  • @assistantto007
    @assistantto007 Рік тому +3

    Do you have to be gas safe registered to undertake that task?

    • @GasTraining
      @GasTraining Рік тому +5

      Gas safe to touch the boiler components my friend. Don’t play with gas if you ain’t gas safe.

    • @dylanbrandley7888
      @dylanbrandley7888 Рік тому +3

      Gas safe as soon as you open the combustion chamber!

    • @assistantto007
      @assistantto007 Рік тому +2

      @@dylanbrandley7888
      OK, does that mean the water side of the boiler (& the electronics) can be serviced by non gas safe engineers ?

    • @ranat5526
      @ranat5526 Рік тому

      ​@@assistantto00730 years ago I became a corgi registered gas engineer, 70% of the people on the course were duffer's!

    • @500bht
      @500bht 11 місяців тому +7

      No gas safe needed as you own the boiler it's your property so do what you like to it

  • @marcush6139
    @marcush6139 Рік тому +2

    I will say karma I do enjoy your videos as a new engineer is help me out greatly. The only thing I will say you make it look so easy because you do all your jobs one-handed where I struggle with two lol. Roll on the next video

  • @Carl-re6zb
    @Carl-re6zb Рік тому +3

    Great vid for anyone wanting to gain confidence in boiler repairs.

  • @ArifPolicewala
    @ArifPolicewala 7 місяців тому +2

    That is a top in depth video as usual❤

  • @ronalynaguipo9666
    @ronalynaguipo9666 5 місяців тому +2

    What chemical you have used sir? Thank you for sharing

  • @rm-mastering
    @rm-mastering Рік тому +1

    Great video and yes top marks for one handed work 🏆

  • @dylanbrandley7888
    @dylanbrandley7888 Рік тому +1

    Some of the things you do whilst holding a camera, sick 👍

  • @SuperVitz
    @SuperVitz 9 днів тому +2

    I just did this a few weeks ago on a newer Viessmann. I'm not gas safe, but I am a competent engineer and will be getting someone out to do a gas safety check. I used central heating cleaner and left it in the heat exchanger for a few hours, took multiple flushes with hot water and shaking the plate to get it clean. In theory this should never block if there is a magnet filter and inhibitor chemicals in the water right? It would've been nice if you added some inhibitor at the end.

  • @abdulaziz-pb5ni
    @abdulaziz-pb5ni Рік тому +1

    I watch all Ur videos they are good and top engineer. Can you do one doing right hand blocks and left blocks repairs

  • @madmaycon2531
    @madmaycon2531 9 місяців тому

    Your videos are very good, they are very helpful, especially for new qualified gas engineers like me.
    Thank you so much !!!

  • @muhammadAli-kd2zp
    @muhammadAli-kd2zp Рік тому +1

    Thank you for your time to share with us . Great job 👏

  • @cliverice5651
    @cliverice5651 5 місяців тому +2

    Thank you for a very informative video. What brand of spirit of salts do you use please? Thank you. Very best wishes Clive

    • @dreamkiss
      @dreamkiss 6 днів тому

      I was also looking for what has he used what chemical is this?

  •  5 місяців тому +1

    Iv heard you can use brick cleaner.?

  • @paulhealey2984
    @paulhealey2984 12 днів тому +1

    Where did you get the spirits of salts? Thanks.

  • @rickd6421
    @rickd6421 Рік тому +1

    Great video mate. I wouldn't be able to film and work with 1 hand so great work :) If the plate hex seals feel and look smooth and not perished, do you just leave originals in when reinstalling plate hex?

    • @advancedboilertraining
      @advancedboilertraining  Рік тому

      Haha! So I always try to change the seals when I can, but if I don’t have any in the van and they seem to be in good condition then I’ll leave them

  • @LaurieAlfonso
    @LaurieAlfonso 10 місяців тому

    Helpful video! If you find that the air valve on the expansion tank leaks out some water when you go to charge it, is that a problem or a sign of a faulty tank?

    • @davelaye7003
      @davelaye7003 5 днів тому

      a lot of the time its not a fault but condensate from compressed air. viessmann put the valve in a stupid place. like the rest of their boilers' badly designed and piece of shit.

  • @freddyc_1
    @freddyc_1 2 місяці тому

    Do you do repair work at all? I'm looking for a plumber for my HIU

  • @Dee-iy4ot
    @Dee-iy4ot 8 місяців тому

    good info , = = = however spirit of salts ( Hydrochloric acid** ) = = = = is too harsh for stainless or alloy ( **Thats why they get pin holed ) . Use a regular kettle descaler instead. and flush both direction with water

  • @sharazali-tabassam3033
    @sharazali-tabassam3033 Рік тому +1

    Good video 👍

  • @nipperh2o925
    @nipperh2o925 Рік тому +1

    Great tips

  • @alihapali
    @alihapali 6 місяців тому

    Any chance we can fit a filter somewhere to stop this blocking mine gets blocked every week even we powerwashed it

  • @mikegallagher2107
    @mikegallagher2107 Рік тому +1

    great content i use this method as well 👌👊

  • @thebigblackguy
    @thebigblackguy Рік тому

    Thanks for this. Subscribed 👍🏾

  • @bluedwarf8858
    @bluedwarf8858 Рік тому +3

    Did you have to use new o rings on the plate heat exchanger

    • @kevinschoales844
      @kevinschoales844 Рік тому +1

      Not sure if he showed whether he cleaned the seals up or replaced them, allways good idea to have replacement seals. & they can fall off !

  • @kovacstamas7332
    @kovacstamas7332 11 місяців тому

    Good job. Thank you. That was the soultion for me.

  • @jockster5525
    @jockster5525 Рік тому +1

    Nice job mate 👍

  • @msangwan7
    @msangwan7 Рік тому +1

    Hi thanks for video. Do you find this PHE blockage on central heating close loop side or cold to hot fresh water side also. Can this unblocking be done on fire main heatexhanger side. does main HE ever get blocked providing there is an inhibitor in the close loop?

    • @advancedboilertraining
      @advancedboilertraining  Рік тому

      So usually the blockage is on the CH side of the plate. I’ve never seen the HW side blocked up
      So yeah, if the system is really dirty then the main heat exchanger can also get blocked

    • @davelaye7003
      @davelaye7003 5 днів тому +1

      always on the hot water side here in London. its thew calcium carbonate build-up that stops heat transfer, the harder the water area, the more common this is.

  • @digitaria
    @digitaria 2 місяці тому

    I didn’t see a filter and the discharge bottle wasn’t primed, apart from that great job.

  • @karlsanderson8127
    @karlsanderson8127 6 місяців тому

    I need to do this on my glow worm the part was only £40 so going to give it ago changing it

  • @shafiqmustafa2777
    @shafiqmustafa2777 8 місяців тому

    I have the problem, will need to buy a new plate, £160 + labour cost, do you work in London

  • @damiebgibbons5710
    @damiebgibbons5710 Рік тому

    Morning great video , have a problem like yours , the thing with my vessmann is that the boiler is not firing on hot water, there is a full flow out of the hot tap , checked the 3 port vale and it is moving freely, could it be a stat or the heat exchanger thanks

    • @Dee-iy4ot
      @Dee-iy4ot 8 місяців тому

      not firing, is nothing like the problem in this video!!

    • @davelaye7003
      @davelaye7003 5 днів тому

      the hall sensor

  • @juniorjassal1995
    @juniorjassal1995 Рік тому

    Would you always replace the 4 o-rings on the manifolds when taking out the plate?

  • @joshd790
    @joshd790 Рік тому +1

    Good video mate shame it was a only a 7 minute one

  • @tomdutton4673
    @tomdutton4673 Рік тому +2

    What spirit salts do you use ?

  • @andrewhull6776
    @andrewhull6776 Рік тому

    Smart guy

  • @raj080288
    @raj080288 7 місяців тому

    If there is a pin hole and you say the pressure in the boiler will always be going up, would that be when the heating is on or even without the heating being turned on?

  • @DaveInBridport
    @DaveInBridport Рік тому +1

    That HCl is evil stuff! Need to be SO careful.

  • @richardhodgson7443
    @richardhodgson7443 Рік тому +1

    Will the plate only go in one way? Cheers

  • @trevjones4564
    @trevjones4564 Рік тому

    Thanks top video

  • @andrejrockshox
    @andrejrockshox Рік тому

    what is the price of new plate?

  • @vladimird3575
    @vladimird3575 Рік тому +1

    What chemical do you use to clean it?

  • @ozwellalford5015
    @ozwellalford5015 Рік тому +1

    Nyc Job

  • @christophersherratt7299
    @christophersherratt7299 9 місяців тому

    What is spirit salts

  • @mcDarkD
    @mcDarkD 4 місяці тому

    a ballfix valve to fill the boiler no checkvalve. i do wonder why the plate was that clogged. not. why am i not surprised..

  • @dreamkiss
    @dreamkiss 6 днів тому +1

    Does anyone what chemicals have been used?

    • @advancedboilertraining
      @advancedboilertraining  6 днів тому +1

      Spirits of salts

    • @dreamkiss
      @dreamkiss 6 днів тому

      @@advancedboilertraining thanks just had a look Selco sells this only a few pounds.

  • @marty3553
    @marty3553 2 місяці тому

    Where to get spirits of salts ?

  • @jorgetristany
    @jorgetristany 8 місяців тому

    Name of liquid to clean the exchanger?

  • @cippollino83
    @cippollino83 Рік тому +1

    Where do you buy spirit of salts?

  • @marcjohndavies8244
    @marcjohndavies8244 5 місяців тому

    Is it legal to flush that down the drain???

    • @kirren79
      @kirren79 5 місяців тому

      If it's a soak away drain, that's really not good for the environment, standard drain it's okay, personally I would just fit a new plate and have old plate recycled. Plus it a lot safer, did you hear him cough due to the flumes 😷

  • @maddawglodbrock1380
    @maddawglodbrock1380 4 місяці тому +1

    It’s a common fault with these boilers its the 2 black rubber pipes that run up the side they corrode and the rubber falls off and blocks up the plate heat exchanger

    • @davelaye7003
      @davelaye7003 5 днів тому

      terrible design, i would never install or advise to fit a Viessmann. as bad as Baxi

    • @maddawglodbrock1380
      @maddawglodbrock1380 5 днів тому +1

      Worst thing was when you tried to claim on the warranty they would try blame it on old system pipe work saying it needed to be flushed I got wise to it when I’d installed a few new systems new everything and it would happen a few weeks later that’s why I never fit them any more especially when they don’t fix their faults and blame the installer that’s why I stick with Worcester most of the time there customer service is great and they fix there faults if one occurs

  • @davebayliss3142
    @davebayliss3142 8 місяців тому

    Spirit of salts will rock the inside of that plate exchanger doesn’t matter how much water you flush through afterwards

  • @mehmetmetin8783
    @mehmetmetin8783 8 місяців тому

    👍🧿👏

  • @gabipaduraru2004
    @gabipaduraru2004 13 днів тому

    After cleaning with HCl you must wash with a baking soda solution

  • @richardpool481
    @richardpool481 5 місяців тому

    If you’re doing the shower hoaky coaky replace it don’t bodge it