The correct way to pipe multiple Rinnai tankless heaters

Поділитися
Вставка
  • Опубліковано 22 січ 2022
  • The first in last out method of piping unites has been around for a long time but in my research of piping the system I found it was overlooked.
    As I explained in the video we learn from our mistakes and the way I piped in that system proved it, after it was fixed it worked perfectly.
    If you would like a piping diagram, please e mail me your info to economyplmbg@aol
    If you would like to buy the filter removal tool, please e mail me at economyplmbg@aol.com and include your complete name and address.
    I hope you enjoy the video,
    Mike
    PLEASE USE A LICENSED PLUMBER TRAINED IN RINNAI LEVEL THREE TRAINING AND TO FOLLOW ALL LOCAL AND NATIONAL PLUMBING AND GAS CODE. FILE A PERMIT WITH YOUR LOCAL BUILDING DEPARTMENT AND TO OBTAIN AN INSPECTION.
  • Навчання та стиль

КОМЕНТАРІ • 66

  • @yzmoto80
    @yzmoto80 2 місяці тому

    Rinnai says differently for a two unit set up, one RXP and one RX.
    They sent me a pipe schematic, and it’s not only first in, first out, but the first in unit is the one without the pump. I’m going with Rimnai’s pipe schematic, because if something doesn’t work right, or something gets fouled up, I’m pretty sure “That Tankless Guy” isn’t going to warranty my customers $6000 in water heaters. No offense to you Sir, You are indeed an angel for all your selfless help to other people out there. 😎

  • @verdiben
    @verdiben 2 роки тому +4

    Thanks Mike. I just installed a second unit using your piping method yesterday and it worked great! Interesting thing to note is that when you display the GPMs on the panel, they are evenly split. When I tested the new Rinnai, I had the old one off. I didn't shut off the hot and cold water inlets to the old one so when I ran water I was only getting half the GPMs through the new unit and it wasn't getting hot enough. As soon as I shut off the old one's shutoff valve, the new one had all of the flow and worked great, which makes sense. Only reason I am mentioning this is that if you do have two units that are piped this way and one fails, the technician needs to make sure they shut off the water flow to the one that has failed because if not, the pressure is split whether it is on or not. Thank you for posting your video. My client was better served by it.

    • @TheBuddylab
      @TheBuddylab 2 роки тому +1

      That’s correct and also unplug the MC cable. Thanks for the comment Mike

  • @chatbot007
    @chatbot007 2 роки тому

    Mike this is a great video, I will remember FILO if we decide to run two units. Thanks for taking my call today and giving me great advice!

  • @jonathanwoo6597
    @jonathanwoo6597 2 роки тому +1

    Thanks for the video. I have seven units in parallel. I will check them to see how they are piped. Looking forward to the upcoming communications video.

  • @ricardotrujillo2692
    @ricardotrujillo2692 2 роки тому +1

    Crazy we just did this on a three tankless set up and works perfectly ... Thanks Mike.

  • @michelleheart190
    @michelleheart190 Рік тому

    It's a great video! Thank you. I"m looking for my grand kids who are in the hvac trades!

  • @tonymc3817
    @tonymc3817 Рік тому

    Wow, ty man. Hope I can keep up. You're very good

  • @Abonilla031
    @Abonilla031 2 роки тому

    Great videos and congrats on the 10k sub 🙌

  • @johnbui5349
    @johnbui5349 Рік тому

    Very informative

  • @evgenyli5947
    @evgenyli5947 2 роки тому +2

    Thank you Mike. Great topic. Correct me if I am wrong but “first in last out” is for non build in recirc pump units only with external pump and aqua stat system. RUR models do not apply. Thank you

  • @charliehall7213
    @charliehall7213 2 роки тому

    Thank you

  • @I2SUSA
    @I2SUSA 2 роки тому

    Thank You!

  • @jzs6272
    @jzs6272 Рік тому

    Great video

  • @vistasbramag9564
    @vistasbramag9564 2 роки тому

    Mike this is a great video, Muchas gracias , puedes Hacer un video flushing un water heater tankles rinnai

  • @shardy083
    @shardy083 2 роки тому

    Man, I am not a plumber, I love this type of work, you are a legend!

  • @idakmiecik3732
    @idakmiecik3732 Рік тому +1

    Hi Mike, you video is extremely helpful. I was wondering how to incorporate a holding tank to a double rinnai system

    • @TheBuddylab
      @TheBuddylab Рік тому

      First you need a storage tank with three tappings. You need to have a pump pump into the tank from the tankless heaters.

  • @jetlaggedchef6806
    @jetlaggedchef6806 2 роки тому

    Great video! Makes perfect sense. Is it possible to use a Rinnai tankless on a hot water line coming from a regular tank hot water heater? I have a large home and with multiple bathrooms but live alone. My tankless is right outside my master bathroom but I also have a regular tank water heater on the far opposite corner of the house. I was hoping to accomplish two things: (1) Have the tankless kick on so I had hot water instantly (for example - when washing hands) and (2) have potentially endless hot water when the tank runs out for the 3 rain maker shower heads in the shower.

  • @ryanminshall5906
    @ryanminshall5906 Рік тому

    Can I get a drawing of how to do this with a dedicated recirc line do I have to put spring checks before both cold feed or do I have to spring check each tankless individually

  • @BrandonAEnglish
    @BrandonAEnglish Рік тому

    Thanks for the explainer video. Question: if I have two weak, electric tankless heaters (one can't get the water hot enough for showers during the winter), then why not run it like this: COLD IN on Heater #1, HOT OUT from #1 to COLD IN #2, HOT OUT from #2 ? Why isn't this an option?

  • @johnhalladay4115
    @johnhalladay4115 2 роки тому +1

    I really enjoyed the video. I have a question on the return line for my 2 tankless cu199en setup. How can I reach you?

  • @StinyGinkle
    @StinyGinkle 2 роки тому

    Off topic, but i have been doing service on alot of tankless Rinnai in a development. all the homes have a short vent horiozontal application, that terminates horizontally. Have had alot of complaints about HEAVY vibrations on high flame needs. . and by heavy, i was able to recreate it, and boy ill tell you it was very noisey and the unit shuttered hard. it eventually code 12. put on the monometer was reading 7 at inlet and used guide to force low fire numbers, when trying to adjust high fire it would shutter sound like a trumpet and code 12 never being able to set it. the builder is putting storm caps on the vent termination outside, which is causing the issue, exhaust and intake mixing. not sure if you have covered that kind of problem on a heater, but somthing simple had me scatching my head as the weatherhead looked OEM.

  • @JF35
    @JF35 Рік тому +1

    hey mike , this same water configuration works on navien tankless ?

  • @CoreyGorgeous
    @CoreyGorgeous Рік тому +1

    This was incredibly helpful. My question is with the ez connect. Do I need to change the parameter 7 for the primary the sub or both? Thank you very much!

    • @mikesmodeltable9040
      @mikesmodeltable9040 Рік тому

      Yes you do have to set the dip switches for the primary and subs

  • @MikeyBickle
    @MikeyBickle Рік тому

    How’s it going! It’s mike from Agustin Inn. I’m about to try and repipe our hot water heaters! Any suggestions on how I should route it? You might remember me, I remember you Informed me of the first in last out a few months ago! Thank you sir!

  • @bijouwesterling3592
    @bijouwesterling3592 2 роки тому +2

    Thank you for the video - I am a homeowner and constructing a new home and planning to have a dedicated RUR199iN for the master suite only, but in the winter (in New England) if the GPM demand cannot keep up with the unit due to the temperature change, would it be difficult to use your technique in this video and plumb in a second unit after the initial install of the first unit? The second unit probably won't be needed in the summer. Is there a way to change from using one unit to two, and vice versa easily? Should I plan for the possibility of needing a second unit in the roughs now? The unit is located in an unfinished storage area in the basement, in case that matters. Thanks for your advice on this!

    • @TheBuddylab
      @TheBuddylab 2 роки тому

      1/ How many bathrooms will be in your house
      2/ would you know what the ground water temperature is of you cold water.
      Mike

  • @walterbutler275
    @walterbutler275 Рік тому

    Hi Mike,
    I am tracking down what I believe is a plumbing issue. I re-did the water piping for "first-in, last-out" as you recommend. Now with only one faucet on, neither water heater fires. With two or more faucets on, both water heaters fire. My house was constructed in 2007 with both a R53 and a R85. One is a back-up, but i would like to have both on the system for greater demand.
    Looking at some of the multiple tankless installation literature I see the use of a Pressure Activated Valve on the second tankless water inlet. This was not in your plumbing video, so before I purchase one, I wanted to run this application by you. What do you recommend?
    Thanks,

  • @dannajones4013
    @dannajones4013 2 роки тому

    I have an 2005 R53, we ran out of propane, once filled unit throwing code 11, I am assuming there is air in the gas line..can you explain how to bleed the gas line. please 🙏

  • @user-rb5mg1hk3r
    @user-rb5mg1hk3r Рік тому

    I am installing two Rheem Performance Platinum 11 GPM Natural Gas High Efficiency Indoor heaters. What do I need to control them?

  • @shockingshorts8043
    @shockingshorts8043 11 місяців тому

    Why don't you do other videos besides water heater and NASCAR?if that could be a thing I would love to see some common commercial plumbing job videos!

  • @user-ec3zc9fh3z
    @user-ec3zc9fh3z 7 місяців тому

    What about a 3 story home with 1 cold water supply, and 1 dedicated tankless for each floor with no recirculating until? How does that get plumbed ? (Electric not gas?)

  • @jbarclay1965
    @jbarclay1965 Рік тому

    What determines first in and last out? I think I see "first in" as shortest pipe length from shared cold water supply and "first out" as shortest length toshared hot water exit.

  • @terryobeney2350
    @terryobeney2350 Рік тому +1

    You mention a video for the correct way to install and set up the EZ-connect cable between 2 RU units. I couldn't find it. Can you provide a link? Thanks

  • @donatogopar8586
    @donatogopar8586 7 місяців тому

    Is this the same for any water brand water heater?

  • @roysoliz3610
    @roysoliz3610 2 роки тому

    I have only one unit and the hot goes to a manabloc. What is the advantage of adding a second unit? I don't know the advantage. Please explain.

  • @JB-jk3ow
    @JB-jk3ow 2 роки тому +1

    Hey Mike. How can one get ahold of you directly say per email? Thanks for what you do from a fellow plumber.

  • @kayzrx8
    @kayzrx8 5 місяців тому

    Hey I have a home that has 2 Rinnai RU199iP in parallel , The previous homeowner did not have them connected to control each other. What parts would I need to fix this. They run erratically as is .

  • @anthonydecandia2556
    @anthonydecandia2556 9 місяців тому

    943 pm I have a salon with 2 tankless water heaters. I checked the heaters one runs 3 sinks. O problem. The other runs 12 sinks and cannot handle the load. Can I twin them to Run simultaneously?

  • @PhilScordato
    @PhilScordato 3 місяці тому

    Hey Mike, Could I send you a couple pictures of a system I just replaced with a bank of 6 RE199ip's and get your opinion? It's a recirculating system with two storage tanks. Aquastat in tank turns on pump which fires all the units at once. I'm curious what the opinion is on this setup vs first in last out ?

  • @MrBobst2003
    @MrBobst2003 2 роки тому

    Hi Mike, i flush rheem and rinnai heaters, trying to flush a double heater (side by side) the left one will not flush, it has its own set of servicing valves, but when i isolate water or cleaner will not cycle.

  • @manuelanos5416
    @manuelanos5416 2 роки тому

    My Rinnai HD200e stops operating the display screen coming on and then goes of after few seconds. What is the problem? I have cleaned water inlet filter, there is no error code on.

  • @jimquinty5378
    @jimquinty5378 2 роки тому +1

    what does a c-4 15 code mean the unit keeps turning? off and needs to be reset. thank you, Jim

  • @sudge3
    @sudge3 Рік тому

    Hi Mike, i have 3 tankelsss water heaters piped the way you have them and were working fine till about 2 weeks ago after working well for 3yrs. When hot water is called for, one of the units turn on, but the water goes from hot to cold, to warm, and then slowly gets back up to temperature if kept running. I called the manufacturer to troubleshoot the units and was told that they are all working well and that the issue might be the lack of a check valve being put on the cold line. I'm inclined not to buy the idea because they were working well till recently, and i cant figure out what the issue might be. Maybe one of the flow sensors from the other water heaters isnt working and is letting cold water run through its line when another water heater is working? Have you ran across this situation before?

  • @haleypowers5112
    @haleypowers5112 Рік тому

    If you have 2 units, one with a pump and one without. Which unit gets the first in last out?

    • @danbeeson9564
      @danbeeson9564 Рік тому

      Did you ever get an answer to your question? I am about to install a pair.

  • @user-wy8ml2mq1t
    @user-wy8ml2mq1t 7 місяців тому

    reverse return

  • @mikeedwards7143
    @mikeedwards7143 Рік тому +1

    Does this work the same with ELECTRIC tankless heaters?

    • @TheBuddylab
      @TheBuddylab Рік тому

      It worked with any type of heater

  • @NastyN84423
    @NastyN84423 2 роки тому

    How about with a research?

  • @russellstroud9361
    @russellstroud9361 2 роки тому +1

    How do I email you Mike ? Thanks

  • @stephenstrong4459
    @stephenstrong4459 2 місяці тому

    Do you have email? I’d like to send you a picture and get your input on a double install.

  • @Vic-td7hp
    @Vic-td7hp 8 місяців тому

    I just printed and color coded a Rinnai rack system, and it is not piped first-in, last-out!

  • @geworthomd
    @geworthomd 10 місяців тому

    Not enough inlet flow to turn on either

  • @grantparnes
    @grantparnes Рік тому

    Im more confused than before I watched this

  • @noahbartholomew932
    @noahbartholomew932 Рік тому

    The whole loopdy loop is Not the correct way to do it. If you want to do it right you have to manifold it so once you tee off to each heater the lines are the same length so that they have the same amount of draw. It still won't work right with the loops. Just like with multiple body sprays in a shower

  • @joseramoncontreras6163
    @joseramoncontreras6163 Рік тому +2

    try editing your videos

  • @philweiand4564
    @philweiand4564 Рік тому

    Need your email