Busbar sizing

Поділитися
Вставка
  • Опубліковано 11 лип 2024
  • This video outlines the basic formulas used to size electrical busbars on the distribution / transmission network and is a sample of the ELECTRICAL CONTROL AND PROTECTION PART 3 course which can be found on UDEMY, use the following link to access the course..
    www.udemy.com/course/electric...
    If you need a $10 discount voucher please drop me a message!!
  • Наука та технологія

КОМЕНТАРІ • 127

  • @jav1494
    @jav1494 Рік тому +4

    Absolute Legend! Completed the Electrical Generation on Construction Sites during lockdown and it was full of so much information. Thanks for everything !

  • @zeeshanhaider4428
    @zeeshanhaider4428 2 роки тому +1

    A sound lecture with simplified examples. Great work

  • @kennethchiebuka5168
    @kennethchiebuka5168 10 місяців тому

    Wow!! You are indeed a legend in the power sector and a great teacher too.

    • @Electricalsteve
      @Electricalsteve  10 місяців тому

      Thanks for the kind words Kenneth, glad you found the course useful!! Steve

  • @angelofranklin1
    @angelofranklin1 2 роки тому

    Very good video Steve

  • @sathishsathiyamoorthi1330
    @sathishsathiyamoorthi1330 4 роки тому

    A very good and detailed video. Thank you sir

  • @scorpionmad3299
    @scorpionmad3299 5 років тому +1

    Thanks alot , It was very useful 👌😍👍

  • @AP-pg6uf
    @AP-pg6uf 2 роки тому

    Thanks, Greate lecture with simplified examples

  • @jayschumacher815
    @jayschumacher815 4 роки тому

    Great info, thanks for posting

  • @erisherm.385
    @erisherm.385 3 роки тому

    Thank you very much. I have learnt something very useful.

  • @vincentmasanja6979
    @vincentmasanja6979 2 роки тому

    Thanks for your teaching.

  • @akramal-frigy1143
    @akramal-frigy1143 5 років тому

    Many thanks for you. Very good video

    • @Electricalsteve
      @Electricalsteve  3 роки тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @ashutoshsawant7013
    @ashutoshsawant7013 2 роки тому

    Very well explained. Thank you Sir.

  • @kingsleychinyani6676
    @kingsleychinyani6676 3 роки тому

    Useful information. Thanks a lot.

  • @Shivkumar-qp9wv
    @Shivkumar-qp9wv 5 років тому

    Sir good knowledge

  • @engalaamenshawy5377
    @engalaamenshawy5377 2 місяці тому

    wow!! very very nice not teacher but you are doctor congratulation.

  • @sambathbunkh
    @sambathbunkh 9 місяців тому

    Great topic

  • @DeepakKumar-zm6sy
    @DeepakKumar-zm6sy 4 роки тому

    Thank you sir..This video is very helpful

    • @Electricalsteve
      @Electricalsteve  3 роки тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @arnovpachani2385
    @arnovpachani2385 4 роки тому +1

    a valuable information
    thank you

  • @lipikashaha2001
    @lipikashaha2001 3 роки тому

    Thanks for Helpful calculation -
    Sir

  • @rkprasadbhookya1878
    @rkprasadbhookya1878 6 місяців тому

    Superb trick

  • @hpvide
    @hpvide Місяць тому

    Wow 😳.. thank you so much

  • @umamahesh1350
    @umamahesh1350 4 роки тому

    Nice explanation sir.

  • @sethu7867
    @sethu7867 3 роки тому

    very good information

  • @PramodKumar-zl4gq
    @PramodKumar-zl4gq 2 роки тому

    Nice explanation

  • @full7184
    @full7184 2 роки тому

    thanks lot , nice video.

  • @akramal-frigy1143
    @akramal-frigy1143 4 роки тому

    many many thanks .....

  • @WarwickChapman
    @WarwickChapman 9 місяців тому

    Does the course cover DC busbar sizing?

  • @alwaga7917
    @alwaga7917 5 років тому

    why is conected shunt reactor on bus bar 400kv thank you

  • @user-es7ib5gq4s
    @user-es7ib5gq4s 3 роки тому +1

    Thanks alot for explaining i think we should raise the rating of bus bar over the selection value to carry the mechanical stress of cables

    • @Electricalsteve
      @Electricalsteve  3 роки тому

      The cable rating will depend on the load being carried under all conditions and the two are not normally linked.

  • @forsanh.a.hassan2677
    @forsanh.a.hassan2677 4 роки тому

    Thanks a lot

  • @navassharif7228
    @navassharif7228 5 років тому

    Hi sir
    It was very useful.we want more video for sizing each Electrical switch gears pls.thanks

    • @Electricalsteve
      @Electricalsteve  5 років тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WETT1001 to get them for $9.99
      Regards
      Stephen Brooks

    • @delosmark18
      @delosmark18 4 роки тому

      @@Electricalsteve what topic in the udemy website sir which includes equipmemt sizing? Thanks im interested.

  • @edherrevideos
    @edherrevideos 5 років тому

    like y suscrito...Thanks...

  • @satishkumar-wm9yl
    @satishkumar-wm9yl 2 роки тому

    please can you explain the choosing the CT, PT, Breaker size for outgoing and Incoming line
    for newly construction line from the existing feeder , thanks sir such a good explanation it has uses a lot for all

  • @efrenebora1430
    @efrenebora1430 4 роки тому +1

    Hi there sir. I would like to ask if I can use the same computation? Say, I need to determine the HV panel outgoing protection to a load 630Kva, 33/0.4Kv Transformer. Hope you could help me. Thanks.

    • @Electricalsteve
      @Electricalsteve  4 роки тому

      Hi Efren, the calculation is valid for all voltages. steve

  • @satishkumar-wm9yl
    @satishkumar-wm9yl 2 роки тому +1

    keep uploading the good concepts for selection of CT , PT , Breaker, cable sizing for Newly construction substation

  • @chired6851
    @chired6851 2 роки тому

    Thanks for that Stephen - in the first example with 1 incomer, the full load current of the secondary side of the transformer is 1050A, could I design the switchgear with a busbar rating of 1000A and an incomer breaker rating of 1000A (maximum peak load including future spare is 900A) . I have done similar on a project which I consider to be a sound design. I think it is fit for purpose but does it break any IEC codes do you know?

    • @Electricalsteve
      @Electricalsteve  2 роки тому +1

      Hi Chi,
      In the UK we would always choose the rating above the transformer rated output , so 1250A in your case. The loads change over time so it’s not the best way to size the busbar.
      Regards
      steve

    • @chired6851
      @chired6851 2 роки тому

      @@Electricalsteve Thanks very much Steve

  • @relaxer7329
    @relaxer7329 5 років тому +5

    hey is there any scientific paper support your information like IEEE standard

    • @delosmark18
      @delosmark18 4 роки тому

      I agree, it is better that the topic is supported by a standard

  • @12345678sharad
    @12345678sharad 4 роки тому

    I am buying your course, please if you can put up a course on transmission line protection, and relay settings for that, thanks a lot

    • @Electricalsteve
      @Electricalsteve  4 роки тому

      Hi Sharad, working on the transmission line protection course now...steve

  • @mohammedrahimuddin268
    @mohammedrahimuddin268 4 роки тому

    Very informative video. Thank you

  • @arafatbaunto4068
    @arafatbaunto4068 3 роки тому

    Nice

  • @thesilentgamer4210
    @thesilentgamer4210 7 місяців тому

    sir, do you know how to size cable for transformer neutral earthing? my transformer is delta y. 3MVA 33KV / 415 V.. I hope you can help me sir

  • @KevinCoop1
    @KevinCoop1 4 роки тому

    This is great if the customer owns all the equipment or is the utility company. If the transformers are utility company owned and the equipment is customer owned, we have to decide how to size the bus bar in the gear based on electrical loads attached. Utility companies can change their transformers as they see fit.

    • @Electricalsteve
      @Electricalsteve  4 роки тому

      Hi Kevin,
      Agreed, if you are trying to conserve money we can base the bus bar on the connected loads, but make sure you future proof the design by adding lots of spare busbar capacity as upgrading the busbar size later when new feeders are added can be very painful in terms of outages and cost....
      steve

    • @KevinCoop1
      @KevinCoop1 4 роки тому

      stephen brooks Over the years doing electrical designs for all kinds of businesses, I have checked back with my customers and gotten a printout of their utility bills for a year minimum. The bus was sized using NEC calculations. Every time the results were very similar. A 3000 ampere rated service equipment would have maximum recorded 900 to 1100 amperes. Utility companies typically took our load information and multiplied it by .5. Respectfully, Kevin

  • @zedikasElectro
    @zedikasElectro 4 роки тому

    nice explanation ... i gate good thing from ur tutor .thanks and keep going with other related components

  • @birendrakumarpati5460
    @birendrakumarpati5460 3 роки тому

    Thanks sir

  • @enriqueh8847
    @enriqueh8847 4 роки тому

    Thanks. I have some questions, could you explain how to calculate or do the sizing for bus-bar at MV side of power transformer HV 220kV/20kV, 12%, 125MVA, YNd11, ONAN/ONAF? where at PCC of transmission, it is 40kA at 220kV (HV side) which is the short circuit current value considered as designing at this high level voltage (220kV) (according to transmission operation) and in addition, the company of transmission gives us a value of 15kA(maximum demand of load) the maximum three phase short circuit current at the same point PCC (High voltage side).. So the second question, according to IEC standard or experience for designing MV switchgear at 20KV, what short circuit current value will it have to be used 40kA or 15kA (PCC connexion, 220kV) for sizing my MV switchgear, Ik and Ip (withstand simetrical and peak short-circuit current?

    • @Electricalsteve
      @Electricalsteve  4 роки тому +1

      Hi Ki,
      This video is a sample only, please take the course for full guidance on this and many other substation design issues.
      Regards
      steve

    • @enriqueh8847
      @enriqueh8847 4 роки тому

      @@Electricalsteve okay, thank you.

  • @wadib3eed7
    @wadib3eed7 3 роки тому

    I have a question. Some peoples in youtube says for copper 1 sq mm = 1.4 Amps and for Al 1 sq mm = 0.8 Amps . Is it correct or not ? and how to calculate the current density for busbar if i want carrying current of 200 Amp as an example.

    • @Electricalsteve
      @Electricalsteve  3 роки тому

      Hi Wadi, this video covers busbars, not conductors. steve

  • @u-canlearn7967
    @u-canlearn7967 4 роки тому

    Very helpful ....Thank you Sir.
    Please keep uploading more videos related to Electrical engineering.....can you help with transformer sizing as well.

  • @vanlahm4728
    @vanlahm4728 9 місяців тому

    Hi Sir. Just a quick question. The busbar rating for the current is multiplied by 3. But why is the voltage not mulplied by 3 also?

    • @Electricalsteve
      @Electricalsteve  9 місяців тому

      Hi,
      The system voltage is kept constant regardless of the power output of the transformers or the size of the loads.
      If the voltage is constant then the only thing that can change as the power magnitude changes is the current and it does, when the power drawn by the load increases the current increases.
      Regards
      Steve

  • @delosmark18
    @delosmark18 4 роки тому

    Hi sir, what topic in udemy the sizing of equipment? I would like to buy thanks

    • @Electricalsteve
      @Electricalsteve  4 роки тому

      Hi Mike,
      This is a module on the air insulated design course hosted by udemy.
      Steve

    • @delosmark18
      @delosmark18 4 роки тому

      @@Electricalsteve hi sir, i have trouble in buying your videos. Paypal, cc or debit card cant be link to udemy :(

  • @AP-pg6uf
    @AP-pg6uf 2 роки тому

    Hi Please can you send a for ELECTRICAL CONTROL AND PROTECTION PART 3

    • @Electricalsteve
      @Electricalsteve  2 роки тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @surendrakverma555
    @surendrakverma555 3 роки тому

    Good

  • @tuna6423
    @tuna6423 2 роки тому

    Generally, bus coupler breaker will be normally open. One transformer A will feed to bus A and trf B will feed to bus B. However, there will be some case that if one of transformer not available another will take all the load of bus A and B in this case bus coupler breaker will be closed it means that both trafo A & B shall be sized based on load on bus A plus load on bus B it means that bus coupler breaker just size as per transformer rating it is not required to unnecessary size double time of trafo rating this is the same thing of bus bar rating also
    Please check your presentation sir

    • @Electricalsteve
      @Electricalsteve  2 роки тому

      Hi PP,
      This is a very simple example and most transmission level substations will have multiple incomers, transformers and busbars.
      The decision on the bus section breaker rating will be decided by the designers to provide the best operational flexibility & cost effectiveness for the system.
      Regards
      Steve

  • @ahilcuts7971
    @ahilcuts7971 5 років тому

    Hi sir .. you said incomer 1 (800A) Incomer 2(800A) future (800A) ..and you going to choose 2500A busbar .if I saw in my switchgear diagram all incomer and buscoupler are same rating .. for example 2500A busbar we choosing Incomer and buscoupler 2500A breaker .. but current rating just 680A for both Incomer why?????

    • @Electricalsteve
      @Electricalsteve  5 років тому +1

      Hi Ahilan,
      You didn’t mention the system voltage but the utility may be future proofing the substation by having the highest rated circuit breakers possible.
      You will also find that the cost difference between 800/1250/2500 circuit breakers can be small for large equipment orders so it makes sense to go for the highest circuit breaker rating , this also reduces the need for different circuit breaker spares and allows the circuit breakers to be interchanged easily when one goes faulty.
      Steve

    • @ahilcuts7971
      @ahilcuts7971 5 років тому

      @@Electricalsteve 415v

  • @shelfrobthomas449
    @shelfrobthomas449 4 роки тому

    The busbar sizing is as per IEC standard, because IEEE have only 1200, 2000, 3000A.

    • @Electricalsteve
      @Electricalsteve  4 роки тому

      Hi Shelfrob, any mention of standards has deliberately been omitted, the focus is on the methodology..steve

  • @pavintechengineeringpavint1389
    @pavintechengineeringpavint1389 2 роки тому

    How it possible request ur advice

    • @Electricalsteve
      @Electricalsteve  2 роки тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @shanu5089
    @shanu5089 2 роки тому

    Sir how to drow single line diagram like this video

    • @Electricalsteve
      @Electricalsteve  2 роки тому +1

      Hi Dill,
      PowerPoint / Autocad are both ideal.
      steve

  • @souadmassi7683
    @souadmassi7683 4 роки тому

    Why in the equation of the power the power factor cos phi did not appear?

    • @Electricalsteve
      @Electricalsteve  4 роки тому +1

      Hi Souad, because we are using the VA equation which does not contact power factor steve

    • @souadmassi7683
      @souadmassi7683 4 роки тому

      @@Electricalsteve Thank you sir

    • @Electricalsteve
      @Electricalsteve  4 роки тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @engineershihas
    @engineershihas 4 роки тому

    Is it possible to get 50kA for 630A busbars.

  • @AhmedAli-zb3oh
    @AhmedAli-zb3oh Рік тому

    @stephen brooks
    Dear Stephen
    I want to get a discount voucher for all your protection courses, please

    • @Electricalsteve
      @Electricalsteve  Рік тому +1

      Hi Ahmed,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @americarsqueensland1667
    @americarsqueensland1667 3 роки тому

    if you had say a 500 amp max load could you use a much higher rated busbar of say 2000 amp, i don't see why you need to have the busbar rating stay near the load value, seems to me you should or could just a much bigger bubar and you wont ever have a problem.

    • @Electricalsteve
      @Electricalsteve  3 роки тому

      Hi, that’s correct. You don’t size the busbar based on the load, as loads can change over time. You size it based on the maximum amount of power available to flow into the substation steve

  • @randhasan
    @randhasan 2 роки тому

    Hi Stephen can you please send me voucher discount

    • @Electricalsteve
      @Electricalsteve  2 роки тому

      Hi,
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code WERD1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

  • @danielmlynarz8900
    @danielmlynarz8900 Рік тому

    Hi Stephen, could you please write me your email address? I need it in relation to the Udemy voucher. Thank you in advance.

    • @Electricalsteve
      @Electricalsteve  Рік тому

      Hi Daniel
      Go to the Udemy website, search for courses under my name ( Stephen brooks ) & use the voucher code IGST1001 to get them for $9.99, vouchers expire in 5 days.
      Regards
      Stephen Brooks

    • @danielmlynarz8900
      @danielmlynarz8900 Рік тому

      @@Electricalsteve Thank you, purchased.