    is 2" pipe work for aluminum or just for cooper? i ask because if it is aluminum is not gonna be too tight for conduit wires 2.0?..is a just a question i would like to know...nice work nice and clean.

    • @RealPropertyShow
      @RealPropertyShow  Місяць тому

      You should be able to fit up to Qty 5 - 2/0 wires in a 2” Schedule 40 electrical conduit. I would recommend checking the most current NEC code that has been adopted in your local area to confirm you are meeting code requirements. Thanks for the question!