Luxpower Online Training for Web Monitoring Introduction

Поділитися
Вставка
  • Опубліковано 19 лис 2024

КОМЕНТАРІ • 5

  • @christoffkruger
    @christoffkruger Місяць тому

    Fantastic tobhave these videos. This is what makes Luxpower stand out (not just their features).
    Where can I get this PDF document, it will make a handy reference manual for my installations.

    • @LUXPOWERTEK
      @LUXPOWERTEK  Місяць тому

      Hi Sir, thanks for your reaching out. Can I have your email? We will share the document with you.

    • @darrencarter7294
      @darrencarter7294 Місяць тому

      Yes please. This would be most helpful.

  • @artemchubenko
    @artemchubenko Місяць тому

    Hello Andy. I am an installer and prefer LuxPower to setup.
    Couple of questions from me:
    1. Let’s image that a customer have 3 phase In AC, but with very limited power, aprx 5 Kw for each phase. Same time the customer doesn’t have a 3F equipment, so it is better to set up a 3 machines for 1 F to divide a load. Can I add the AC in via Gen port to each inverter, so the Luxes will ignore the sinus? In this case I might have a divided load with full AC support.
    2. The situation was with Smart load.
    I enabled it, but I found that load from Gen port used directly AC when AC available instead of using inverters power (battery and PV). Maybe I missed something with settings.
    3. When I settled up a Smart load, I connected a neutral bond from AC out and GEN to an AC neural.
    Usually, without using a smart load I normally connecting AC out neutral from inverter to a city AC neutral and everything is ok.
    However when I also connected the Smart load neutral to city neural, turned on machine then enable the city AC and at that moment did not turned on the EPS button On, I am receiving a 20th error. If I do the same set up with a wires, turn on machine first, then EPS on and then city AC - I don’t receive such error.
    PS - I sent a video to support with this issue.
    Thanks.

    • @LUXPOWERTEK
      @LUXPOWERTEK  29 днів тому

      Hi Sir, thanks for your reaching out.
      For your question 1: We don't recommend that connect generators to each inverter in the parallel system, the system will not operate.
      For your question 2: We guess that you enable the function "Grid always on" in the Smart Load setting section.
      For your question 3: I also forwarded this error to our tech-support, they will reply to you asap.