If EPS differs from a UPS by switch over time how do you explain the inverter sharing load between say the solar panel supply and the grid supply. There is no switching between the two is there? Doesn't it just share the load ?
Hi, We have one of these inverters installed with solar panels connected. The solar panels don't show that they are charging the batteries. what must I do. Is it just a setting?
Good day, i installed my 5kw inverter but when i log in via the web, it only shows a few parameters on charging that can be changed, it only shows info on lead acid battery although i have a LifeTide 5kwh battery connected. How do i get into this page to check everything as per the training video.
I want to configure my inverter so that when my battery state of charge (SOC) drops to 10%, the inverter stops supplying power, and the grid takes over to supply the load without charging the battery. The battery should only recharge using solar photovoltaic (PV) panels. How can I achieve this setup?
Hi, I got a notice on the app. EPS Voltage High. This morning when loadshedding started it gave no backup power. Inverter not connected to the db bord. It pre assembled trolly setup.
If the installer add my inverter to his system, am i still able to connect to app as the end consumer as the PIN will have been used or i will be at the mercy of the installer to get log in details
Awesome video's....well done. Quick question i have 2 5kw 100a batteries, should my monitoring app now say 200amp or is it fine that it still says 100amp?
I have two more settings at nr. 6 that is not documented. Not sure what the values should be...I have (what looks to be) Ic, Idc and Igc Looking at the web setup the extra 2 are probably AC charge battery current and Generator charge battery current?
When Using a lithium on lead acid setting how do I tell the inverter what voltage range to look at so it displays 100%, when My lithium with no comms has reached float status. it always show 75% only on web when full
Why do I not see the generator block in the Application settings, Also if I change settings on the generator it gives me an operation failed - error code 1? I also do not see the Remote update on the left hand side of the screen?
Hello, great video. I love your product and would like to purchase your LuxPower LXP-LB-US 12KW Hybrid Inverter with the wifi accessory. I have emailed your sales team but have not received a response. Thank you!
As a installer with 70 odd units in the field my distributor/supplier to date cannot help me register as a installer! How do i go about it? I am based in Randburg, Johannesburg, South Africa
Then When does the Buzzer actually sound as it seems to only work when pressing buttons, low battery warnings seems silent and catch you by surprise, How do i activate warning with a sound?
Приветствую Lux sna5000 был куплен в интернет магазине При регистрации просит код клиента Я обратился к продавцу На что получил ответ ,,заплати денег ‘’ Как мне зарегестрировать продукт ? В дальнейшем планирую ещё две станции приобрести Местные дилеры много денег хотят при нынешней ситуации А официальный говорит чтоб обращался к местным дилерам Но они мне не помогли Что мне делать? Спасибо
Hi Guys Just did setups on my LuxPower inverter however I am not sure about the batteries codes. I am using Shoto. On the table shared on the video the Shoto code is number 2. But I also hear you say that we can also use code number 6. Which one is which? Please advise
Hi thanks very for up louding this video we appreciate it I just bought lux power inverter and Hubble Betty I am struggling with my setup everything is connected fine but issue is my battery is charging up to 48% I think actually I know l am set up wrong I want it to change up 100% or is that wrong I am using Eskom to change it up I don't have solar yet is 5kva inverter and 5.5v Hubble battery lithium
Hello good people. How can i get hold of Jaco. We have purchased 3 lux sna5000 inverters. All 3 sites have the same problem. When loadshedding we get eps overload. The suppliers said we have to upgrade the firmware. They have uograded 2 sites remotely. After that the 2 site became worst. The first issue still not resolved. Inverter trips qith loadshedding and now the best part is, the panels for one or other reason watts are so weak. The batteries reach a percentage like 85% and it stay there even when grid charge batteries. I even saw forums where people from the uk ask how is the inverter and saw its from sa. The 1 guy replied and said there are now support and that is true. You do t get support from lux support team. So please i need help. Thanks
Hi. My SNA5000 works great so I decided to increase loads :-) and for this reason I'm planning to parallel another one. The question is: If I have a master with 2 strings and a battery rack and a slave with ONLY ac in and ac out can the system manage a load exceeding 5KW draining batteries and PV till 5 kW and the remains by the grid through the slave? Thanks
Приветствую Ошибка внутренней связи 2 Не принимает с сети и не отдаёт в бекапе Батарею показывает Сеть показывает Без сети пишет статус Нормал Как появилась сеть сразу в ошибку падает в статусе! Кто подскажет? Могу скинуть даталог
Hi I have an sna5000wpv , on Maintain , I only see remote set. How can I get the full installer settings profile?
Setting 20 (Green Functions) has 2 options, UPS ECO and BAT ECO. The manual only mentions ECO Mode on/off. What does BAT ECO do?
If EPS differs from a UPS by switch over time how do you explain the inverter sharing load between say the solar panel supply and the grid supply. There is no switching between the two is there? Doesn't it just share the load ?
Hi, We have one of these inverters installed with solar panels connected. The solar panels don't show that they are charging the batteries. what must I do. Is it just a setting?
Good day, i installed my 5kw inverter but when i log in via the web, it only shows a few parameters on charging that can be changed, it only shows info on lead acid battery although i have a LifeTide 5kwh battery connected. How do i get into this page to check everything as per the training video.
I want to configure my inverter so that when my battery state of charge (SOC) drops to 10%, the inverter stops supplying power, and the grid takes over to supply the load without charging the battery. The battery should only recharge using solar photovoltaic (PV) panels. How can I achieve this setup?
Hi Sir, thanks for your reaching out, could you please tell me which model or SN do you use? Different model has different working modes and settings.
Hi, I got a notice on the app. EPS Voltage High. This morning when loadshedding started it gave no backup power. Inverter not connected to the db bord. It pre assembled trolly setup.
How do I set it up that it doesn't use battery when the grid is on? Thanks.
If the installer add my inverter to his system, am i still able to connect to app as the end consumer as the PIN will have been used or i will be at the mercy of the installer to get log in details
Awesome video's....well done.
Quick question i have 2 5kw 100a batteries, should my monitoring app now say 200amp or is it fine that it still says 100amp?
I have two more settings at nr. 6 that is not documented. Not sure what the values should be...I have (what looks to be)
Ic, Idc and Igc
Looking at the web setup the extra 2 are probably AC charge battery current and Generator charge battery current?
When Using a lithium on lead acid setting how do I tell the inverter what voltage range to look at so it displays 100%, when My lithium with no comms has reached float status. it always show 75% only on web when full
Why do I not see the generator block in the Application settings, Also if I change settings on the generator it gives me an operation failed - error code 1? I also do not see the Remote update on the left hand side of the screen?
Hi, kan ek Jaco se nommer kry asb. Wifi dongle sien nie wifi of inverter nie. Dankie.
Hi what is the Ac first charge settings for
Thanks
Hello, great video. I love your product and would like to purchase your LuxPower LXP-LB-US 12KW Hybrid Inverter with the wifi accessory. I have emailed your sales team but have not received a response. Thank you!
As a installer with 70 odd units in the field my distributor/supplier to date cannot help me register as a installer! How do i go about it? I am based in Randburg, Johannesburg, South Africa
Hard to believe this. Who is your supplier?
Where can l find the training manual
Hi ,(sna5000) can i put one string panels (5400watt) on the pv1 input and just bridge/bond the pv 2 input?
Can I be added to the community group please, I intend connecting the generator to the inverter and want to know if some one can assist
Hi there, I have a SNA5000, does the inverter trip the CONLOG meter if its used in hydrid mode
Why does my battery charge until its full and switch grid off and then use from the battery and then charge battery again with grid supplying the load
you need to check your charge settings parameters and Discharge settings parameters as well
Then When does the Buzzer actually sound as it seems to only work when pressing buttons, low battery warnings seems silent and catch you by surprise, How do i activate warning with a sound?
ps, my buzzer setting is enabled
Приветствую
Lux sna5000 был куплен в интернет магазине
При регистрации просит код клиента
Я обратился к продавцу
На что получил ответ ,,заплати денег ‘’
Как мне зарегестрировать продукт ?
В дальнейшем планирую ещё две станции приобрести
Местные дилеры много денег хотят при нынешней ситуации
А официальный говорит чтоб обращался к местным дилерам
Но они мне не помогли
Что мне делать?
Спасибо
You should note the dongle only works on 2.4ghz Wi-Fi and not 5ghz
Hi Guys
Just did setups on my LuxPower inverter however I am not sure about the batteries codes. I am using Shoto.
On the table shared on the video the Shoto code is number 2. But I also hear you say that we can also use code number 6.
Which one is which?
Please advise
Hi thanks very for up louding this video we appreciate it I just bought lux power inverter and Hubble Betty I am struggling with my setup everything is connected fine but issue is my battery is charging up to 48% I think actually I know l am set up wrong I want it to change up 100% or is that wrong I am using Eskom to change it up I don't have solar yet is 5kva inverter and 5.5v Hubble battery lithium
Hello good people. How can i get hold of Jaco. We have purchased 3 lux sna5000 inverters. All 3 sites have the same problem. When loadshedding we get eps overload. The suppliers said we have to upgrade the firmware. They have uograded 2 sites remotely. After that the 2 site became worst. The first issue still not resolved. Inverter trips qith loadshedding and now the best part is, the panels for one or other reason watts are so weak. The batteries reach a percentage like 85% and it stay there even when grid charge batteries. I even saw forums where people from the uk ask how is the inverter and saw its from sa. The 1 guy replied and said there are now support and that is true. You do t get support from lux support team. So please i need help. Thanks
Seems to be a battery issue here
What is the maximum passthrough current of this inverter ?
I'd also like to know please
Answer is in the video
Do you have the name of a LuxPower Installer in Cape Town ?
Hi.
My SNA5000 works great so I decided to increase loads :-) and for this reason I'm planning to parallel another one. The question is: If I have a master with 2 strings and a battery rack and a slave with ONLY ac in and ac out can the system manage a load exceeding 5KW draining batteries and PV till 5 kW and the remains by the grid through the slave?
Thanks
Please inquire your local installer for system design.
Пишет
Ошибка внутренней связи 4
Что это?
Спасибо
Hi can I be added to installers group please? Thanks
Please add me in the group i am an installer
Where can I download the install menu
or Manual
please advice where can i get the training manual
Приветствую
Ошибка внутренней связи 2
Не принимает с сети и не отдаёт в бекапе
Батарею показывает
Сеть показывает
Без сети пишет статус Нормал
Как появилась сеть сразу в ошибку падает в статусе!
Кто подскажет?
Могу скинуть даталог
Please sir I m Kiki could please add more on the luxpower group
where can i get this training manual
Does your system support Vestwood batteries?
Looking for the dongle IP Client settings. port and ip please
How do I get the inverter out of the standby mode
go to the maintenance menu, under application settings, locate Normal/standby then activate to normal.
which group can we join?
Thanks
I have a SNA5000 - is this approved in Cape Town. Please add me the group
Please assist in registering as an installer
Please I need the same, did u come right
Did you ccome right i also need to register
Please add me to the installers group please thanks
Please add me to the group.
Add me to the group
I have just bough the Luxpower SNA5000 and will be installing soon as it arrive please add me to the luxpower group
Please add me to the group
Hi please add me to the group
can you please add me on group..
Please add me tp the group
Please add me to the group