3 Phase Balanced vs 3 Phase unbalanced system / load | Explained | TheElectricalGuy

Поділитися
Вставка
  • Опубліковано 13 лип 2018
  • Three phase balanced system or load and Three phase unbalanced system or load are the two most commonly used concepts in power system. But, what do we really mean by a balanced or unbalanced 3 phase system? What are the parameters that decide whether a system is balanced or unbalanced? So, if you want to get the details and the basics of a 3 phase balanced and unbalanced system, watch the video.
    Star & Delta Connection - • Star and Delta Connect...
    For more interesting videos & articles about electrical engineering visit - www.theelectricalguy.in
    Find me:
    Facebook - / iamtheelectricalguy
    Instagram - / the_electricalguy
    LinkedIn - / gaurav-r-joshi
    UA-cam - / gauravj
    Google + - plus.google.co...

КОМЕНТАРІ • 226

  • @elguapo1507
    @elguapo1507 4 роки тому +18

    That was a smashing explanation which reminded me of my training in ac theory many years ago. Nicely done!

  • @MissionFitnessCTC
    @MissionFitnessCTC Рік тому +6

    Good video. I would have liked to see more explanation around how the unbalance creates current flow in netural.

  • @claytonharrop
    @claytonharrop 5 років тому +3

    I watch HVAC SCHOOL channel to continue learning about my HAVC trade. I'm so glad I've finally found someone of the same quality to continue to learn about my Electrical trade! Thank you for these videos!

  • @nickb1875
    @nickb1875 4 роки тому +3

    Hi sir, really liked your video. I'm not an electrician I am a DIY guy. I was wondering if it is possible to connect 2 or more ac power sources ( alternators or generators for example) in parallel, in order to obtain higher wattage whilst maintaining same voltage. For example, if the source produce 220 each. I want to keep the 220 but with high load capabilities.

    • @philip1541
      @philip1541 4 роки тому

      Yes that is possible and done i many places, the problem is you have to synchronize them meaning that L1 L2 and L3 have to be "in fase" when connected or it will not be possible.

  • @atemobengbeng
    @atemobengbeng 2 роки тому +7

    thank you for this 🥺 it is hard to learn with yourself specially now Online class i really enjoy watching and at the same time learning, now i have a learnings about 3phase system ❤️ thank you i know that it was 3years ago. but this can help not only me a lot of student will appreciate it thank you

  • @manjuchauhan2777
    @manjuchauhan2777 4 роки тому +2

    This is fantastic explanation I had never seen is in english

  • @sarathk.b5020
    @sarathk.b5020 4 роки тому +1

    Sir,
    What is the problem if the neutral is earthed in load side inorder to bypass unbalanced current?

  • @lpndoro
    @lpndoro 3 роки тому +1

    Excellent explanation.

  • @abdulmughniabuzainah2561
    @abdulmughniabuzainah2561 6 років тому +2

    You can’t imagine how useful your videos are to me..
    Keep going bro

    • @GauravJ
      @GauravJ  6 років тому +1

      Thank you friend. Do share the video with your friends, so that it will also help them. 😊

    • @1994anandhu
      @1994anandhu 5 років тому

      I too have Mr Gourav.. u r videos r so clearful.. Understandable.. I often recommend these videos to my students.

  • @mahadevakumar2104
    @mahadevakumar2104 4 роки тому +2

    Thanks for the video, which is the software u used to simulate ?

  • @lucasokomuniewski6525
    @lucasokomuniewski6525 Рік тому

    Is It bad to have an unbalanced system?? Also if you have 3 separate inverters and turn them on at diffrent times will the source be unbalanced? Is there a device that can balance a wave form?

  • @KH4N0607
    @KH4N0607 4 місяці тому +1

    Thankyou for these videos ❤️

    • @GauravJ
      @GauravJ  4 місяці тому

      Glad you like them!

  • @dashok4749
    @dashok4749 7 місяців тому

    Sir,Why the neutral conductor size is half the size of phase wire, during unbalanced condition the neutral current may be equal to phase current?

  • @thezarina4681
    @thezarina4681 2 роки тому +1

    That was simple ND a neat explanation..keep going...thank q😇

    • @GauravJ
      @GauravJ  2 роки тому

      Thanks 😊 do share and subscribe

  • @erin4439
    @erin4439 5 років тому +3

    Great video. Do you have any videos on calculations? I couldn't find one on your channel. I am currently learning Wye and Delta, balanced and unbalanced. It is difficult to find a video that will show how to learn the calculations. Thank you for your videos.

    • @azirulbahrom5438
      @azirulbahrom5438 4 роки тому

      Did u find out already? Im currently looking for it as well

  • @omarsh77
    @omarsh77 4 роки тому

    If both source and load are solidly grounded and if we assume a negligible resistance in the neutral wire, shouldn't the supply neutral and the load neutral be at the same potential i.e. neutral current = 0 A?

  • @ImthiasAhamed
    @ImthiasAhamed 2 роки тому +1

    Good video
    Please explain use of MATLAB

  • @manojkumarsaddala8236
    @manojkumarsaddala8236 5 років тому

    how to create phase unbalance, is it possible to create phase unbalance using VFDs? or we can also induce the phase unbalance for DOL connections?

  • @samrush3700
    @samrush3700 8 місяців тому

    Hey can you make a video on fault occur on balanced system and haw 2 phases increase √3times in faulty condition

  • @emmanuelmawulikorve7805
    @emmanuelmawulikorve7805 3 роки тому +1

    You are awesome... Thanks for the video

    • @GauravJ
      @GauravJ  3 роки тому

      My pleasure!! Do share and subscribe to my channel ✌🏻

  • @swarupmohanty3655
    @swarupmohanty3655 5 місяців тому

    Sir how cbct detects these unbalances in phases please make a video on it

  • @pushpakbhangale2689
    @pushpakbhangale2689 6 років тому

    Hello sir, there is one question ,What will happen if we connect two AC source of same frequency and magnitude but uneqaul voltage (paralle and series in both case). say, one of 25 kv & another of 27 KV source to 25 KV load. What will be the effect on voltge, Power & current of the circuit as well as to the another 25 KV load? Previously i am working on the same ckt the 25 kv source if from Xmer and another source i am talking about is an induction motor which is connected parallely to Xmer as well as to the other loads. Whenever we require a mechanical energy we used it as a motor but at time of stoping we have used a regenerative braking system, at that time induction motor generates emf is more then 25 KV. One more thing i want to add on we have connected a braking resistors to motor ckt so that the generated power can be dissipated. But what if we didn't connect the braking resistors or if the resistors is blolwn out. What will be the reaction in ckt. If possible please make a video on this or send the explanation to my mail id pushpakbhangale303@gmail.com

  • @sampawar7674
    @sampawar7674 3 роки тому +2

    Please explain concept of floating neutral

    • @GauravJ
      @GauravJ  3 роки тому

      Hi.. here is the video on floating neutral
      ua-cam.com/video/b9hDHGxaufM/v-deo.html

  • @mr.calculator1207
    @mr.calculator1207 Рік тому +1

    Thank u sir.....and sir plz one request plz do video on power system

    • @GauravJ
      @GauravJ  Рік тому

      Thank you. Videos available on my channel. Do check it out

  • @DSEE-ShashikumarHanagi
    @DSEE-ShashikumarHanagi 10 місяців тому

    will you please explain how grounding is compensate unbalanced system to balanced system.

  • @sububalan
    @sububalan 2 роки тому +1

    Thank you. This was a good refresher.

    • @GauravJ
      @GauravJ  2 роки тому +1

      Do also check out other videos on my channel 😊

  • @youssofasiry7233
    @youssofasiry7233 10 місяців тому

    Thanks for your easy explain.
    What is the allowed unbalance persent of current in three phase motor and if I connenct neutral wire will protect the motor from heating?

    • @GauravJ
      @GauravJ  10 місяців тому

      Hi. A three phase motor is a balanced load and hence no neutral is required.

  • @venkatavenkey3842
    @venkatavenkey3842 3 роки тому +2

    Good explanation thanq sir 👍 iam new subscription 🤗🤗🤗...

  • @Sagartechnicals
    @Sagartechnicals 2 роки тому

    How can we maintain the equivalent current in each phase which are use connected to other appliances as well as three phase induction motor .
    suppose
    i have three phase motor which i use to run in delta
    and if i select one of phase for single phase motor , definitely there's the unbalance conditions appear in three phase induction motor
    how can we maintain it...

  • @khalidialsaqqa500
    @khalidialsaqqa500 3 роки тому +1

    Hi
    Thanks for your nice explanation.

    • @GauravJ
      @GauravJ  3 роки тому

      You are welcome ☺️ do share the videos!

  • @mustafasami3023
    @mustafasami3023 3 роки тому

    Dear Gaurav;
    Ok, we have understood unbalanced system but how can we balance an unbalanced sytem. ( especially 380 system driven by 220v + capacitor)

  • @bhuvanakrishna1960
    @bhuvanakrishna1960 6 років тому +3

    Thanks for doing these videos....! Expecting more videos

  • @SivaKumar-cq2wu
    @SivaKumar-cq2wu 3 роки тому +1

    I am requesting upload video on effects of faults on alternator.

  • @bravindsouza3375
    @bravindsouza3375 4 роки тому +1

    Sir where does neutral current go back to in case of unbalanced system ?

  • @Abcde-yk6qy
    @Abcde-yk6qy Рік тому

    Hi sir can you please explain why 3 phase falt cable one conductor get different reading ?

  • @radhakrishnans785
    @radhakrishnans785 5 років тому +1

    Very easy to understand

  • @arsalan479
    @arsalan479 5 років тому

    Hello gaurav I have a basic question. In a.c. star connection three coil will form a 3phase. We all know that we are making phase neutral in a sane wire for All three wire carrying electrons which always flow towards the phase direction my question is why not all three phases electron going towards neutral direction and meet. Why it is going always opposite side of neutral. What is the reason behind this.

    • @GauravJ
      @GauravJ  5 років тому

      Phase and neutral wires are different. To complete the circuit current needs a return path and hence it flows through the neutral.

  • @Premsai18
    @Premsai18 3 роки тому +1

    Thanks brother for your easy explained I have understand easily❤️😍👍

    • @GauravJ
      @GauravJ  3 роки тому

      Good. Do share and subscribe to my channel ☺️✌🏻👍🏻

  • @harishbonthala2494
    @harishbonthala2494 4 роки тому +1

    Sir, will you please upload a video about connections of windings in a power transformer

  • @jamesr5094
    @jamesr5094 6 років тому

    I am new to electrical things. As seen in the video, on balanced load at any degree the current is same. But in unbalanced load current varies in 3 phases and neutral is needed.
    what is the function of neutral in unbalanced load and what happens if neutral fails?
    Why neutral is not needed in balanced load and what happens if neutral fails?

    • @GauravJ
      @GauravJ  6 років тому +1

      In balanced system neutral is not needed because the sum of return currents is ZERO (watch video from 2.10 mins), but in case of unbalanced load the sum of return currents is not zero and hence there will be some return current for which neutral is needed. And if neutral fails, the machines start heating and this will reduce the overall life of machine.

  • @freshersofbose456
    @freshersofbose456 Рік тому

    WHAT is the current returning path in delta connection plz sir describe it 🙏

  • @silverubica
    @silverubica 3 роки тому

    What will happend in balansed system if 1 phase line is interrupted,what current will be then in?

  • @bennettmnathe7009
    @bennettmnathe7009 2 роки тому

    Suppose an industry is supplied from two 3 phase transformers, and somehow on the installation to the loads, the earth is swapped, is the any effect?.

  • @khadraj3178
    @khadraj3178 5 років тому +1

    Hello sir,Thank you for your great videos, I’v a refrigeration compressor works and then stops for less than a minute and when measured the current for 3 phases, I noticed L2 giving a very high current "3 times the normal value" and L1 and L2 normal, what is expected to occur this problem, Even though there is a failure phase sequence in the circuit.

  • @desyemoges745
    @desyemoges745 5 років тому +3

    thank you your language is smooth and easy to understand

  • @charlescoyle433
    @charlescoyle433 4 роки тому

    Thank you for good explanation of balanced 3 phase distribution. Have question, Using 3 phase 208 volt Y power at our church. 3-phase to large HVAC equipment, Using individual phase legs and neutral to provide 120 volts to utility outlets in building. When circuit breaker is shut of on one of the 208 volt legs we see a small voltage across the switched off leg and neutral. Interested to know what causes small voltage appearance and if it is drawing any power. When measuring small voltage, ~20 t0 40 volts, there is no load across wires. Any explanation will be appreciated.

    • @GauravJ
      @GauravJ  4 роки тому

      It may be because of the capacitive charge which is present in the transmission line/cable. You can use disconnector with earth switch, using earth switch you can ground the charge.

  • @MrShafeek4
    @MrShafeek4 3 роки тому

    My 3 phase generator producing a low voltage on one phase the other 2 phase gone high? What is the reason and how can I fix this issue?

  • @igordekanga8297
    @igordekanga8297 4 роки тому +2

    Hi
    We want to know if DC grounding must be separated from AC grounding in telecom site.

  • @yuvarajbommuraj5357
    @yuvarajbommuraj5357 3 роки тому

    Sir , Can You post Potential Transformer Secondary connections

  • @iyearn1
    @iyearn1 3 роки тому

    Dear Gaurav, I am wondering: if a 3 phase motor moves only a small angle (like 30 degree), rather than 360 degree repeatedly, is it a unbalanced system?

    • @GauravJ
      @GauravJ  3 роки тому +1

      No. 3 phase motors are balanced loads..!

  • @prakashyadav408
    @prakashyadav408 Рік тому

    What is the acceptable limit of ampere difference in load balance

  • @tedlahm5740
    @tedlahm5740 4 роки тому

    Kindly delve into single phase step down transformer operation. With attention
    to the NEUTRAL connection thru the two windings. Primary and secondary.
    Thank you. Also please MENTION how much current is on the Neutral
    of an unbalanced system.

  • @reeshamaniyath6937
    @reeshamaniyath6937 4 роки тому +1

    Thank u sir...ur videos very useful

  • @DownToEngineer
    @DownToEngineer 2 роки тому +1

    Thanks! great explanation.

    • @GauravJ
      @GauravJ  2 роки тому +1

      Do share and subscribe 😊

  • @yahyaalsarfi3188
    @yahyaalsarfi3188 3 роки тому +1

    Thank you. How we can eliminate the unbalance power?

    • @GauravJ
      @GauravJ  3 роки тому

      That is practically not possible

  • @glennmacabuhayvillas9461
    @glennmacabuhayvillas9461 4 роки тому +2

    Thanks for the video.

  • @cr7_______....____
    @cr7_______....____ 3 роки тому +1

    perfect explanation.....well explained hats off bro

    • @GauravJ
      @GauravJ  3 роки тому

      Thank you. Do subscribe to my channel and also share the video 🙂 you'll get more such easy to understand explanations 🙏

    • @cr7_______....____
      @cr7_______....____ 3 роки тому +1

      i already subscribed ur channel becoz u deserve it.....i hope u will keep providing us with such awesome videos regarding electrical engineering....

    • @GauravJ
      @GauravJ  3 роки тому +1

      Thank you 😊 sure, I'll keep posting the videos

  • @mohammadpathan4668
    @mohammadpathan4668 6 років тому +2

    very nice explanation!

  • @prabakaranpk3291
    @prabakaranpk3291 5 років тому +1

    Superb explication 👌👏

  • @johntony5421
    @johntony5421 4 роки тому +1

    good explain.....thanks much.

  • @kishankumar5014
    @kishankumar5014 3 роки тому

    Sir Please make a video on this topic three-phase transformer connections from basic .......please please.

  • @geethag3420
    @geethag3420 3 роки тому +1

    Superb sir...tqq soo much sir...😊😊

  • @ronmar1able
    @ronmar1able Рік тому

    You have illustration control for medium voltage switchgear?

  • @mosesezirim4430
    @mosesezirim4430 3 роки тому

    is there any scenario where the earth cable can be used in place of the neutral. if yes, can you do a video on that?

  • @santhoshdhanajaya815
    @santhoshdhanajaya815 2 роки тому

    3 phase system has unbalanced load in my factory do we have any alternative to balance it ?

  • @karinayu4374
    @karinayu4374 10 місяців тому

    how to do three phase unbalanced compensation in control loop?

  • @etechnanban6478
    @etechnanban6478 5 років тому +1

    Very clear explanation thank you....

  • @scotthudleson3098
    @scotthudleson3098 2 роки тому +2

    I admire your knowledge and value the information you graciously share with us. Perhaps it would be better that an interpreter or voice over is used for those of us who lack exposure to so many wonderful cultures and languages.
    I think we focus on trying to interpret your English with an Indian accent rather than the education you're promoting sir.
    I think it's amazing that people can speak multiple languages. I hope some day I will too.
    Thank you kind sir for your valuable information.

    • @michaelshaughnessy9809
      @michaelshaughnessy9809 Рік тому

      I'm just the opposite, the accent helps me and a voice over with some robotic voice would drive me insane. Perhaps it would be better if you exposed yourself to some cultures and languages.

  • @paulbeisler1606
    @paulbeisler1606 6 місяців тому

    How about a three phase generator that has a balanced resistive load but voltage is not balanced.

  • @lawnwoke4958
    @lawnwoke4958 3 роки тому

    Thanks for the tutorial, kindly permit my to ask question. apart from electrical motors, what other devices do unbalance system affect.
    If a UPS is installed on unbalance system does it affect the output of the ups?

  • @manivk7784
    @manivk7784 2 роки тому

    Give the problems for this balenced and unbalenced loads sir thank you

  • @ajaytentu9904
    @ajaytentu9904 3 роки тому +1

    Thank you sir

  • @reddypochasivasankara4745
    @reddypochasivasankara4745 2 роки тому

    HI Gaurav,
    Can you post some detailed videos on inductions motors and it controls

    • @GauravJ
      @GauravJ  2 роки тому

      Sure. I’ll try

  • @sayedrezasadat4881
    @sayedrezasadat4881 Рік тому

    thanks it was really helpful but need some examples

  • @syamsreedevada2783
    @syamsreedevada2783 4 роки тому

    The best explaination that never heard

  • @PramodKumar-zl4gq
    @PramodKumar-zl4gq 2 роки тому

    Plz explain non linear resistance calculation for a surge arrestor

  • @Rakeshjalli
    @Rakeshjalli 6 років тому +2

    Please do vidoes on power system protection sirrr

    • @GauravJ
      @GauravJ  6 років тому +1

      Sure my friend..👍🏻

  • @minasagun8718
    @minasagun8718 5 років тому

    How about if phases and neutral cables have same amount of current? What is the cause?

  • @SSSS-ot8yk
    @SSSS-ot8yk 5 років тому

    Please do video about..in transmission lines voltage is high but current is low..it is not satisfying ohms law how it is?

  • @krishankantrajput7008
    @krishankantrajput7008 3 роки тому

    Sir please make video of poly phase system

  • @rashidchibvuri2036
    @rashidchibvuri2036 4 місяці тому +1

    Nice

  • @tejrajadhikari7269
    @tejrajadhikari7269 3 роки тому

    then if the system is unbalanced or has an unbalanced load in 3 phases then what to do to make it balance and all .. a video want on it with example and procedure

    • @GauravJ
      @GauravJ  3 роки тому

      Hey. Watch this video to get the answer. -
      ua-cam.com/video/dRuYSd7pwSY/v-deo.html

  • @viswanathancr2801
    @viswanathancr2801 2 роки тому +1

    good video

  • @10-madhumitamanikmahapatra73
    @10-madhumitamanikmahapatra73 3 роки тому +1

    Very well explanation sir🙏🙏,sir can you please make video on three phase transformer.

    • @GauravJ
      @GauravJ  3 роки тому +1

      Thanks. Sure I'll try ✌🏻 do share and subscribe to my channel ☺️

  • @thisukainol
    @thisukainol Рік тому +1

    thanks a lot man

  • @fardinulhoque5339
    @fardinulhoque5339 4 роки тому

    Brother what happens for 100 ohm, -100j ohm and 100j ohm can they make a balanced delta load

  • @MrHazahari695
    @MrHazahari695 3 роки тому +1

    Thank you. It's helpful.

    • @GauravJ
      @GauravJ  3 роки тому

      Thank you ☺️ do share and subscribe to my channel ☺️✌🏻

  • @charcoal386
    @charcoal386 Рік тому

    I have a star connected heater arrangement which is balanced. There is no neutral. What happens if one heater blows open circuit

    • @GauravJ
      @GauravJ  Рік тому +1

      It will create unbalance. You may have voltage fluctuations!

    • @charcoal386
      @charcoal386 Рік тому

      There are parallel resistors in each leg of star. If one blows I would have 20 ohms in 2 legs and 40 in one. Is anybody up for calculating resulting voltages

  • @anirudh7829
    @anirudh7829 3 роки тому

    plz explain what is per phase analysis ?

  • @naveenrevuri3611
    @naveenrevuri3611 3 роки тому +1

    Exlent explination

  • @manjuchauhan2777
    @manjuchauhan2777 4 роки тому

    Can u explain one thing for us that if power factor is capacitive for long time what will happen

  • @svg127
    @svg127 5 років тому

    Please explain how is current flow happen on neutral conductor without voltage it's very difficult to understand me

    • @ladekishor9731
      @ladekishor9731 5 років тому

      Yes sir me too

    • @tedlahm5740
      @tedlahm5740 4 роки тому

      Perhaps the electrons are PUSHED and PULLED from the Hot side of the circuit.
      Electrons (negative charged particles in the copper atom) move back and forth.
      If not balanced, they would end up at the end of one of the copper conductors.

  • @technicalswag3925
    @technicalswag3925 2 роки тому

    Smashing explanation

  • @sudheeshss5503
    @sudheeshss5503 5 років тому

    Sir.. I want to know about Negative sequence protection for generators.Kindly explain

  • @karimullashaik3245
    @karimullashaik3245 Рік тому

    Sir can you please fully explain unbalanced distribution system

  • @sudhirpatil3434
    @sudhirpatil3434 5 років тому +1

    Good explanation!

  • @studyforyou9621
    @studyforyou9621 3 роки тому

    Sir I want to video on electronics and on power electronics

  • @allsquire8362
    @allsquire8362 2 роки тому

    Sir please describe the different types of protective relay and zone...

  • @ramesheee3209
    @ramesheee3209 3 роки тому

    Do video about harmonics in generated

  • @sachinhosamani5797
    @sachinhosamani5797 3 роки тому

    By using nutral in un balanced condition how we Ower come effect of different current drawn sir?

    • @GauravJ
      @GauravJ  3 роки тому

      Hi. Check out this video. This might help.
      ua-cam.com/video/dRuYSd7pwSY/v-deo.html