How to troubleshoot a mini split air conditioner

Поділитися
Вставка
  • Опубліковано 7 вер 2024

КОМЕНТАРІ • 252

  • @sleek55044
    @sleek55044 4 роки тому +2

    This facility is definitely an MMJ Grow, interesting way to hide the outdoor condensing units.What a cluster F on those linesets, brazing and flares oh my! Good way to heat the building in the winter time though! Nice work getting her in order!

  • @kimojon9665
    @kimojon9665 4 роки тому +1

    Treat it like an ice machine! Love it. Came here for the mini split info, ended up loving the bonus footage of the beautiful surfing!!! Nice.

  • @tcphvacr9950
    @tcphvacr9950 4 роки тому +24

    Never put a multi head system in where one room has to always stay cold. The others will never be happy. Put in a one to one for the cold room, and then a multi for the others. Good advice, always weigh the charge, because you're chasing your tail if you don't. Guys with gauges-just don't. Put them away, get a stub gauge to check pressures when diagnosing transducers, but otherwise, don't. Gauges on inverters are useless. You don't know what speed they're running at at any given time.

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому +2

      Excellent point Tom.

    • @honkwok5489
      @honkwok5489 4 роки тому +1

      sound like salesperson selling big dram for multi head when install. i think all independent system will not cost too much more multi head.

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому

      Eric M Eric did u ever do a video of your system finished. I remember seeing the piping and it was nice.

    • @peepeepoopoo1399
      @peepeepoopoo1399 3 роки тому

      Is there no way to manually have them run at full capacity to check SH?

    • @seanmathews1826
      @seanmathews1826 2 роки тому

      @@peepeepoopoo1399 Not really. I have heard from multiple sources that all you can do is weigh in the factory charge and that's it.

  • @stephenmarrone9847
    @stephenmarrone9847 Рік тому

    How do you clean the condenser coil. Did The installer provide access doors on the ductwork? Also as mentioned the head units need a total Yearly maintenance power washing using the ductless mini split bib Cleaning kit. This is an excellent source of information, well done. 45+ years in the HVAC industry And I'm still learning. Never stop Learning.

  • @MrHVAC503
    @MrHVAC503 4 роки тому +1

    Great job showing the right way to deal with the refrigerant side of mini splits. Appreciate your videos brohamm

  • @Clasped003
    @Clasped003 3 роки тому +1

    This knowledge is invaluable. For real you have helped me out of so many future problems with this. Wishing you the best dave. Been following you on other accounts, etc for 4+ years. Youre an OG
    If i am ever down in santa cruz i owe you a beer and a dinner.

    • @NorCal-refrigeration
      @NorCal-refrigeration  3 роки тому

      Thanks 🙏🏻

    • @nopenope8364
      @nopenope8364 3 роки тому

      @@NorCal-refrigeration Hey, i have a question.
      I have a Split Air con and when I turn it on, it just makes a weird noise and does not even blow air, it just stays on with that weird noise, do you know what the problem might be?

  • @shine-cg9uf
    @shine-cg9uf 4 роки тому

    U have a blessed life. The opening/ending of video was so peaceful to watch. I wish i was on a beach instead of on my couch with no $$. Thankyou for sharing.

    • @Clasped003
      @Clasped003 3 роки тому

      Dawg learn to be an hvac tech and youll be good. Theres a real future in this career. We need techs

  • @YodaPala
    @YodaPala 4 роки тому +14

    THESE are the videos we love😃

  • @markcutshall833
    @markcutshall833 2 роки тому

    AWESOME info, you explained that very well. I'm a second year HVAC/R student and doing some work to make it through school. Thankyou for the help, much appreciated !

  • @sorn32837
    @sorn32837 4 роки тому

    That's Quest is one heck of an expensive dehumidifier, but wrote ever penny.. great info brother. Been lost in space with them mini splits till I came across your channel 👍🏻

  • @jeffreykubiak5126
    @jeffreykubiak5126 4 роки тому

    Thanks Norcal Dave ! New job heard be working on a lot of mini splits and VRF systems VRFs never worked on! I'm amazed how the industry gets better tools for service man long way from the 80s and 90s beer can cold!

  • @FireandFrostHVAC
    @FireandFrostHVAC 4 роки тому

    Looks like a gas and go bandit serviced it several times... “the machine isn’t working, better add some gas!” Good call to recover and weigh so you know where you’re at. Good video Dave, thanks.

  • @scottk0623
    @scottk0623 4 роки тому

    Dave your spot on with that approach.👍I work on a lot of Mitsubishi mini splits and I see a bunch of “gas & go” jobs. I always weigh it out and start over. I have been doing this along time and have never found a better way to get back to square one. I HOPE some guys listen. Thanks. The thumbs down guy is a “super tech” lol. The 600psi for 24 hr. is still the suggested procedure as far as I know, that ain’t gunna happen.

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому +1

      I had to do it at the hospital. State inspector was on his game.

  • @RichGT350r
    @RichGT350r 4 роки тому +9

    “Smurf Boner”! Classic!
    I couldn’t agree more, recover the charge, test and recharge. Now you know where your at and not chasing others mistakes! Good advise! Start with the basics! Thanks Dave! 👍

  • @HAGICASA
    @HAGICASA 4 роки тому

    temp difference at the evap should be between 10 to 14 cooling mode ..after the right charge and vacuum .great video ...as usual

  • @heavydiesel
    @heavydiesel 4 роки тому +1

    Additional charge here is in grams per meter, makes it easier to work out I think! One of the worst ones I've seen was 26kg overcharged, had some fun measuring pipe run as it was three stories up and had to follow pipes above ceiling tiles, killed the original compressor!

  • @airfromaboveairconditionin8754

    Perfect approach. Love the detailed explanation 💪

  • @mallow399
    @mallow399 4 роки тому

    You da man daver! Those cant be troubleshot by pressures as they are all inverter. I have ran into a couple that you can put into a 100% capacity run mode. But ya exactly like you did ! Awesome video. Can confirm your mits pressure of 600 also. They also want under 300 microns on the vaccum too. I went 3 years ago.

  • @dennisnoone7427
    @dennisnoone7427 4 роки тому +10

    It was just slightly topped off to compensate for some future leaks

  • @acservicetechchannel
    @acservicetechchannel 4 роки тому +11

    Absolutely fantastic job! Love it, thanks!

  • @mhm8477
    @mhm8477 4 роки тому

    I love yours videos

  • @hvacgabe5889
    @hvacgabe5889 4 роки тому

    Nice one dave!👍 I once worked with a guy who would say "when in doubt, flood it out" maybe he was there before you.😂😂😂😂

  • @ntsecrets
    @ntsecrets 4 роки тому

    That overcharge is impressive. The suction ports are In circuit with the EXV so you can't rely on that pressure to charge. Also - on the T-stat if you hold down COPY/Follow me for 5 seconds it might show you all the temp sensors reading in C. Thats a Nor-cal Fan Tip of the Day!

    • @ntsecrets
      @ntsecrets 4 роки тому

      On top of that the factory charge assumes you have all 5 circuits in use with usually a max of 25 ft line set on each. So that unit was wayyyyyy overcharged!

  • @unkomikey1494
    @unkomikey1494 4 роки тому

    I trouble shoot mini splits all day everyday here in Hawaii and about 99.9999999% of them get overcharged by someone sometime in its life.. frigin ridiculous. everyone running around with a set of gauges just wants to gas everything up and go. the worst are city multi units because they will just eat gas and if they are trying to charge by pressure it will never move and they just keep charging. I've seen some that are almost 20lbs overcharged crazy. But good job man! Always enjoy your videos!!

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому

      What’s the most common issue you come across on these?

    • @unkomikey1494
      @unkomikey1494 4 роки тому

      Nor-Cal Refrigeration & H.V.A.C evap coil leaks and geckos frying the boards is a close battle for most common problem out here!

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому

      Unkomikey leaky coils here also.

  • @BurnabyCorey
    @BurnabyCorey 4 роки тому

    Yes, came across this few times too. Great job once again Nor Cal Dave!

  • @frankmashione139
    @frankmashione139 4 роки тому

    Solid diagnostic strategy

  • @miguelrasmijn4491
    @miguelrasmijn4491 4 роки тому +1

    Hello from Aruba exellent work

  • @PaulHVAC1
    @PaulHVAC1 3 роки тому

    Dave that was a excellent informative video...real field common sense. Keep up the great content. Cheers!!

  • @hvacknowledgechannel1621
    @hvacknowledgechannel1621 4 роки тому +1

    Gud job in this location it will create leak always these types of place always tripping or leakage call keep making more vdo sty in tch frnd

  • @bradcapps5684
    @bradcapps5684 2 роки тому

    Este tipo es el mejor de UA-cam para aprender mis amigos sin duda.

  • @chewy2804
    @chewy2804 3 роки тому

    I work at a property that has close to 700 of these condensers. I always recover the charge. I run into systems that are overcharged all the time. Coworkers in a hurry “topping it off” I pulled 6 lbs out of a 1 1/2 ton that only holds 3 lbs a few days ago.
    The modes issue we run into all the time in spring and fall. It’s hard to get tenants to understand that all rooms have to be set to the same mode ( all on cool, or all on heat )

  • @FlyEaglesFly19111
    @FlyEaglesFly19111 4 роки тому

    I have an Apion twin.. it rocks and is pretty light weight. Wow two ilunits worth of charge. Thirdly make a case to clean those blower moto wheels. If they pack with enough dust it throws off the motor to think it's running in high speed when it's really in low. I would say those motor measure resistance and this may be happening. Lock box the #1stat this way it cannot be messed with or lock out the stat itself. Be safe brother Dave..I'm late fue to the draft...woooooo speed kills

  • @terrygym7667
    @terrygym7667 Рік тому

    Do you always put the refrigerant back into a system I’ve been using new refrigerant because I worry about from the previous technicians.
    And should we always change the refrigerant when you do a compressor.
    Video is good hi attention to detail.
    I have a 3 head Carrier at a customers house and tech support thought the eev was bad and told me to pull back into the condenser and switch from a to b head port and now there is an e3 communication error and the wording is correct the other heads are working tech support is closed and i really want to get it going for them.

  • @ApartmentMaintenance
    @ApartmentMaintenance 4 роки тому

    Nice work, learned something new on approaching this kind of setup & a ice machine. 👍👍👍👍

  • @Heavy_metal_rulez
    @Heavy_metal_rulez 4 роки тому +1

    Learned quite a bit about these multi zone systems in just a few minutes from you big Dave! And you are correct about cranking these up to 600 psi for 24 hours. Thats what the Samsung reps told us to do

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому +1

      I never forgot that. Had to by a regulator to get to 600. Hospital inspector checked that one they don’t miss to many specs.

    • @Heavy_metal_rulez
      @Heavy_metal_rulez 4 роки тому

      Yea we had to do the same. Kind of expensive for those ones

  • @tobybakerbakerheatingcooli6604
    @tobybakerbakerheatingcooli6604 4 роки тому

    I agree. They called Mr Nor-Cal because the installing company/person,just added gas. Want it colder..Ok...I will add the refrigerant..hahaha. I do the same thing if its not my install. You almost un install it ,to reinstall it correctly to know your charge is to factory spec. I tell the customer that this may take longer,but its the only way to make it right.Start at a solid base line. As all ways Great Work Dave

  • @TheGgin
    @TheGgin 4 роки тому

    Nice Surf'n shots! Great diagnoses and fix, but you forgot to look for that "hidden" receiver they retrofitted into the system LOL :-)

  • @Hvacmania
    @Hvacmania Рік тому +1

    If it was overcharged that bad ,
    Doesn't that slug the compressor?

  • @stevem9629
    @stevem9629 3 роки тому

    You nailed it Dave! Nice

  • @biblebloopers946
    @biblebloopers946 2 роки тому

    You know you can recover it a lot quicker if you would have hooked it up to the blue suction port on the recovery tank and flipped it upside down

  • @RobertL78
    @RobertL78 4 роки тому

    What some people don't get is that the expansion device is buried inside the condensing unit, so your entire line set is an extension of the evaporator. That's why both lines are insulated and you don't have a true "liquid" line outside of the condensing unit to check.

    • @jmmiller0383
      @jmmiller0383 2 роки тому

      That’s the information I’m looking for! My “liquid line” is cold and sweaty so I was freaked out. Is this true for heat pump style also?

    • @RobertL78
      @RobertL78 2 роки тому +1

      @@jmmiller0383 yes, when in heating mode, both lines will be warm.

    • @jmmiller0383
      @jmmiller0383 2 роки тому

      They say the internet is a waste of time. Appreciate it!

  • @chicoabdallah3944
    @chicoabdallah3944 4 роки тому

    Nice job Dave

  • @ritchieortiz5610
    @ritchieortiz5610 4 роки тому +1

    Good job buddy

  • @dennisbarkley1551
    @dennisbarkley1551 4 роки тому

    Nice way to start the day brother

  • @ntsecrets
    @ntsecrets 4 роки тому +2

    Right away I can tell you thats a Midea re-brand I have the same RS485 thermostat on mine.

  • @OcRefrig
    @OcRefrig 4 роки тому +1

    i Was on a ice o matic 600 lb ice machine the other day ( 12 years old ) not harvesting , That little Z-Man Suction stubby Guage Saved My ass the other day. it Paid for itself on that one Job. Watching suction pull down test, diagnosing a weak compressor would not pull below 28psig , adjusting pressure control cycles to compensate, So much easier than dealing with an app ! analog Rules ! sometimes ! No batteries 🔋, no Digital Lag. , instant response. it Kicked ass ! Suction stubby Guage for the Win ! No Refrigerant loss ! i Wish i Got it all on video But, Customer Was Right there.

  • @coldfinger459sub0
    @coldfinger459sub0 4 роки тому

    Lol 😂 I recognize that type warehouse very floral there. Always see we overcharged or under charged got those good old knew it all guys beer can cold. Because either they’re brand new in the business and no nothing or they been in the business for 30 years and learn by breaking things and they are always right. You are 100% correct. In those wall mounts get tons of mildew buildup on the blower fan blades

    • @coldfinger459sub0
      @coldfinger459sub0 4 роки тому

      Eric M high static pressure air handler are the way to go. You can add multiple Merv 16 20“ x 30“ 5 inch deep pleated filters carbon impregnated. And then on top of that you can add your peroxide generating module inside the airstream. If you want to take it one step further you can either add your humidifier and smart fog system or pezio electric humidifiers. And if you want to make things easier put it outside the room if that’s necessary you could duct in parallel your dehumidification system using the same ducting. With this system you just taking care of killing bacteria killing virus is filtering out mold spores and complete climate control

    • @coldfinger459sub0
      @coldfinger459sub0 4 роки тому

      Eric M yes you’re 100% correct but that was being used in a cannabis grow facility. And guys keep on Insisting on using cheap residential minisplits for a commercial industrial production facility that has extremely high humidity in organic biomatter floating in the air as debris to feed fungus and mold.

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому

      t lech you are correct.

    • @coldfinger459sub0
      @coldfinger459sub0 4 роки тому

      Nor-Cal Refrigeration & H.V.A.C looks like our paths have crossed on customers over there in Santa Cruz.

  • @manuelh8918
    @manuelh8918 4 роки тому

    I had 5 mini split condensers up in a similar set up for a grow warehouse similar like that.

  • @jeffreylentz6699
    @jeffreylentz6699 3 роки тому

    Thank you for the advice and actually works save so much time

  • @mychoclabwinston
    @mychoclabwinston 4 роки тому

    Jealous at watching you watch son and friend surf, what a beautiful spot

  • @vap0rtranz
    @vap0rtranz 4 роки тому

    as a know-nothing home owner, I get the impression that lazy techs just add more refrigerant as a Blind BandAid.
    I hired a Grey-haired independent HVAC tech b/c AC "wasn't cooling". He walked me through a heat pump check out by the condensor. He said to me: "What do you bet it's overcharged?" And then chuckled when he found that to be the case. AC cooled after he left. :D

  • @JohnDoe-vf8cw
    @JohnDoe-vf8cw 4 роки тому +1

    I think the installer looked at the tag on the condenser and probably thought the factory 10lbs charge is what he had to add. Would make sense why its 10 lbs overcharged.

  • @dhamm7x633
    @dhamm7x633 3 роки тому

    Man what a beautiful view

  • @budnotu
    @budnotu Рік тому

    Great video, you should be teaching start your own school.

  • @bradgoodale3249
    @bradgoodale3249 4 роки тому

    Same problems here in the land down under Dave.🤘

  • @kingofthecrease30
    @kingofthecrease30 4 роки тому

    i switched over to the fieldpiece SRS3 wireless charging scale....so far so good...much better than the inficon wey tek non wireless scale i had....i used to own that CPS scale...nothing but problems

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому

      Yes the cps quality on this model dropped compared to the old ones. So far 4 years no issues just eats batteries.

  • @terrytugwood7848
    @terrytugwood7848 4 роки тому

    Great video Dave 👍

  • @JDT738126
    @JDT738126 4 роки тому

    Awesome video Dave, you re the best

  • @sharky5570
    @sharky5570 4 роки тому

    Great video Dave

  • @leoashrae4199
    @leoashrae4199 4 роки тому

    I guess I'm not the only one to find so many over-charged mini-splits. I seem to find it a lot more often than over-charged conventional systems. Many of my local competitors still do a splash'n go, before they even try to troubleshoot a problem.

  • @tonydelgrego2906
    @tonydelgrego2906 4 роки тому

    Nice tip Dave
    Great video. Thank You

  • @markcarpenter3600
    @markcarpenter3600 4 роки тому

    You could have offered to fix the real problem. They need a single head minisplit for that room. Most likely the other tech didn't UNDERSTAND THE SEQUENCE OF OPERATION and kept adding gas one visit after another. "I'll bet you!" LOL!

  • @ADM_NEIL
    @ADM_NEIL 4 роки тому

    Love the video bud. Hope your keeping well. Keep the videos coming bud!!

  • @Oz_is_on_fire
    @Oz_is_on_fire 4 роки тому

    HOT DAMN, PREACH IT!!! Good stuff Dave, thank you!

  • @harrydickson4575
    @harrydickson4575 4 роки тому

    Nice job Dave 👍👍👍👍😷😷😷

  • @335alien335
    @335alien335 4 роки тому

    Not quite three years back I installed 9K Mitsubishi mini-split heat pump to keep some pretty plants cool. Other than being really poor at maintaining a consistent temperature in its one and only head, which required a $270 MHK1 wireless thermostat to resolve, it cooled adequately. At least it did until a couple of months back. Recovering the charge indicated that it was down from 2.58 pounds to about a half pound. Found a leak in the middle of the indoor heat exchanger. (Another has been ordered.) I saved nearly 5 grand by installing the heat pump myself. Too bad that I have no warranty for having taken that approach. It lets Mitsubishi off the hook for its poor workmanship. I won't buy or recommend them in the future. On a positive note, a fair bit of the $5K savings got put into some tools and getting a Universal certificate. Kind of nice to have the stuff needed to make things happen properly and not have to worry about calling in someone. It would have been even nicer not to have to mess with it at all.

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому

      Unfortunately all the evap coils leak of every brand. 5-7 years max I find.

  • @derrickgarcia303
    @derrickgarcia303 2 роки тому

    I have a Lenox that has an indoor unit single head freezing up.

  • @blh3741
    @blh3741 3 роки тому

    let me see... minisplits and humidifier in Bay Area= pot farm???? How much impact on the system is there when you only use 3 of the 5 heads?

  • @kennethbubser9601
    @kennethbubser9601 3 роки тому

    Good job

  • @alexmontoya7258
    @alexmontoya7258 2 роки тому

    Do you have a video on mini split with E1 error and diagnostic

  • @prophetfgsm
    @prophetfgsm 4 роки тому +1

    City multi still the same, 600PSI for 24 hours and hold 300 micron for 30 minutes or 1 hour I don't remember exactly.

  • @2020romania
    @2020romania 4 роки тому

    It may be the long approach but it is the wright approach.

  • @rrodgers3285
    @rrodgers3285 2 роки тому

    U said g manifold or probes that r gray at 6.43 in the video what r those ?

  • @rrodgers3285
    @rrodgers3285 2 роки тому

    Great vid (video) thx... at the time 6.43 u mention how to plug into an ice maker so not to waste any Refrigerant can u explain that or refer me read or watch more on this...God Bless Norcal University

  • @JuanLopez-zc5mz
    @JuanLopez-zc5mz 4 роки тому

    Can you add in description the cheap lamps where you get them at seem to work as well as your expensive one.

  • @stephenmarrone9847
    @stephenmarrone9847 Рік тому

    Two - - Is A Mode conflict Fault code.There is no master head Unit on a Lennox system. All head units must be either in Cooling, or heating Mode. If they are in auto mode the head unit with the highest Demand will dictate what mode they will be in. The set point, Throttling range will be 3 to 5° Fixed By the manufacturer programming Algorithm.

  • @jaymz0074
    @jaymz0074 2 роки тому

    Do you have to use a magnet to open the solenoid valves for recovery and vacuuming? Newbie here and still learning. Thank you.

  • @juanreveles3866
    @juanreveles3866 4 роки тому

    good info on ice machine

  • @kangaroogod
    @kangaroogod 4 роки тому

    Good video,, keep on keepin on

  • @chriscooley906
    @chriscooley906 4 роки тому

    Great video, Great content, Thanks for Sharing Super Dave, Could you not just relocate the T stat ?

  • @aitdat
    @aitdat 4 роки тому

    How low air temp should you expect coming out of the indoor unit on these new double inverter units? Thanks.

  • @USA-GreedyMenOfNoIntegrity
    @USA-GreedyMenOfNoIntegrity 5 місяців тому

    Why did they not just install a standard 4 ton split system with ductwork so that it can be easily troubleshot, cleaned, repaired and a high efficiency air cleaner can be installed. Mini splits have a purpose and it’s not for installations like that. DIY’ers around the country are going to save up front, spend twice as much in the end and wonder why no companies will work on those pieces of plastic junk.

  • @kennethbubser9601
    @kennethbubser9601 3 роки тому

    Don’t like heatpump in attic. But I assume it has enough air discharge.

  • @diysolaradventures7894
    @diysolaradventures7894 Рік тому

    On this video when you first start off are you pulling the refrigerant from the mini split I get confused when you say charge or are you charging the mini-split with refrigerant ?

    • @NorCal-refrigeration
      @NorCal-refrigeration  Рік тому +1

      The charge, is the total amount of refrigerant the system holds.
      But my use of language is all over the place. And my grammar is terrible.

    • @diysolaradventures7894
      @diysolaradventures7894 Рік тому

      @@NorCal-refrigeration it's okay you speak from a professional standpoint I think my mini split needs the old refrigerant pulled out a new refrigerant added is that what you did in this video ?

  • @awesomeaustin2348
    @awesomeaustin2348 4 роки тому

    Can you change which ahu is the master, per t-stat program or dip switch settings ? I'm a chiller guy so I rarely work on mini-splits but that would be good info to know. Thanks...

  • @mrgreen2646
    @mrgreen2646 4 роки тому +1

    When a unit is overcharged can it damage the compressor or the metering device?

    • @mrgreen2646
      @mrgreen2646 4 роки тому

      @Eric M thanks good to know

    • @maxd4968
      @maxd4968 4 роки тому

      Most mini splits are quite smart and will detect when it’s overcharged and throw an error code to the indoor(s)

  • @hectormercado8065
    @hectormercado8065 2 роки тому

    The fact that the heat pump is indoor, wouldn’t that affect your subcool or superheat?

    • @hectormercado8065
      @hectormercado8065 2 роки тому

      I learned a lot in this video, I’m just curious if the unit will be efficient with warehouse heat. . Thank you!

  • @keithkealy3802
    @keithkealy3802 4 роки тому

    Any thoughts on a Friedrich mini split system that keeps increasing room humidity in 2 of 3 rooms? 2 7000 btu heads in separate rooms after a period of running will have humidity in 90's and room temp of 65.

  • @superiorcomfortheatingairl3373
    @superiorcomfortheatingairl3373 4 роки тому

    Good Video👍, Just curious did that unit show high discharge pressure fault code? This is one of the reason I like Mitsubishi Electric verses Gree (Lennox used Gree as their manufacturer of Ductless for a while), there is a way with Mitsubishi to lock the unit into full capacity and use Mitsubishi charts for checking suction & Head pressure inside the outdoor unit, they have ports on both high & low side just hard to get to.

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому +1

      It was not running when I got there. They had it off and just went straight to recovery mode. I like Mitsubishi the best, my day job as so many diakin units i wish Mitsubishi was spec, state has to take lowest bid.

  • @HiddenResolve
    @HiddenResolve 4 роки тому

    Just had one where some installers had put in a minisplit for a shop. Condenser mounted outside right on the otherside of the wall of the head unit. Go there todo a 'startup', find the unit low on charge and head unit freezing. Nitrogen pressure test was fine, but end up putting almost double the charge in to stop the coil from freezing and get ok line temps. It seemed weird. Come to find out that the installers left the full length of both linesets looped in the wall, didnt even have any insulation at the condenser to the wall. Im like, "holy f**k, dont send me on anymore startups".

  • @rrodgers3285
    @rrodgers3285 2 роки тому

    Can u do a video on deviation time what is that?

  • @joeyysossa4144
    @joeyysossa4144 3 роки тому

    Hi..why wont the minisplit display turn off...when minisplit is off...it keeps showing the temperature number...help me!!!

  • @sterlingarcher46
    @sterlingarcher46 4 роки тому +1

    Man , I hate mini splits , what a pain they are , pressures don't mean anything until you're severely undercharged .
    So , do you end up bringing the extra refrigerant to the supplier so they can dispose of it or how does it go ?

    • @Gatsu1995
      @Gatsu1995 Рік тому

      Release it back into nature where it can be free /s

  • @HotelHandyMan
    @HotelHandyMan 4 роки тому

    Good tip! Thank you

  • @44R0Ndin
    @44R0Ndin 4 роки тому

    That's a good method of making sure you have the right charge in a system, but how many pounds of refrigerant is that recovery tank rated to hold?
    I've watched other channels that say those tanks are only rated for holding 18 pounds of refrigerant, but I could be wrong.
    All of my experience with HVACR systems is from dealing with automotive HVAC systems.
    The way you describe critically charged systems leads me to believe that most automotive HVAC systems are in fact critically charged, since the majority of systems hold under 3 pounds of refrigerant, and generally for the same size vehicle, the newer it is the less charge it holds. I've seen systems that take under a pound in small sedans.
    All of that makes it very important that you weigh out and weigh in the charge in an automotive HVAC system, because the first thing a person with DIY tendencies is going to do when it's summer and it stops blowing cold air is add refrigerant. To be fair, most of the time that will solve the problem, but not always. When it doesn't solve the problem, it ends up in the shop and now I have to fix it the right way. So I weigh out the charge with the recovery machine, and weigh in the charge after a vacuum decay test. By doing that, I have proven two things; the system is sealed and the system has the proper charge. With that baseline established, I can start the full diagnostic procedures.

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому

      44R0Ndin tank holds 30 #’s it has a tare weight stamped on it. The key is to only fill it 80% max. To leave room for high ambient temps. Over fill it and it gets hot 💥

  • @Valor4Christ
    @Valor4Christ 4 роки тому

    Hey there, I have a mini ductless split unit, cooling works great, and blows fine. When I try to switch it over to the heating, heat pump, it does not do anything inside or outside. Would you be able to help me troubleshoot this?

  • @MrRUKidddingMe
    @MrRUKidddingMe 4 роки тому +1

    here's a toughie for ya boys...
    We've been contracted to replace fire-damaged heads from Mitsu MUZ-FE09NA systems (TEN of them!) But Mitsu doesn't make an MSZ-FE09NA head anymore... replaced with a MSZ-GE09NA which Gensco says won't be compatible. I call BS.
    Owner doesn't want to replace outside units (great shape) but inside has to be swapped.
    What to do?

  • @bradmurray9401
    @bradmurray9401 4 роки тому +1

    How long did this system run before you were called out

  • @socalcasedog
    @socalcasedog 4 роки тому +1

    Was this in a grow house? Some of the equipment looks similar to 1 i had serviced a chiller and walk-in and another 1 the Wifey works in

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому +2

      Weed shop league here still open. Getting high is essential 🤘⚡️🤘

    • @socalcasedog
      @socalcasedog 4 роки тому

      @@NorCal-refrigeration Ya...its "medical" lol.....

  • @socalcasedog
    @socalcasedog 4 роки тому

    Ive been curious about setting up a mini split in my garage but having the condenser in the attic area above the garage. I was planning on setting up and exhaust fan at my gable vent but i started thinking about setting the condenser about 12" from the exhaust so when its running it would suck the hot air out through the exhaust fan. Think that might be feasible? If my side yard gate was built further forward i would just mount it on the ground outside so that no 1 could see it.
    Forgot to mention, I live down here in Laughlin NV so we do see some real heat during the summer, hence why I was already planning on getting a fan up in the vent

    • @NorCal-refrigeration
      @NorCal-refrigeration  4 роки тому +1

      I would put it outside. It will die in the attic. And condensate all over the place.

    • @socalcasedog
      @socalcasedog 4 роки тому

      @@NorCal-refrigeration Ok....was just a thought. Though the possibility of being out of direct sunlight would be better. The "thought" wheels have been moving upstairs since ive been out of work so long. Sucks,....just when im "recovered" from a work injury and ready to go back to work, we get all this crap happen so now im just "daddy day care" with schools all being closed 🤷‍♀️