As a retired machinist I will say that you did a professional job. You obviously planned out the project and it shows. The lines looked plumb and level. The hose mounting clips all looked at the same level and spaced evenly. And the hose itself is pulled straight, not drooping like Xmas tree lights. Also, I have the exact same moisture/filter and regulator (SAF and SAR 4000?). The SAF performance is just ok so I added a Motor Guard M60 filter to trap additional moisture. Thanks for the video.
I set up my garage in similar fashion, however I used copper pipe and sweated necessary fittings. I have a sand blast cabinet along with tools throughout the garage. Been running it for 2 years. With no leaks or issues.
Thank you for the time you put into this. I am starting my piping today. At the bottom of the vertical runs, and at the distribution blocks, I will install a 12 inch or longer pipe down to the drain valve to have a reservoir to collect the water so the air doesn't have to bubble through it between drainings. Maybe useful, maybe overkill, just me. I also plan to take off the top of the horizontal runs using a T for my feed lines. My thinking is this will reduce the amount of moisture to the point of use. Your time and effort in this saved me a great deal of time and research. It is easier to build on an existing project than to start from scratch. Thanks again for taking the time to produce this video.
I though about doing this in type "M" copper. It's cheaper than "L" & faster than black. You've got an awesome setup, there. Thanks for the tip on using that hose as a buffer for neutralizing vibration.
This is a great replacement for my old regulator/oiler that started leaking It came with brass nipples that saved me a trip to the hardware store and even came with teflon tape.
Very good.... Thanks for the information and recommendations. Just had an electrician hardwire my DeWalt today and I’ll be ordering this kit in a few. I’m not much into the tech world but I love UA-cam! Thanks again!
Great video. Gives me a lot of idea. Questions: This video is 6 years old. Have you attached an air dryer/cooler addition to your setup? Where do you drain out the tank condensation to in the closet? thanks.
Looks like a very well thought out and executed setup. Simular to what I'm envisioning for my shop, except with the use of PEX and normal fittings instead of the Max Air kit. I have my compressor in a lean to along the side my 30x30 building. I will be running 3 drops along each side of the building and one down the center support column to a reel, making the system an H shape when looking from the front of the shop.
Please read.. the electric motor on ours cought fire in a well ventilated room. It was a husky brand with the same electric motor as yours. Ours wasn't the only one. It was about 4 years old.
Dang hows he gona say somthing like that, then leave us all hanging? I'd like to know what brand motor catches on fire lol. Ofcourse it's on a husky thou, I seen one of there ratcheting end wrenches catch on fire one time...to much torque I guess🤷♂️.
Condensate forms in the piping. As such, you do not want it plumb to the ceiling, you want it pitched away from the compressor 2" per 25' of run. Your blue piping is already flexible. It you used a valve with a pex barb at the compressor you could have connected directly without the whip.
so even though you have breaker on that outlet, that you can shut off, you still stand a chance of getting water in that outlet if you have to open up your waste line and snake it from a clog.
Drop Tine True, I keep the disconnect in the off position whenever I'm not using the compressor so chances are it will be deenergized...but good point none the less. Thanks for the comment.
Great video! Just got the newest version of this compressor from Tractor Supply. What is the cut on/off pressure on the compressor? I noticed it has a bung at the front that is blocked off, is that where you can take control of when it cuts on and off?
Double pole 20 amp is 40 amp overall you should run intake through wall to outside, I did really quiets down and you get fresh air., I did a 25 foot of 1/2 inch copper tubing between compressor head and tank with air separator just before tank will drop your air temperature and reduce moisture in tank.l hardly ever get any water after doing it
Most recommend having an 18" clearance away from the wall for air flow. Do you find having it in such a closed - in space a problem with air flow for the motor?
Had 2 of those from lows..china built..runs vary loudly..,change the oil every 2-3 hundred hrs..I hope your room is vented ..nice set up..I went American made..no more China crap..have a Saylor-beall..made in st.johns ,Michigan..All American American iron..Baldor motor..mine runs on a 30 amp.220 v..and runs vary quit..my 3 hp. Unit is a 2 stage pump..spent 3 grand ..I would put a fan in your closet..again love your set up..I'm now retired..I'm in fl. So for heat issues my unit has an after -cooler built on my unit with a fan..built on the motor..check out utube video on Saylor-beall..fully pkg unit ..ul see how they build there. Comprsoir s...u can do a set up on yours simply..add on to yours ..
I had always heard to NEVER use pex for air lines. They always leak at the push fittings....and if it doesn't now, it will. I was debating doing 3/4 copper pipe
Thanks for this, a thorough overview and exactly what I was looking for. That said, I think you used 30a fuses in the disconnect, may I ask why? You already have a 30a breaker on this circuit, so is this redundancy needed? Or am I missing something? Thanks again.
The disconnect I used requires cartridge fuses in order to work...completely not needed but it was the only disconnect I could find at the time. The breaker alone is more then sufficient. Hope this helps.
@@fixitwithzim Not sure, but I think the panel breakers are not designed to be used as "switches". Just resets when tripped. The disconnect is a switch.
When you first installed your Air compressor, did you leave it open to the atmosphere and run it for 30min-1hour to break in the motor? I'm looking to install mine and I've seen a few videos recommending it.
Putting the twist lock also makes it code complaint.the 20 percent rule is to keep the wires from over heating it definitely should be 10 gauge and if it’s more then 75 feet should be 8 gauge .
Hi more power to your channel ,I got a question I have a 50 ampere service in my garage and it’s 220volts can I use my dewalt air compressor same as what you have?do you think it’s possible?thanks any comments is greatly appreciated.
Great vid man but one question, in your finished basement, how do you drain off the compressor tank itself without staining the floors with the brown oily condensate that comes out of the main tank? A lot of water builds up in them no matter what if you don't have a pre-cooler and trap before the tank in but after the pump.. I use a car transmission radiator and gravity trap below the tank drain so had to mount the tann on a big block pad.. Gotta drain off those tanks at least once a month otherwise that closets gonna turn into a window to the garage..
Thanks very much for taking the time and trouble to lead the way. I just bought my 60 gal. tonight and your video has a ton of great tips tricks and important things to think about. Especially glad you're a "code" guy like me.
You need already 3/4 inch line leaving tank you have really cut down your volume, with the 60 gallon 155 I found it best to reduce pressure setting to 135 to prolong life of compressor they struggle the last 15 psi to shut down and you will never need 155 psi,, l went from 7 to 5 minutes to fill tank from empty. Will give you year's longer
It's been around 3 yrs since you post your video- question, has the rapid air system held up to your expectations? Also I think you did a great job installing. I too would put a shut off valve where you said you should..thanks for sharing!
i thought i heard you say that you ran romex through the conduit? that would be a bad idea for several reasons including being a code violation but more importantly its a fire hazard. the sheathed wire (romex) is not rated for use in conduit ; at the very least the sheathing should be removed from the conductors to avoid excess heat buidlup inside the conduit. Not trying to be negative at all, just a headsup in case you actually did run romex inside that conduit don't want your house to catch fire and do want you and your family to stay safe. Nice neat install
Don Alexander thanks for the comment. You’re partially incorrect regarding Romex in conduit. NEC 300.4 actually calls for protecting conductors and cable where physical damage might occur. I believe it goes on further to say NM cable sleeving is recommend in areas subject to these conditions. You can take that interpretation anyway you’d like. In my case, I believe I used 1 1/4 conduit to sleeve the NM cable. In my opinion, there is no chance for harm here, especially with both ends of the conduit open and not sealed and the cable having plenty of “breathing room” in an oversized pipe.
@@fixitwithzim Your PVC (or CPVC - or whatever you're using) isn't sufficient. Period. The code is really only worried about physical damage from nails or screws... Here's a DIRECT quote from NEC 300.4: the cable or raceway shall be protected from penetration by nails or screws by a steel plate, sleeve, or equivalent at least 1.6 mm (1⁄16 in.) thick. For the safety of your family, protect those wires. Please. Are you likely to cut into them? NOOO!!! Could it "maybe" happen? YEP! That's the reason for codes.
ddotodd11 thank for your concerns, yes understand what your saying but there is zero chance of someone screwing into that conduit (8 inch poured concrete foundation wall on one side and the opposite side is open in free space, not hidden where a nail or screw puncture would be possible). But yes, in a concealed space, emt would be in order and the better choice
Was the price of a long 3/4 hose more han the whip? Just cut and add a new end if not. Leftover hose gets an end too, does it matter if it's 12 inches shorter? Nice compressor closet. Did you use an exterior (insulated) door?
Ron Yerke You could definitely do that. I wanted a 100% leak proof system and my experience with clamping new fittings on the hose is that they start to leak over time. The closet door is just a standard raised panel interior door, hollow core. Thanks for the comment!
zimsjeep Yeah, it's no fun when your hoses leak. Perhaps a different kind of clamp would be good to try. I thought that was a hollow core door by the amount of sound coming through it, but had to ask. My younger brother has doors like those in his house. He has a matching insulated door to his garage that's pretty good at blocking sound. I know they're higher priced than hollow core, but if anyone spends significant amounts of time in the next room (or wants to), you might want to think about an upgrade. I've even heard of people stapling or gluing things like carpet squares or moving blankets to the inside of the doors to their compressor boxes. Whatever keeps her happy, right? I like your setup pretty well as is, don't get me wrong. Keep on keepin' on. :-)
Can you show how you are wired from the receptacle to black control box on the compressor? I just bought a DeWalt 60 gallon myself. I already have 30 Amp NEMA 5-50P outlet in the garage.
Great vid! Very nice install! Thanks for sharing! I'm installing a 60 gal. 2 stage Kobalt (Lowes/Campbell Hausfeld) outside my 2 car garage in a shed. Do you think you would put a filter down low at the compressor on hose before the run you made with the maxline? Mine will be all level ground but thinking on a filter low in the shed before entering the garage. Gravity is a cheap commodity.... Thoughts?
What wire did you use from the compressor itself to the twist lock plug? I just got one of these compressors and was curious what others have used. Thanks!
Great setup and clear instructions and explanations. I am thinking of getting a 60 gallon compressor for my garage for automotive work. Which drier regulator do you recommend?
youratlanteon friend Yes, that's important to do. I did a little research into the auto drain valves and might invest in one of them soon. Thanks for the comment
Gotta ask. . . Since you don't appear to have anything permanently connected to air (like a blast cabinet) and it looks like you already have a hose reel that you mention plugging into the last outlet in the air line. . . why didn't you just mount your hose reel on the wall near the filter/dryer/regulator, run pipe semi-permanently to that, and then use the hose reel for whatever it is that you use air for - instead of running all that tubing all the way up and around the garage? I'm just curious. I mean, if I didn't have a blast cabinet, I'd just mount my hose reel right next to the compressor and pull hose out when I need to inflate tires, run my impact wrench, use a cutoff tool, etc. Especially in a one-car garage, it seems like that would have been a lot easier.
Jerry C I was planning for future use. I’ve reconfigured my garage to now have a bench on this wall (you can actually see this in my drawer slide video). I now extended this drop to the back wall so I have air on my rear wall bench and have a coil line permanently connected here. I just prefer this convenience wise to have a short hose on my tool ready for use rather then running line from the spool. You’re right, could have done it either way. Just my preference and it made for a good video. Thanks for the comment.
@@fixitwithzim Ah. That makes sense. I'm currently designing my airlines so I have a conveniently located outlet for paint guns (i.e. pre-oiler), my hose reel (for car work - inflators, impact, etc.), and 2-3 bench outlets for . . . whatever I end up doing at the bench. But, I think I do like the idea of running a hard line across the garage so I have an outlet for a short hose on that end. You've got me thinking! Nice job on the tubing, btw - I just had to ask why you did that.
Before blindly following mounting "advice" check the installation instructions for your unit. For example Quincy explicitly forbids any isolators with its QP-series vertical compressors.
They are not all the same. That compressor is a single stage.Where was the compressor and electric motor Manufactured (What nation) ? I would go with a 2 stage shorter cycle times and higher pressure,total different animal than a single stage.
THAT THING GONNA GET HOT AS HELL IN THAT CLOSET! GETS MORE WATER IN THE LINE, AND WILL SHORTEN LIFE OF AIR COMP. you could add a fan to cool it maybe, but that does keep sound down in the closet.
Actually it’s been great in that closet and hasn’t gotten hot...going on 3 years now. The closet also isn’t closed off fully. Watch the whole video. Thanks for the comment.
How many amps will determine what size breaker to use. 17 amps 20 amp breaker on 12/2 Rolex Over 20 amps 30 amp breaker with 10/2 Rolex You could also use mc and not use the pipe. 20 Percent only applies to something that can run continuously for three hours or more that compressor will not run continuously for three hours or more.
Rapid air is a type of pex called Pex-Al-Pex Its pex then a aluminum pipe inside then a thin pex layer inside the Aluminum pipe to keep the aluminum pipe from corroding. one benefit is The aluminum allows it to keep its shape when bent.
Charles Graham yeah, things kept coming to mind that I thought might be useful for everyone. Better then reshooting the whole thing and forgetting something else
Wrong pipe S/B copper, kits are crap ,wrong place to put it..SCFM MEANS BS WHAT IS THE CFM? it’s about cfm and volume. You are building in problems with this install.
amzn.to/2kHbeen DeWalt 60 Gallon Air Compressor
amzn.to/3HKDsgb Air Filter Regulator Combo 3/4" NPT
amzn.to/2kH0TiM TEKTON 1/2-Inch I.D. by 3-Foot Lead-In Air Hose
amzn.to/2kH1Wil Maxline M7500 Master Kit, 3/4-Inch x 100-Feet
amzn.to/2kWjndC ¾” Elbow for Maxline Kit
amzn.to/2kkyICP Anti Vibration Pads - Set of 4
amzn.to/3FTboXe 30 Amp, 240 Volt Disconnect
amzn.to/3eJNEJ7 Brady Label Maker
As a retired machinist I will say that you did a professional job. You obviously planned out the project and it shows. The lines looked plumb and level. The hose mounting clips all looked at the same level and spaced evenly. And the hose itself is pulled straight, not drooping like Xmas tree lights. Also, I have the exact same moisture/filter and regulator (SAF and SAR 4000?). The SAF performance is just ok so I added a Motor Guard M60 filter to trap additional moisture. Thanks for the video.
i have a large shed in the backyard and didn't really know what to use a air line system,thanks to you and this install i will be getting a rapid air.
I used a 3/4” clear hose with a cross hatch material inside. My 80 gallon compressor goes to 175 pounds I had that on there 5 years no problem
I set up my garage in similar fashion, however I used copper pipe and sweated necessary fittings. I have a sand blast cabinet along with tools throughout the garage. Been running it for 2 years. With no leaks or issues.
Nice, sounds like a great setup!
Thank you for the time you put into this. I am starting my piping today. At the bottom of the vertical runs, and at the distribution blocks, I will install a 12 inch or longer pipe down to the drain valve to have a reservoir to collect the water so the air doesn't have to bubble through it between drainings. Maybe useful, maybe overkill, just me. I also plan to take off the top of the horizontal runs using a T for my feed lines. My thinking is this will reduce the amount of moisture to the point of use. Your time and effort in this saved me a great deal of time and research. It is easier to build on an existing project than to start from scratch. Thanks again for taking the time to produce this video.
I though about doing this in type "M" copper. It's cheaper than "L" & faster than black. You've got an awesome setup, there. Thanks for the tip on using that hose as a buffer for neutralizing vibration.
This is a great replacement for my old regulator/oiler that started leaking It came with brass nipples that saved me a trip to the hardware store and even came with teflon tape.
The level of organization is excellent! About to tackle my system, and this helps out tremendously. Thank You
Very good....
Thanks for the information and recommendations. Just had an electrician hardwire my DeWalt today and I’ll be ordering this kit in a few.
I’m not much into the tech world but I love UA-cam!
Thanks again!
Great video. Gives me a lot of idea.
Questions:
This video is 6 years old. Have you attached an air dryer/cooler addition to your setup?
Where do you drain out the tank condensation to in the closet?
thanks.
Excellent video! I just got a Dewalt Compressor, and had many questions, which you answered.
You’re welcome! Enjoy your new toy!!
Hockey pucks work well as vibration dampers too if you have any on hand.
Thanks for the comment
Well spoken, informative yet concise....fantastic video! Definitely like the attention to detail and clean install!
Thank you for publishing this video, well done answered all my questions.
Looks like a very well thought out and executed setup. Simular to what I'm envisioning for my shop, except with the use of PEX and normal fittings instead of the Max Air kit. I have my compressor in a lean to along the side my 30x30 building. I will be running 3 drops along each side of the building and one down the center support column to a reel, making the system an H shape when looking from the front of the shop.
Sounds like a good plan. Good luck with the job and thanks for taking the time to comment.
zimsjeep
Got it all in and setup, works great, thank you.
Great information from a normal guy with an exceptional mind. Kudo to you sire.
Please read.. the electric motor on ours cought fire in a well ventilated room. It was a husky brand with the same electric motor as yours. Ours wasn't the only one. It was about 4 years old.
Interesting, does the manufacturer have a recall out on the motor? What brand is the motor on yours?
Dang hows he gona say somthing like that, then leave us all hanging? I'd like to know what brand motor catches on fire lol. Ofcourse it's on a husky thou, I seen one of there ratcheting end wrenches catch on fire one time...to much torque I guess🤷♂️.
Condensate forms in the piping. As such, you do not want it plumb to the ceiling, you want it pitched away from the compressor 2" per 25' of run. Your blue piping is already flexible. It you used a valve with a pex barb at the compressor you could have connected directly without the whip.
Very nice set up you have there
Thanks you!
so even though you have breaker on that outlet, that you can shut off, you still stand a chance of getting water in that outlet if you have to open up your waste line and snake it from a clog.
Drop Tine True, I keep the disconnect in the off position whenever I'm not using the compressor so chances are it will be deenergized...but good point none the less. Thanks for the comment.
Awesome set up 👍
Great video! Just got the newest version of this compressor from Tractor Supply. What is the cut on/off pressure on the compressor? I noticed it has a bung at the front that is blocked off, is that where you can take control of when it cuts on and off?
Double pole 20 amp is 40 amp overall you should run intake through wall to outside, I did really quiets down and you get fresh air., I did a 25 foot of 1/2 inch copper tubing between compressor head and tank with air separator just before tank will drop your air temperature and reduce moisture in tank.l hardly ever get any water after doing it
i mounted my compressor on hockey pucks, worked well and was cheap
Good idea!!
Most recommend having an 18" clearance away from the wall for air flow. Do you find having it in such a closed - in space a problem with air flow for the motor?
Bobby Prewett no problems at all. It’s been working great and doesn’t get too hot. I’ve been running it in this location for a little over a year
Without looking it up Id guess it needs 1000 cu ft of air space..
Nice overview Zim. Thanks.
Had 2 of those from lows..china built..runs vary loudly..,change the oil every 2-3 hundred hrs..I hope your room is vented ..nice set up..I went American made..no more China crap..have a Saylor-beall..made in st.johns ,Michigan..All American American iron..Baldor motor..mine runs on a 30 amp.220 v..and runs vary quit..my 3 hp. Unit is a 2 stage pump..spent 3 grand ..I would put a fan in your closet..again love your set up..I'm now retired..I'm in fl. So for heat issues my unit has an after -cooler built on my unit with a fan..built on the motor..check out utube video on Saylor-beall..fully pkg unit ..ul see how they build there. Comprsoir s...u can do a set up on yours simply..add on to yours ..
I had always heard to NEVER use pex for air lines. They always leak at the push fittings....and if it doesn't now, it will. I was debating doing 3/4 copper pipe
I've used pex and sharkbite fittings for years, never had a problem. Just make sure you gauge all you fitting.
very nice and well organized great job!!!
Thanks for this, a thorough overview and exactly what I was looking for. That said, I think you used 30a fuses in the disconnect, may I ask why? You already have a 30a breaker on this circuit, so is this redundancy needed? Or am I missing something? Thanks again.
The disconnect I used requires cartridge fuses in order to work...completely not needed but it was the only disconnect I could find at the time. The breaker alone is more then sufficient. Hope this helps.
@@fixitwithzim Not sure, but I think the panel breakers are not designed to be used as "switches". Just resets when tripped. The disconnect is a switch.
Nice work!! Only "bad" thing is, this red soft hose, next to tank, will fill up with water. You may cut it a little..
Riku Koivisto I actually haven’t had any moisture accumulate in the hose. Good observation though
Thanks for this! Fantastic video and gave me some ideas!
When you first installed your Air compressor, did you leave it open to the atmosphere and run it for 30min-1hour to break in the motor? I'm looking to install mine and I've seen a few videos recommending it.
I didn’t do that. Still have the same system in place for at least 5-6 years now…no issues and everything working great
Great video and awesome install!!!!
You must be a process engineer/ process technician. Your terminology gives it away haha
Black pipe would rust. You did it right this way
Putting the twist lock also makes it code complaint.the 20 percent rule is to keep the wires from over heating it definitely should be 10 gauge and if it’s more then 75 feet should be 8 gauge .
Thanks for sharing! Very informative! Well done! 👌👍
Very good video
Hi more power to your channel ,I got a question I have a 50 ampere service in my garage and it’s 220volts can I use my dewalt air compressor same as what you have?do you think it’s possible?thanks any comments is greatly appreciated.
Yes, should work fine. That’s what I have in the video. Just make sure all the breakers and wiring is sized correctly
Great vid man but one question, in your finished basement, how do you drain off the compressor tank itself without staining the floors with the brown oily condensate that comes out of the main tank? A lot of water builds up in them no matter what if you don't have a pre-cooler and trap before the tank in but after the pump.. I use a car transmission radiator and gravity trap below the tank drain so had to mount the tann on a big block pad..
Gotta drain off those tanks at least once a month otherwise that closets gonna turn into a window to the garage..
I put an old 5 quart oil container that I cut the side off of under the tank and bleed it. The container traps the rusty water. Thanks for the comment
Thanks, I’m about to do something like this,,,,,,,yours looks GREAT.....
Thanks very much for taking the time and trouble to lead the way. I just bought my 60 gal. tonight and your video has a ton of great tips tricks and important things to think about. Especially glad you're a "code" guy like me.
NMranchhand You're welcome. Good luck with your install!
NMranchhand M. L
You need already 3/4 inch line leaving tank you have really cut down your volume, with the 60 gallon 155 I found it best to reduce pressure setting to 135 to prolong life of compressor they struggle the last 15 psi to shut down and you will never need 155 psi,, l went from 7 to 5 minutes to fill tank from empty. Will give you year's longer
Thanks, I’ll look into making the change
It's been around 3 yrs since you post your video- question, has the rapid air system held up to your expectations? Also I think you did a great job installing. I too would put a shut off valve where you said you should..thanks for sharing!
Thanks! Yes, no complaints on the rapid air system. Still working great and no leaks. I wouldn’t hesitate installing it again if I needed too.
@@fixitwithzim thanks so much for replying! I'm purchasing tomorrow!!
THANK YOU...for sharing. Watched and very much enjoyed.
I have the same compressor . What kind of plug should I ask for when going to the hardware store ?
i thought i heard you say that you ran romex through the conduit? that would be a bad idea for several reasons including being a code violation but more importantly its a fire hazard. the sheathed wire (romex) is not rated for use in conduit ; at the very least the sheathing should be removed from the conductors to avoid excess heat buidlup inside the conduit. Not trying to be negative at all, just a headsup in case you actually did run romex inside that conduit don't want your house to catch fire and do want you and your family to stay safe.
Nice neat install
Don Alexander thanks for the comment. You’re partially incorrect regarding Romex in conduit. NEC 300.4 actually calls for protecting conductors and cable where physical damage might occur. I believe it goes on further to say NM cable sleeving is recommend in areas subject to these conditions. You can take that interpretation anyway you’d like. In my case, I believe I used 1 1/4 conduit to sleeve the NM cable. In my opinion, there is no chance for harm here, especially with both ends of the conduit open and not sealed and the cable having plenty of “breathing room” in an oversized pipe.
@@fixitwithzim Your PVC (or CPVC - or whatever you're using) isn't sufficient. Period. The code is really only worried about physical damage from nails or screws... Here's a DIRECT quote from NEC 300.4:
the cable or raceway shall be protected from penetration by nails or screws by a steel plate, sleeve, or equivalent at least 1.6 mm (1⁄16 in.) thick.
For the safety of your family, protect those wires. Please. Are you likely to cut into them? NOOO!!! Could it "maybe" happen? YEP! That's the reason for codes.
ddotodd11 thank for your concerns, yes understand what your saying but there is zero chance of someone screwing into that conduit (8 inch poured concrete foundation wall on one side and the opposite side is open in free space, not hidden where a nail or screw puncture would be possible). But yes, in a concealed space, emt would be in order and the better choice
Was the price of a long 3/4 hose more han the whip? Just cut and add a new end if not. Leftover hose gets an end too, does it matter if it's 12 inches shorter? Nice compressor closet. Did you use an exterior (insulated) door?
Ron Yerke You could definitely do that. I wanted a 100% leak proof system and my experience with clamping new fittings on the hose is that they start to leak over time. The closet door is just a standard raised panel interior door, hollow core. Thanks for the comment!
zimsjeep Yeah, it's no fun when your hoses leak. Perhaps a different kind of clamp would be good to try. I thought that was a hollow core door by the amount of sound coming through it, but had to ask. My younger brother has doors like those in his house. He has a matching insulated door to his garage that's pretty good at blocking sound. I know they're higher priced than hollow core, but if anyone spends significant amounts of time in the next room (or wants to), you might want to think about an upgrade. I've even heard of people stapling or gluing things like carpet squares or moving blankets to the inside of the doors to their compressor boxes. Whatever keeps her happy, right? I like your setup pretty well as is, don't get me wrong. Keep on keepin' on. :-)
Who installed the 220 outlet directly under the sewage trap line? Perhaps not an ideal location?
All good and works great! Thanks for the comment!
I used copper pipe worked out good 👍
Nice, I was thinking about going that route initially as well. Glad it worked for you 👍🏻
Can you show how you are wired from the receptacle to black control box on the compressor? I just bought a DeWalt 60 gallon myself. I already have 30 Amp NEMA 5-50P outlet in the garage.
CRM6718 Did you figure out how to do this, sorry for the late reply. Been busy
@@fixitwithzim Hi, yes I figured it out. Now, I need hoses and filter etc setup...any thoughts on brand and where I can buy it?
CRM6718 Yes, in the video description is links to all the items I used. I haven’t had any problems and everything has been working great
They are Campbell hausfeld compressors, accept the central brand
Great vid! Very nice install! Thanks for sharing!
I'm installing a 60 gal. 2 stage Kobalt (Lowes/Campbell Hausfeld) outside my 2 car garage in a shed. Do you think you would put a filter down low at the compressor on hose before the run you made with the maxline? Mine will be all level ground but thinking on a filter low in the shed before entering the garage. Gravity is a cheap commodity.... Thoughts?
What wire did you use from the compressor itself to the twist lock plug? I just got one of these compressors and was curious what others have used. Thanks!
Philip Rudd 10 gauge, 3 conductor SJ cord
Would it be okay to use pvc instead people have told me its okay
My concern with pvc is it can shatter very easily in a shop environment. Not the best idea.
New subscriber great video will definately give it a gi. Thanks for sharing Artie👍👍👍
just what i needed do install my tank!
Great, glad I could help
Great setup and clear instructions and explanations. I am thinking of getting a 60 gallon compressor for my garage for automotive work. Which drier regulator do you recommend?
racerxnk Thanks!... Link is in the description for the one I recommend and use.
Looks like -except tubing?
Great video thank you sir!
The Moto fixery Thank you!
what kind of pipework do you usally use for a compressed air intallation
Morgan Mackay Usually black pipe but found this kit pretty handy and easy to install. Over a year later and still no leaks and holding strong!
I would try to remember to go down every once and a while and drain it
youratlanteon friend Yes, that's important to do. I did a little research into the auto drain valves and might invest in one of them soon. Thanks for the comment
Very nice setup. What device did you use to make your labels?
Thanks...I have a link to it in the description. Brady label maker. Nice unit, prints 3/4 labels
Gotta ask. . . Since you don't appear to have anything permanently connected to air (like a blast cabinet) and it looks like you already have a hose reel that you mention plugging into the last outlet in the air line. . . why didn't you just mount your hose reel on the wall near the filter/dryer/regulator, run pipe semi-permanently to that, and then use the hose reel for whatever it is that you use air for - instead of running all that tubing all the way up and around the garage? I'm just curious. I mean, if I didn't have a blast cabinet, I'd just mount my hose reel right next to the compressor and pull hose out when I need to inflate tires, run my impact wrench, use a cutoff tool, etc. Especially in a one-car garage, it seems like that would have been a lot easier.
Jerry C I was planning for future use. I’ve reconfigured my garage to now have a bench on this wall (you can actually see this in my drawer slide video). I now extended this drop to the back wall so I have air on my rear wall bench and have a coil line permanently connected here. I just prefer this convenience wise to have a short hose on my tool ready for use rather then running line from the spool. You’re right, could have done it either way. Just my preference and it made for a good video. Thanks for the comment.
@@fixitwithzim Ah. That makes sense. I'm currently designing my airlines so I have a conveniently located outlet for paint guns (i.e. pre-oiler), my hose reel (for car work - inflators, impact, etc.), and 2-3 bench outlets for . . . whatever I end up doing at the bench. But, I think I do like the idea of running a hard line across the garage so I have an outlet for a short hose on that end. You've got me thinking! Nice job on the tubing, btw - I just had to ask why you did that.
I bought my 3/4" whip at Northern tool for $40
Michael Bortz
Thanks for info!
Before blindly following mounting "advice" check the installation instructions for your unit. For example Quincy explicitly forbids any isolators with its QP-series vertical compressors.
Curious as to why that is?
@@fixitwithzim no idea but it is undoubtedly a very good idea to follow manufacturer instructions.
They are not all the same. That compressor is a single stage.Where was the compressor and electric motor Manufactured (What nation) ? I would go with a 2 stage shorter cycle times and higher pressure,total different animal than a single stage.
muddyriverdogz Nahh, this one works great for what I do. Thanks for the comment
THAT THING GONNA GET HOT AS HELL IN THAT CLOSET! GETS MORE WATER IN THE LINE, AND WILL SHORTEN LIFE OF AIR COMP. you could add a fan to cool it maybe, but that does keep sound down in the closet.
Actually it’s been great in that closet and hasn’t gotten hot...going on 3 years now. The closet also isn’t closed off fully. Watch the whole video. Thanks for the comment.
How many amps will determine what size breaker to use.
17 amps 20 amp breaker on 12/2 Rolex
Over 20 amps 30 amp breaker with 10/2 Rolex
You could also use mc and not use the pipe.
20 Percent only applies to something that can run continuously for three hours or more that compressor will not run continuously for three hours or more.
denoise compressor
No, not noisy at all inside the closet
enformacion en Español Conprensora de 80 galones
Get Hydraulic hose at tractor supply 18 dollars for 4 foot 3500 psi hose
This is just to help other you can also do pvc pipe like 3/4 or 1/2 it is the best setup I have fond
COMPRESSOR KOBALT 60 GALLON IS GOOD ????.
Yes, its essentially the same as this one. Its a good unit, my buddy has had one for a few years.
Hi
I'm perfectly willing to admit that I might not be 100 percent correct 😎
My main concern was that you were aware that there could be a safety issue and it looks like you have done your homework
...100 dB "suffer the children" terror
Looks like Pex tubing ( stupid auto correct)
Rapid air is a type of pex called Pex-Al-Pex Its pex then a aluminum pipe inside then a thin pex layer inside the Aluminum pipe to keep the aluminum pipe from corroding. one benefit is The aluminum allows it to keep its shape when bent.
You can use pex instead. the only benefit of the al layer is that it can handle direct sunlight without breaking down.
guys has alot of side notes.. lol
Charles Graham yeah, things kept coming to mind that I thought might be useful for everyone. Better then reshooting the whole thing and forgetting something else
Wrong pipe S/B copper, kits are crap ,wrong place to put it..SCFM MEANS BS WHAT IS THE CFM? it’s about cfm and volume. You are building in problems with this install.
You know shit is getting cheap when they use aluminum tube instead of copper
ImpartialTuber yup, unfortunately nothing is made the way it use to be anymore
Poor wife
She loves it!
Code violation. Disconnect must be within line of sight of the motor. You failed sir.
There’s a switch on the compressor. No need for a disconnect on this. Go back to school