsiddique4842 3 роки тому

    Nice one....keep going...good luck

  • @victoraghanti4317
    @victoraghanti4317 2 роки тому

    this is great. Thanks

  • @abusayedmd.rashed7597
    @abusayedmd.rashed7597 Рік тому

    This is good video, thanks

  • @agnirudraghoshchowdhury448
    @agnirudraghoshchowdhury448 4 місяці тому

    Sir can you please tell me why are we multiplying KW with Ampere for Circuit breaker sizing?can you please explain the formula or logic behind this ......

  • @nitinahuja2472
    @nitinahuja2472 3 роки тому +1

    Can we calculate one city power consumption in similar manner?

  • @jiteshrajput3836
    @jiteshrajput3836 3 роки тому

    Superb bro 😎

  • @kaifahmed930
    @kaifahmed930 Рік тому

    Sir what's the reason to use a 50 amp MCB for 29A load?

  • @ayedtannous2902
    @ayedtannous2902 2 роки тому

    very useful videos

  • @amitkhedekar8473
    @amitkhedekar8473 2 роки тому +1

    Very nicely made video and crisp information delivered.
    I have a query. What if the load changes during the project execution ? It may reduce or increase. Then what is to be done about the transformer sizing ?
    Such scenario occurs most of the time.

    • @ElectricalInfinity
      @ElectricalInfinity  2 роки тому +1

      Well the project don't directly go to construction phase. There are different stages like preliminary, tender and construction set. Each stage has 3 to 4 revision. The project will start on site once the construction set is finalised. It takes 3 to 8 months to complete these stages depending on size of project.
      Thanks for appreciation ❤. Keep watching and keep sharing.

    • @amitkhedekar8473
      @amitkhedekar8473 2 роки тому

      @@ElectricalInfinity Yes, that's true and I am aware about the project life cycle. But there are times when the client comes up with some drastic changes (atleast in India). Then how we can accommodate those changes in the already designed power system or what are the other strategies to adopt ?

    • @ElectricalInfinity
      @ElectricalInfinity  Рік тому +1

      We have to reassess the maximum demand to make sure the load is below total ampere. The client can't make any changes to load without consulting electrical consultant. If the load is above the limit even after diversity factors then the project timeline and cost will increase due to changes in supply capacity, reapplying supply application to supply authority, transformer sizing, cable sizing and main switchboard. The client already know the impact and it is upto him. If he want changes then have to bear the cost.
      We can avoid this situation by allowing 15 to 20% spare amperes for future provisions during a preliminary stage of maximum demand calculations.

  • @mohdirshadshaikh444
    @mohdirshadshaikh444 4 роки тому +2

    Very good explanation in less time..
    Please make a detailed videos for electrical Designing in parts and add it into playlist
    Make videos in more details like how to use safety factor of 2
    Thanks in advance 😊

  • @engr.imtiazahmad1051
    @engr.imtiazahmad1051 3 роки тому

    excellent

  • @kr7356
    @kr7356 3 роки тому

    Thank you boss , your technical teaching is awesome !!!!!! am in search of Dubai DEWA electrical designing and calculation , so kindly post a video in that topic sir .

  • @vinodhvinodh4975
    @vinodhvinodh4975 3 роки тому

    Sir, pl tell wat is the incomer cable from metering panel to house

  • @loveleen2567
    @loveleen2567 2 роки тому

    Great...

  • @pavintechengineeringpavint1389
    @pavintechengineeringpavint1389 4 роки тому

    Excellent

  • @Vision267
    @Vision267 3 роки тому

    Why is a safety factor of two used for end MCB ratings?

  • @atifrahman1555
    @atifrahman1555 4 роки тому

    🏇🏇🏇🏇🏇🏇 awesome sir🤺🤺🤺🤺🤺🤺🤺

  • @Vision267
    @Vision267 3 роки тому

    Hi why did you use a 3P MCCB after the transformer instead of a 4P MCCB

  • @umarahmad8001
    @umarahmad8001 9 місяців тому

    Can you please provide the links to sizing charts you used in this video

  • @sundarauslia
    @sundarauslia 3 роки тому

    Good explanation...I need this type of wrtiting pad....where I get?

  • @natasiafisher1669
    @natasiafisher1669 7 місяців тому

    thank you

  • @eizzuddinnawawi5349
    @eizzuddinnawawi5349 3 роки тому

    Tq for the explanation and interactive. Sir, could you please share the calculation to decide the cable sizing please.

  • @Ravi-rp3sb
    @Ravi-rp3sb 3 роки тому

    I would like to learn designing and drafting. Can you guide me what kind of course should i do. What software should i learn..

  • @AkashSingh-jz4zo
    @AkashSingh-jz4zo 3 роки тому

    How to avail these standard tables for transformers, circuit brrakers and cables??

  • @maheemaheesa1824
    @maheemaheesa1824 2 роки тому

    When you find common load circuit breaker size , you multiplied the common load by safety factor.
    But when you do the calculation in high raise building why did you multiplied by demand factor?
    What is the reason for it?

  • @gopikrishna9159
    @gopikrishna9159 2 роки тому

    What about ground floor sir ... is there no 3bhk and 4 bhk flats in ground floor ?

  • @vegvillage-kj9qs
    @vegvillage-kj9qs 8 місяців тому

    Great

  • @Durga189
    @Durga189 4 роки тому

    Great effort

  • @rashidchibvuri2036
    @rashidchibvuri2036 11 місяців тому

    Thanks bro

  • @manusankar2339
    @manusankar2339 3 роки тому

    Good video

  • @aqsaali4829
    @aqsaali4829 3 роки тому

    Sir can you please guide me how to calculate the estimated lighting, small appliance and power loads for each space in w/sq ft. for lighting i can use ashrae standards. but for small appliances how much watt we used for per outlet or area wise?

  • @apollosam44
    @apollosam44 3 роки тому

    Thank you sir for the session. Simple and easily explaned . which device you are using to write. Can you inform with its make.

  • @ikhwanhaziq7630
    @ikhwanhaziq7630 5 місяців тому

    Good

  • @piyushpandey6303
    @piyushpandey6303 3 роки тому

    amazing vidio please make for hotel

  • @smartelectrician9406
    @smartelectrician9406 Рік тому

    Sir is the peak demand of the building is the total load of the building

  • @pandawani1278
    @pandawani1278 Рік тому

    Are you open for courses by zoom? I wanna to learn more

  • @truefaceofmo8307
    @truefaceofmo8307 3 роки тому

    We TP mccb for common load?

  • @sefatullah441
    @sefatullah441 3 роки тому

    try to upload more videos related to electrical design plzz

  • @klmkt4339
    @klmkt4339 3 місяці тому

    Good. Man.

  • @piyushvaghela9496
    @piyushvaghela9496 3 роки тому

    Mam I really impressed your knowledge..And i have plz request ,I want to Work with under your guidance... 👍👍🙏

  • @niranjanmishra9359
    @niranjanmishra9359 Рік тому

    Good ,But miss the cable part... Sizing and type according.

  • @abdulkadirxussein6277
    @abdulkadirxussein6277 2 роки тому

    Fast I want to thanks you teacher second I have question you calculate 3BHK in 15no's and each 3BHK in 5floor is 2 so if I multiply 2×5floor = 10no's so how you get 15no"s thanks teacher

  • @venkateshnayak9809
    @venkateshnayak9809 3 роки тому

    Your teaching is great but u didn't consider ground floor for calculation. Its G+5=6. So its 5 or 6 for flat load calculation. Pls do reply.

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому +1

      Mostly ground floor is used for parking. No flats on ground floor.

    • @venkateshnayak9809
      @venkateshnayak9809 3 роки тому

      ​@@ElectricalInfinity Thank you very much for the reply sir.

  • @Kk-hs4qf
    @Kk-hs4qf Рік тому

    2BHk 5Kw... where can I find the code? NEC or any specnfnc IS? Please quote the standard.

  • @sagarkanojiya103
    @sagarkanojiya103 4 роки тому +1

    Though I'm a fresher still I understood maximum part of these video
    Great work sir...
    Can I get your linkedIn id ?

  • @shyamdas8863
    @shyamdas8863 2 роки тому

    What is the purpose of that 2 safety factor

  • @vairagijayesh
    @vairagijayesh 3 роки тому

    Thank you sir .. Can you please recommend book Or any online course so we can learn in detail 🙏

  • @sheikhsadi8605
    @sheikhsadi8605 3 роки тому

    Awesome constant !!! Can you give a book or published paper reference on your the statement and formula that you used in the video?

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому

      That’s what we follow at our workplace and I don’t have any published papers on this.

  • @mohammedjaberasim8259
    @mohammedjaberasim8259 3 роки тому

    Excellent sir, thanks a lot . Kindly do design video for high rise towers like 20 floors and above. Regarda

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому

      Welcome. Will make one soon

    • @sefatullah441
      @sefatullah441 3 роки тому

      we will waiting for ur next video related to design

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому

      @@sefatullah441 here is a video for you on high rise building ua-cam.com/video/z6_7jpO8zPE/v-deo.html

    • @sefatullah441
      @sefatullah441 3 роки тому

      thanks alot sir G... you are genius

    • @sefatullah441
      @sefatullah441 3 роки тому

      thanks alot sir g... try to upload more videos related to building design..
      cable sizing farmula etc... more videos please..
      God bless you

  • @Vision267
    @Vision267 3 роки тому

    How can we decide the short circuit ratings of MCCB and MCB?

  • @mohamedsalam2905
    @mohamedsalam2905 2 роки тому

    Mashallah

  • @AMANKUMAR-jt2hx
    @AMANKUMAR-jt2hx Місяць тому

    may you please provide the pdf of electrical design data , where you have written the sizes

  • @vishals11
    @vishals11 4 роки тому +1

    any software would you recommend for this ?

  • @adityaghewari1335
    @adityaghewari1335 3 роки тому

    Sir... Can 3 bhk flat work on single phase

    • @ElectricalInfinity
      @ElectricalInfinity  3 роки тому

      Depends on load. If the power load is less , for example no AC or geysers then single phase is fine.

  • @MH-gw9jk
    @MH-gw9jk 3 роки тому

    Please prepare similar video for 30x40size 3 floor building

  • @anasvahab613
    @anasvahab613 3 роки тому

    very good video , but SLD is wrong since it is a high rise building your have to provide MDB , from MDB to SMDB for each floor from SMDB to DB for each Flat
    for eg -MDB to SMDB -1 ( floor 1) then from from SMDB 1 to DB 1( flat -1 3bhk ) , SMDB 1 to DB 2 ( 4 BHK ) etc
    According to the load of SMDB & DB Cable Size Has to mention in SLD

  • @HariHari-jr5pg
    @HariHari-jr5pg 3 роки тому +1

    I WANT DETAIL TO DESIGN CONTROL PANELS, FLC*MULTIPLIER FOR SFUNITS, CONTACTOR ,OLR,CABLE FOR IN&OUT CABLE TO ALL TYPES OF CONTROL PANELS & GEN-SET PANEL S ETC.