is 2" pipe work for aluminum or just for cooper? i ask because if it is aluminum is not gonna be too tight for conduit wires 2.0?..is a just a question i would like to know...nice work nice and clean.
You should be able to fit up to Qty 5 - 2/0 wires in a 2” Schedule 40 electrical conduit. I would recommend checking the most current NEC code that has been adopted in your local area to confirm you are meeting code requirements. Thanks for the question!
is 2" pipe work for aluminum or just for cooper? i ask because if it is aluminum is not gonna be too tight for conduit wires 2.0?..is a just a question i would like to know...nice work nice and clean.
You should be able to fit up to Qty 5 - 2/0 wires in a 2” Schedule 40 electrical conduit. I would recommend checking the most current NEC code that has been adopted in your local area to confirm you are meeting code requirements. Thanks for the question!