WEIL MCLAIN STEAM BOILER TROUBLESHOOTING
Вставка
- Опубліковано 22 жов 2021
- Weil Mclain natural gas powered Steam boiler with beckett burner and Honeywell burner control 7800 series, pilot fault 28 troubleshooting. no heat service call
#d2dnyac #heatingproblem - Навчання та стиль
Omg I really enjoyed the way you explained the sequence of this and give heads up advice about not for beginners thank you sr.
Thank you for watching
Thanks for your different videos keep them coming👍🏼
Thanks for watching
Nicely done! Not too many guys out there posting videos like this, that honeywell interface is a must have working on larger commercial equipment, love those things. Keep up the good work 💪
Thank you 🙏
Fucking love the accent and the detail to attention, explain it like I was 5 years old!
Thank you for stopping by
Great vid brother!!! Appreciate you!!! Thank You!!
Thank you for stopping by
Nice video, I probably would check the ignition lead with my meter for resistance, and if it was low and the connections were good. I would probably not change it.
Normally always the probes, but the ceramic was breaking down on this one.
Always nice to find a problem with a intermittent issue. 👍
Thanks 🙏 for stopping by
Be careful with that green clip lead. That wire insulation is probably only rated for 300 volts. So the 6kv will leak through the insulation. Just make sure you are not grounded when you touch the green test lead. Beware of where your other hand is. A safer way to do that test would be to connect the clip lead to ground first, then bring the other end close to the transformer terminal. That way the wire is always at ground potential, spark or not.
Thanks you for stopping by