HVAC MOTOR PROTECTECTOR EMERSON CORE SENSE FOR SCROLL COMPRESSOR EXPLAINED .

Поділитися
Вставка
  • Опубліковано 23 січ 2025

КОМЕНТАРІ •

  • @kaundabwalya7776
    @kaundabwalya7776 2 роки тому

    Wonderful video 👍👍👍

    • @jollyscaria1922
      @jollyscaria1922 Рік тому

      Ssp over lord portacter srll tup m1 m2 24 220 v T1t2 power comprssar potacter 😊

    • @jollyscaria1922
      @jollyscaria1922 Рік тому

      M1 m2 conrold circuit hp swich lp km2 swich winding port hoted model çonrold high lp conlrold senszy systom model B+a+bms conrlld pointed

    • @jollyscaria1922
      @jollyscaria1922 Рік тому

      Conrold wind hot senzing greeing lockout mode sermiter wire rmobving agin fix no 1o r Shoeing lok out bord sysyom

  • @davemaldo07
    @davemaldo07 Рік тому +1

    Paused video at 8:30 to bypass M1-M2. The compressor hadn't run since since 2019, according to history on comfortlink. Awesome video. Many thanks.

    • @D2DNYAC
      @D2DNYAC  Рік тому

      Thanks for watching

  • @Cre666in666
    @Cre666in666 3 роки тому +2

    Thank you so much, encountered one of these for the first time today and struggled to understand how it operates

  • @IRONDICKMECHANICALHVACdavis
    @IRONDICKMECHANICALHVACdavis 3 роки тому

    Boss video. It has to be a yardman. Teaching this. 100%. Respect.

  • @38sohaib
    @38sohaib Рік тому

    Wonderful explanation brother. Keep up the good work. Love from pakistan❤.

  • @dodirt2184
    @dodirt2184 3 роки тому

    Thank you for taking the time to help me learn 👏🏿🙏🏿

    • @D2DNYAC
      @D2DNYAC  3 роки тому

      Thank you for stopping by

  • @laworder6092
    @laworder6092 3 роки тому +1

    Thanks sir for your excellent teaching method 👏

    • @D2DNYAC
      @D2DNYAC  3 роки тому

      Thank you 🙏 for stopping by

  • @marcoselgaucho1106
    @marcoselgaucho1106 2 місяці тому

    Your the man! Great stuff

    • @D2DNYAC
      @D2DNYAC  2 місяці тому

      Thanks for watching my brother

  • @hkhvac270
    @hkhvac270 3 роки тому +1

    Thank you for explaining good luck 👍

  • @abdulsami2148
    @abdulsami2148 Рік тому

    Great sir 👏

    • @D2DNYAC
      @D2DNYAC  Рік тому

      Thanks for watching

  • @RonnieL-k3y
    @RonnieL-k3y Рік тому

    Im getting 4 flashes indicating scroll high temperature but the compressor is isn't over amping. Could the sensor be bad?

    • @D2DNYAC
      @D2DNYAC  Рік тому +1

      Yes, and if there’s no redundancy on the compressor, then it would have to be replaced thus i would replace the module first just in case it’s malfunctioning

  • @bradsellers5592
    @bradsellers5592 2 роки тому

    I'm having a issue with connector not pulling in no 24v. I have 24v to m1 and m2 goin to compressor. If I jump m1 and m2 the compressor will start. Also if I put 24v to coil connector it'll rn just fine.

    • @D2DNYAC
      @D2DNYAC  2 роки тому

      So the module is bad or the thermistor is opened or the compressor is overheating

  • @exlost245
    @exlost245 2 роки тому

    Hi.
    My coresense keeps flashing green succesively. My compressor.is shutting down about a minute. And can't figure things out..hope you can help

  • @stratosgiannis4340
    @stratosgiannis4340 4 роки тому

    Great vid, keep it up!!

  • @dangross6134
    @dangross6134 3 роки тому

    Very nice explanation, Will the compressor start if you don't use the t1and t2 or m1 and m2. I changed out a trane compressor to a Copeland and the trane does have the core sense...

    • @D2DNYAC
      @D2DNYAC  3 роки тому

      It will start

    • @D2DNYAC
      @D2DNYAC  3 роки тому

      It will star however its beneficial for the compressor to have this connected into the controls circuit!

  • @welcom3779
    @welcom3779 3 роки тому

    Nice explication

  • @zebbspascua8028
    @zebbspascua8028 3 роки тому

    My old system ZP182KQE-TFD-477 does not have the Coresense compressor protection and said they don"t make that model anymore, Instead they provided with ZP182KCE-TED with Coresense . (The only difference is these models is the motor protection. TFD has the internal motor protection. TEDhas the newer, updated Coresense module. "F" is internal protection. The "E" is electronic enhanced. How can I wire this?

  • @covid-kw9fb
    @covid-kw9fb 3 роки тому

    Awesome info man, thanks

  • @kwelilukomba6445
    @kwelilukomba6445 3 роки тому

    can you please show up and explain the all compressor wiring from mammoth and motor protector?

  • @Randylazz
    @Randylazz 4 роки тому +1

    Ya learn something new everyday
    Have A Great Weekend............😎

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 5 місяців тому

    They have software and all you need is a RS485 converter. You can log into the motor protector and get all sorts of information off it

    • @D2DNYAC
      @D2DNYAC  5 місяців тому

      Really, is this an emerson software?

  • @prithwishdey6708
    @prithwishdey6708 3 роки тому

    Please discuss ICM-220 lock out relay Waring and Copland protection (INT69SC)

    • @D2DNYAC
      @D2DNYAC  3 роки тому

      I will stay tuned for that

  • @kwelilukomba6445
    @kwelilukomba6445 3 роки тому

    can you please explain how wire core sense to compressor ,solenoid, low and high pressure switches ,hot gas t1 and t2 , m1 and m2 i mean full wiring to compressor components.please need it AsP

    • @D2DNYAC
      @D2DNYAC  3 роки тому

      Okay I will explain

    • @D2DNYAC
      @D2DNYAC  3 роки тому

      T1 & T2 is your core sense power connection ,
      M1 & M2 is to be connected in series with high and low pressure switches

  • @mohamedatef-do6pj
    @mohamedatef-do6pj Рік тому

    Very good video
    Can i contact you ?

    • @D2DNYAC
      @D2DNYAC  Рік тому

      Thanks

    • @D2DNYAC
      @D2DNYAC  Рік тому

      May I suggest you becoming a preferred Member of my channel!

  • @binho8308
    @binho8308 4 роки тому

    i have problem with alert code (red) SOLID (don't flash). Can't you help me fix it?? Do i replace a new once??
    Many thanks.

    • @D2DNYAC
      @D2DNYAC  4 роки тому

      Yes! pause the video at 15:10 to see fault codes

  • @wasiahmed3202
    @wasiahmed3202 4 роки тому +1

    If the terminal T1,T2 not use ?
    Safety device not work (ok) .
    I do not use safety device.
    Machine direct supply this terminals (L1,L2,L3) what is possible without safety device compressor work only ?

    • @wasiahmed3202
      @wasiahmed3202 4 роки тому +1

      Already my machine safety equipment available.

    • @D2DNYAC
      @D2DNYAC  4 роки тому

      wasi Ahmed T1 T2 is the power supply terminals, if you don’t connect those then the module is useless!

    • @D2DNYAC
      @D2DNYAC  4 роки тому

      wasi Ahmed The module will not protect the compressor if t1 and t2 not connected, if you wish to protect compressor apply the appropriate power supply to t1 and t2 (24v or 120/230v make sure correct voltage!) then connect m1 and m2 in series with high and low pressure switches

  • @Ed_Tech-Esco
    @Ed_Tech-Esco Місяць тому

    AAON CF unit had bad discharge thermister . Tech support said I needed 75k resistor in order to bypass it . No shot I had one 🤷🏻‍♂️

    • @D2DNYAC
      @D2DNYAC  Місяць тому

      75 k ohnm Resistor for this module? Or for input on Aaon controller?

  • @muralisingh5334
    @muralisingh5334 2 роки тому

    Please upload video on trane dx BAS unit

  • @SombraLocs
    @SombraLocs 3 роки тому +1

    Are M1 and M2 the ones you can jump out if the module keeps giving nuisance trips, but you want to keep compressor running until you get a new module? Daikin AGZ alarm OffMtrProtect.

  • @yusufansari8955
    @yusufansari8955 3 роки тому

    Thank you very much.

    • @D2DNYAC
      @D2DNYAC  3 роки тому

      Thanks for stopping by

  • @thebigpush2835
    @thebigpush2835 2 роки тому

    Thank you

    • @D2DNYAC
      @D2DNYAC  2 роки тому

      Thank you for stopping by

  • @rajphilip4346
    @rajphilip4346 2 роки тому

    Tks bro

  • @riyaz.samsung8568
    @riyaz.samsung8568 3 роки тому +1

    SSPS mean

    • @D2DNYAC
      @D2DNYAC  3 роки тому

      SSPS ??? or SPDT!