RAYPAK Boiler 1

Поділитися
Вставка
  • Опубліковано 16 вер 2024

КОМЕНТАРІ • 11

  • @RobWhitey1
    @RobWhitey1 3 місяці тому

    Thank you for taking the time to make and post this.
    Can you do one on testing all the safeties on the raypak unit?

  • @wardoggy100
    @wardoggy100 2 роки тому

    Great vid

  • @minnesotasalamander5913
    @minnesotasalamander5913 6 років тому

    Thanks Luis. Good explanation.

  • @MrLeona017
    @MrLeona017 2 роки тому

    Great video

  • @mx-lj4qq
    @mx-lj4qq 5 років тому

    Luis bien chingon primo gracias

  • @purrungas2012
    @purrungas2012 Рік тому

    What are the high and low settings for the limit switches?
    Thanks

    • @oldironsides3992
      @oldironsides3992 Рік тому

      They need to have a 60-degree difference. Example if you desire 130 on the water you recive at the tap, the set point is 130. Your high limit will be set at 190. Check with the manufacturer representative for their opinion but this has been my experience.

  • @MrLeona017
    @MrLeona017 2 роки тому

    Where you hook up to do a combustion test?

    • @irineogomez
      @irineogomez Рік тому +1

      Drill a tiny hole in the exhaust pipe and stick the probe in roughly half the diameter of the stack.

    • @irineogomez
      @irineogomez Рік тому +1

      Drill a tiny hole in the exhaust pipe and stick the probe in roughly half the diameter of the stack.

    • @oldironsides3992
      @oldironsides3992 Рік тому

      You can use a combustion analyzer or a manometer.