Standing pilots, combination gas valves, Thermocouples.

Поділитися
Вставка
  • Опубліковано 18 жов 2024
  • We demonstrate different types of standing Pilot gas valves. Heat motor/ time delays and solenoid / immediate open.
    We show thermocouple operation and how to read millivolts.
    We also show manufactured home valves.

КОМЕНТАРІ • 94

  • @mattgallagher9827
    @mattgallagher9827 Рік тому +4

    Agreed! You're a great teacher! I figured out the idea of redundancy, from watching, it seems, because the pilot solenoid becomes back up for main gas burner, which is my best way of explaining. it. Thanks again!

  • @DindoNuffin-e2x
    @DindoNuffin-e2x 3 роки тому +8

    Best explanation of my furnace. Thanks! You are a great teacher.

  • @krelb
    @krelb 9 місяців тому +1

    Best explanation ever. Thanks.

  • @UltraHydrophobiccoat
    @UltraHydrophobiccoat 3 роки тому +4

    The best explanations of the most commonly used gas combustion systems 👍🏻

  • @carlosportilla7634
    @carlosportilla7634 Рік тому +1

    Congrats. Real life teaching thanks

  • @clearsky2546
    @clearsky2546 Місяць тому

    Best explanation I found😊

  • @REFRITEKREFRIGERACION
    @REFRITEKREFRIGERACION 3 роки тому +3

    Enjoy all your videos, Nice video, very informative. Thank you.

  • @gastjjs
    @gastjjs Рік тому +1

    Excelent explanation, thank you very much

  • @ParabellumX
    @ParabellumX Рік тому +1

    Great video, BananaMan!
    Thanks! 😊

  • @dominiquepierre916
    @dominiquepierre916 2 роки тому +1

    Very great video ;
    You are the best instructor I have ever seen in my life ,
    I will be very grateful if some day make video of Career modulating furnace .
    I set modulating gas valve (high and low ) according to manual but still customers calls back and I find code 33 (over heat )
    Filter is clean:Ac coil is clean .
    This career furnace is like nightmare for me;and I am starting to dislike this furnace "
    The manual of career infinity does not explain very good.
    Please make video and especially those dip switches 🙏🙏
    Thanks a lot .

    • @love2hvac
      @love2hvac  2 роки тому

      I want to do one for modulating but I don't yet have access to one.
      Overheat is usually an airflow issue. Check the static pressure on the air side and you will probably find the static pressure is too high.
      I have my opinions on modulating furnaces I will do a video on after I show the operation of one.

    • @dominiquepierre916
      @dominiquepierre916 2 роки тому +1

      @@love2hvac
      Thank you very much.

  • @motionsick
    @motionsick 11 місяців тому

    I love youtube. Thanks man.

  • @PatIreland
    @PatIreland 2 роки тому +1

    ALL your vids are simply GREAT.

  • @BigmoRivera
    @BigmoRivera 2 роки тому +2

    Great Job Nicely Done 👍🏽⚡️🔥

  • @chesstime356
    @chesstime356 3 роки тому +4

    Very nice thank you professor.

  • @1983gubsy
    @1983gubsy 2 роки тому +2

    Very well detailed video

  • @chesstime356
    @chesstime356 3 роки тому +1

    Always watch your video they’re nice 👍

  • @patrickmurphy7978
    @patrickmurphy7978 11 місяців тому +1

    Truly appreciate you taking the time to produce these great videos. Keep up the good work! I've a question as well, the spec sheet for my gas valve indicates it operates with 24 volts DC, yet when I measure the "opening" voltage applied from the controller, it's 24 volts AC. Do 24v gas valve's solenoids work with both AC and DC voltage? Will utilizing AC voltage for the valve likely be detrimental in the long term? Thanks

    • @love2hvac
      @love2hvac  11 місяців тому

      Thanks Patrick
      Most of the gas valves today operate on 24V AC.
      Some really old package units had some 120 and 240v coils that are not allowed anymore for safety.
      Some wall and floor furnaces use a millivolt DV gas valve and use a thermopile to create the voltage from the pilot to operate on.
      Some of the valves today have a switch and a mini control board inside. It's possible the board is a rectifier converting AC to DC so it would work with either. Possible, not confirmed.
      As for 24v DC I do not know. I can't remember seeing that. I will have to take a look and see what the labels show and get back with you.

  • @lazmotron
    @lazmotron 11 місяців тому

    Great video. If I were to replace the pilot from the gas valve, with a new pilot, do I use regular pipe joint/fitting compound.

  • @abhiescorts
    @abhiescorts 2 роки тому +1

    completely understood the thermocoupler function. i am facing a problem where gas donot cut off inspite of thermostat in workung condition.

  • @freemanfanmao
    @freemanfanmao 2 роки тому +3

    Really great vid, thanks a lot. However just one question, in the vid you used a lighter to light up the pilot, in the actual furnace what triggers the spark?

    • @love2hvac
      @love2hvac  2 роки тому +2

      These pilots are manual light and they stand or burn constantly. There are kits available to convert a standing pilot to intermittent.

  • @kattithegreat1737
    @kattithegreat1737 Рік тому

    Thanks for the information

  • @RegieWinn
    @RegieWinn 11 місяців тому

    Thanks for laying out the working parts of the furnace in plain site, its much easier to see whats going on. I have a hanging garage furnace that dates pre 90's that has had the name of the unit removed before I got it so I'm lost as to know where I can get replacement parts for it. I am in need of a new solenoid as the thermocouple is ok (thanks for your info on how to test). the only number I can see is on the solenoid housing and that is 807-78 the only words on the housing is "reset button" and has an arrow pointing to the red button at bottom of housing. I have been unable to locate any parts that look like what i have. Would you have any idea that would deal in old furnace parts? Thank you.

  • @kenny-Poo
    @kenny-Poo 2 роки тому +1

    Great explanation of the thermocouple and the pilot side of the valve but how does the main valve open? Where does the 24 volts come from ? My gas fireplace pilot is lit but the main valve does not open. Why?

    • @love2hvac
      @love2hvac  2 роки тому

      There are 2 valves, the pilot holds open one valve, then the second valve is controlled by the 24v of the furnace.
      On a gas fireplace there are many different ways. Some use a thermopile instead of a thermocouple to creat aditinal voltage for a switch or thermostat, some use manual valves, some use DC and some use 24v with a controller.
      I have not worked on a gas fireplace in about 10 years so I'm not sure all the different methods used today.

  • @samersarah957
    @samersarah957 2 роки тому +1

    Very informative video Ty thank you for the time you spend it. Q: The thermocouple will generate a small amount of voltages so this volt should be AC or DC? And is it contain a coil to pull the valve? Thankfully.🌳🌺

    • @leversforever9748
      @leversforever9748 2 роки тому +1

      DC

    • @love2hvac
      @love2hvac  2 роки тому

      It's DC and there is a coil inside the valve just for this. One of the videos I pull the coil out so you can see the operation. I don't remember which one but it will be under the gas heating playlist.

  • @kjlee4890
    @kjlee4890 7 місяців тому +1

    Best video. My boiler pilot is failed . The solenoid (1:30) is failed. Any one know the parts number of it? Where to buy it? I live in Vancouver,B.C. Canada. Thank you.

    • @love2hvac
      @love2hvac  7 місяців тому +1

      You can get a new thermocouple pretty easily
      You can't get just the solinoid, you will have to get the entire combination gas valve.

    • @kjlee4890
      @kjlee4890 7 місяців тому

      Thank you.@@love2hvac

  • @TheGaboni809
    @TheGaboni809 2 роки тому +1

    Hello thanks for the video
    I have the same gas valve and I can't adjust the pilot light. I even bought a new gas valve thinking that there was something wrong with mine and the new one is the same can't adjust the pilot up or down I follow the instructions that came with it, any suggestions. Thanks

    • @love2hvac
      @love2hvac  2 роки тому +1

      There is a separate adjustment for the pilot regulator. It has a smaller cap on it and a smaller adjustment.
      Google the gas valve model and PDF , you might be able to find something.
      Usually it's the pilot orifice that is clogged up. Be careful cleaning it, even a needle can make it too large and too big of a pilot.

    • @TheGaboni809
      @TheGaboni809 2 роки тому +1

      Thanks

  • @warrencorcoran9824
    @warrencorcoran9824 2 роки тому +1

    Very professional voice, well presented. Well spoken, Reach out to manufactures of equipment,, You could do very well monetarily. get an agent or lawyer up front, contingency only ..

  • @lonetraveler5660
    @lonetraveler5660 5 днів тому

    I have a 1940-50’s winter air conditioner, which is forced air furnace. It was working last winter. Now it won’t turn on. It has gas chain not combination valve. I can manually turn it on. I took the pilot out to clean. But there is thermopile. There are two gas lines. One to pilot and one to gas control valve. There are two wires for thermopile, but no thermopile left. I checked it at bottom as well. There are 4 wire connectors, one is G, one is no letter, (the remaining thermopile wires are connected to those connectors. The other are white and yellow. G, W and Y connectors has wire. Does the polarity of thermopile matters. I tried a thermopile from water heater. It won’t turn on by itself. If i manually turn it on. It will reignite for couple times. But not all the time. What could be wrong. Thank you

  • @Lockandload-nr6tk
    @Lockandload-nr6tk 8 місяців тому

    So , I saw your video and watched a few others, if you don't want to respond, I understand, but here's what I have a 1991 circa Reznor that is in a small garage, it has a standing pilot, the unit has developed a high pitched whistle, I believe it's in the combination gas valve, when I turn the main valve toward off to see if the pitch will change or stop, the whistle becomes louder and at a higher pitch, when I open the main all the way back open, the whistle stops for a moment but starts to whistle again. The whistle is at the back, behind where the pilot is , this is the first year that the unit has been used in the last three years, the whistle wasn't there when it was last used, the pilot was on though through those three years, the pilot burns clean and blue, the furnace heats fine, other than the loud whistle which sets off my tinnitus. I haven't been able to find anyone that has an idea. The burners are blue also.

    • @Lockandload-nr6tk
      @Lockandload-nr6tk 8 місяців тому +1

      By the way, thank you for the videos, very informative.

    • @love2hvac
      @love2hvac  8 місяців тому +1

      Without being there I cannot be 100% certain, it's likely the diaphragm inside the gas valve is damaged. It can be stuck on one side or it can have rip in it that acts like a feed of a musical instrument.
      It can be burning blue but still not burning correctly. Rachel Kaiser did a great presentation at the HVAC school symposium this year about that.
      My bigger concern is if it's fully shutting off. It can be leaking gas by until it builds up enough for a little back draft. You may not notice it, but it can get worse over time.
      You can look for a replacement gas valve. White Rogers makes a universal kit they also have one with electronic ignition or intermiten pilot, but then again it might be time to look at a newer model heater.
      For shops I like infrared heaters as they direct the heat in objects and people instead of air.
      I'm some cases a big can clog an orifice or the burner tube and also make a similar noise.
      What ever you use get a low level CO monitor (not alarm) so you can know what's happening inside.
      Good luck!

    • @Lockandload-nr6tk
      @Lockandload-nr6tk 8 місяців тому

      Found the problem, although the jets were clean at the tips and I ran a pipe cleaner back through them, it hasn't solved the problem, so I held a wide standard/straight screwdriver over one jet out of the three, each jet changed the pitch of the whistle until I got to the last of the three, the whistle stpped, I removed the jets only to find a thin carbon deposit inside the jet, with everything off, I used compressed air through the rail, and chemtool/carburetor cleaner on the jets, I let the jets soak for a few minutes in the cleaner then used the brass pipe cleaner again, put everything together, opened and closed the combination valve and gas supply valve a few times to make sure any blockages might flush with the pressure, then lit the pilot, then turned on the power and waited, ran through the cycle completely, No Whistle :)
      Thank you again for your videos and response. Very informative.

  • @willisdelacruz6901
    @willisdelacruz6901 11 місяців тому

    My thermocouple keeps the flame lit. But pilot tubes go off after 1-5 minutes after I do the recommended steps to relight it. Any suggestions?

  • @1971omi
    @1971omi Рік тому

    Ty you mentioned 24 volts for combination gas valve. Where's the transformer for that to get that voltage? My understanding on standing pilot was, main gas valve gets power from pilot once it is lit. Wall heater don't have transformer and we have 3 spade on gas valve. 1 is for pilot 2bd is TH/TP. 3rd is for gas valve to open.

    • @love2hvac
      @love2hvac  Рік тому

      In gas furnace the same transformer that powers the 24v system. R- tstat, comes back as W through the safeties and ( and control board on new ones) then to the combination gas valve. There thermocouple uses 30 millivolts only to hold the pilot coil in the valve, separate system.
      Wall furnaces are different. Well some have transformers but most do not.
      The wall furnaces don't use a thermocouple they use a Thermopile.
      The thermopile creates about 650 to 850 millivolts. This is enough to run to a millivolt thermostat, through some normally closed safeties and to energize the main valve on the wall furnace. It also holds open the pilot valve.
      Because there is more load and longer wire runs a thermocouple does not work so the thermopile takes over.

  • @robertcherry4971
    @robertcherry4971 2 роки тому +2

    You can check the millivolts with out the adapter.Place one lead on aluminum nub. Other on copper tube snd you will read the millivolts when thermocouple is heated.Just disconnect nub from gas valve light pilot hold in and check.

    • @love2hvac
      @love2hvac  2 роки тому +1

      Yes they are great. One of these videos I think I showed it. I can't remember.
      I did not know about the adapter. Place. I will check them out.

  • @dene1196
    @dene1196 Рік тому

    Is there a quick method to determine if gas valve is defective? How can i test it to find out if it works the way it should?

  • @rojobandito318
    @rojobandito318 3 роки тому +1

    Thanks Ty

  • @RB-nm3ko
    @RB-nm3ko 8 місяців тому

    While pressing PILOT, eventually the solenoid keeps the pilot light valve open. So what then does the ON setting do? I'm trying to follow how the ON valve is first but the pilot light valve opens first? Thanks

    • @love2hvac
      @love2hvac  8 місяців тому

      Internal piping.
      The pilot valve solinoid stops or allows gas to flow to any part of the gas valve. Once the pilot valve is open it allows gas to flow to the next chamber. With the knob turned to the on positions it continues to allow the gas to flow to get another chamber where the main solenoid controls the gas flow with a call for heat.
      When the knob is turned off, it closes the paths to all the chambers including the pilot valve.

  • @carlosportilla7634
    @carlosportilla7634 Рік тому

    I have ? Sr. Why my gas valve don open when I push the pilot down? Do. No smell gas any idea? Thanks again

    • @love2hvac
      @love2hvac  Рік тому

      It will only open to the pilot tube. Often you will not smell gas be used it's so small.
      If it will not light the pilot with the pilot knob used it could be:
      A: pilot tube orifice clogged up
      B: No gas to the house
      C: no gas to the unit (gas shutoff closed)
      D: gas pipe rusted or corroded u.
      E: inlet screen to the gas valve clogged up
      F: gas diaphragm in the gas valve bad
      G: pilot chamber corrected inside valve
      H: pilot regulator out of adjustment
      I: shaft or knob form the inside is broken
      J: Pilot tube kinked
      K: Pilot tube or conectirs leaking

  • @Guyhakverdi
    @Guyhakverdi 2 роки тому +1

    Is it possible to have a bad thermocouple that can still send 30 milivolts and can’t hold the solenoid ?

    • @love2hvac
      @love2hvac  2 роки тому

      Yes, it's good to check under load. I have the starter that slows me to do that.
      Now if your getting 30 connected and it's still not opening, then there is a problems
      1 with the valve
      2 with an external limit
      3 wiring connection of the external limit
      4 the connection of the thermocouple /valve

  • @mark.r8900
    @mark.r8900 2 роки тому +1

    Is it normal for the pilot hood to glow red hot? Thanks

    • @love2hvac
      @love2hvac  2 роки тому

      No, something is wrong

  • @alacran1986
    @alacran1986 2 роки тому

    Can you demo a slow open and regular gas valve on this set up or side by side?

  • @INTERNA9
    @INTERNA9 2 роки тому +1

    wow!

  • @mark.r8900
    @mark.r8900 2 роки тому

    Hi, i hear a clicking sound from gas valve when thermostat calls for heat. But the pilot is off. Does this clicking sound means that the gas valve is being energized and gas is going to burner even though the pilot is off? Thanks

    • @love2hvac
      @love2hvac  2 роки тому

      no the clicking is most likely a solenoid engaging, but gas cannot flow unless the pilot solenoid is also open.
      2 solenoids, they both have to be open for gas to flow

  • @sanjesengineering3143
    @sanjesengineering3143 4 місяці тому

    Whats the title and author of the book? thanks

  • @RyanRamtahal-u1n
    @RyanRamtahal-u1n 9 місяців тому

    I have a Pennco boiler. it doesn't spark to light reding code 15 B

  • @dexenationgracey1979
    @dexenationgracey1979 3 роки тому

    I'm starting to think I just have a dirty pilot because I can't get it to light at all. I sprayed soot remover on the pilot and thermocouple then used a wire brush to clean off the soot. I'll see if that worked. I don't think they make those kinds of pilots anymore.

  • @mark.r8900
    @mark.r8900 2 роки тому

    Would gas flow to main burner if 24vac is applied to gas valve with the pilot off? Thanks

    • @love2hvac
      @love2hvac  2 роки тому

      No, gas would not flow to the main burner with the pilot off even with 24v applied.

    • @mark.r8900
      @mark.r8900 2 роки тому +1

      Thank you

  • @barronweir123
    @barronweir123 2 роки тому +1

    When I see these I recommend replacement. I won't touch them had someone lied about why his shop caught on fire....it was one of these old things its like 40 years old most the time. He told me a drunk caught his business on fire. But on further investigation it's because he refuses to replace old furnaces so he can work on them himself. He says new furnaces "have too many electronics" good riddance to this person I did not go back

    • @love2hvac
      @love2hvac  2 роки тому

      There are some I will service but its a safety and Liability issue.

  • @Projects.mark.108
    @Projects.mark.108 2 роки тому

    Kindly tell me how I would be able to daisy chain 4 pilots so I can build this off grid heater... Thank you very much

    • @love2hvac
      @love2hvac  2 роки тому +1

      The problem would be the orifice size inside the gas valve. It most likely would not allow enough flow.
      What type of heater are you trying to build? I can't see needing more than 1 pilot for anything.

    • @Projects.mark.108
      @Projects.mark.108 2 роки тому

      @@love2hvac check out this video, would like to build with four pilots and copper heating element pipe ua-cam.com/video/6ZnayOUQN28/v-deo.html

    • @Projects.mark.108
      @Projects.mark.108 2 роки тому

      @@love2hvac did you get a chance to check out the video?

    • @love2hvac
      @love2hvac  2 роки тому

      I don't see a video link

    • @Projects.mark.108
      @Projects.mark.108 2 роки тому

      @@love2hvac ua-cam.com/video/6ZnayOUQN28/v-deo.html

  • @garybrown7044
    @garybrown7044 3 роки тому +1

    standing pilots are alive & well in water heaters & 'vent-free" space heaters.

    • @love2hvac
      @love2hvac  3 роки тому +1

      Thank you for the comment.
      Water heaters are a diffrent and some animal. I will leave potable water to the pipefitters and will make another series for hydronics.
      As for ventless heaters, they are an Indoor Air Quality nightmare. An air monitor reports with and without their operation quickly convense customers it's time to upgrade.

    • @garybrown7044
      @garybrown7044 3 роки тому

      @@love2hvac i wish the mfgrs. of "ventless" heaters would make a vented type. i would gladly run b-vent for safetys sake. as american gas valves use a universal thermocouple, the overseas valves use different ones that are next to impossible to obtain.

  • @nunyabusiness6746
    @nunyabusiness6746 3 роки тому +1

    The amount of gas that will leak on a standing pilot with the proper type of gas supply isn’t that much if you loose the flame. As far as reliability goes, my furnace is this style and i’ve been here since 1987 and i’ve never had to replace the thermocouple, no lie, now how many ceramic igniters do you think you would go thru in that time 8, 10 ? Another plus for a standing pilot system, other than its simplicity, is many homes have their heat in a damp cellar and the continuous pilot keeps the heat exchanger dry and rust free in the off season. Now don’t get me wrong, i’m a big fan of electronics, in fact i’m also an electronics technician.

    • @love2hvac
      @love2hvac  3 роки тому +1

      My concern is the bigger picture of house pressurization and depressurization. If a person first took a class from David Richardson or Jim Davis with National Comfort Institute about Carbon Monoxide and the whole home picture I would be more inclined. I will make some videos this winter about that issue. A natural draft furnace is the most susceptible to the pressure changes. Even a windy day can comply change the air properties and cause carbon monoxide poisoning. So many people get CO o poisoning every year and never even know it. A pilot furnace is simple but the operation in a home becomes very complex. That class will really open your eyes to the bigger picture.

    • @robertcherry4971
      @robertcherry4971 2 роки тому

      You would not compare the thermocouple to the igniter by the way you would compare it with the flame sensor. The problem is they are inefficient,not very safe.and are no longer being made.The standing pilot type furnace is of the past . Evolve or get left behind.

  • @aifrisyad7491
    @aifrisyad7491 2 роки тому

    can i install ekternal elektric igniter modul to light the pilot?

    • @love2hvac
      @love2hvac  2 роки тому +1

      I used a honey well or white rogers brand ignitor but it requires replacing the combination gas valve, the pilot assembly and installing a control board that comes with the kit.

    • @aifrisyad7491
      @aifrisyad7491 2 роки тому

      @@love2hvac thanks man

  • @danielstevens5925
    @danielstevens5925 2 роки тому

    nothing wrong with standing polite other than the waste in the summer( which i just turn off the gas to the furnace in summer)
    they are perfectly safe
    simply change out exhausted worn components

    • @love2hvac
      @love2hvac  2 роки тому +1

      3 part problem.
      1 they have not made a standing pilot furnace in 29 years. The heat exchanger, the main part of that unit is aged, and worn. Your talking a lot of expansion and contraction, a lot of rust and a risk of cracks.
      2 natural draft. Because they are natural draft and rely on natruak convection, there is a much greater risk of back crafting CO into the home. This is magnified with better windows, roofing, insulation siding and all the modern ways people seal a home. Just a change in the wind, a bathroom fan, kitchen exhaust or clothes dryer will put the house in negative pressure and the CO will be pulled into the home.
      3 they had limited safety featured. I have rewired many of them over the years. The flame back crafts and melts all the comments. There was nothing to ensure proper draft, or flame roll out.
      I like the old trucks with manual windows, manual locks, manual transmission, solid front axle and built solid.
      However those trucks I live have not been made is some time and age. For the general population they are not as fuel efficient, comfortable or as safe.
      The air bag, the anti lock breaks, the frame that's made to buckle selling the engine below the driver, the dash designed to not take off the knee caps are big safety improvements for the majority. The lighter weight, arrow dynamics, and fuel injection systems make them more fuel efficient. All of these things take priority over the few like me that appreciated the old system.

  • @cliffordbuckman3672
    @cliffordbuckman3672 2 роки тому +1

    i have this one chill on the negativity bro

  • @juliocv719
    @juliocv719 3 роки тому +1

    USE A REAL MANS METER DUDE

    • @love2hvac
      @love2hvac  3 роки тому

      I have and use Fluke, Fieldpiece, UEI, Klein, Simpson and others. I'm not brand loyal.