Bizarre Ventilation System Design: Zehnder ERV Layout by Licensed Mechanical Engineer

Поділитися
Вставка
  • Опубліковано 2 лип 2024
  • Let's dive into the details on a licensed engineer's ventilation design for a new home. Thanks to my Hungarian pal Szabi Fekete, Zehnder America (www.zehnderamerica.com/) for lending his wide technical expertise on this.
    Check out my deep dive into Ventilation Design & Installation: buildingperformanceworkshop.c...
  • Наука та технологія

КОМЕНТАРІ • 37

  • @johnhaller5851
    @johnhaller5851 8 днів тому +5

    The Stud Pack channel is building a house, which they are trying to make tight. They put a huge exhaust fan in the bathroom, with no makeup air. Right now, this is just a second floor over the garage, so probably won't get used a lot after they build the main house. They did put in an ERV, but it didn't seem to be well placed They did do one collab with Matt Resinger on windows. They could really use a collab with you describing what they did wrong on the garage living space, and how to fix it for the main house. But, they didn't have time to read all the comments. Peehaps if you reached out to Matt, he would connect you two. They would be another good example of a bad design for the part of the project they are doing.

    • @juliancate7089
      @juliancate7089 8 днів тому +1

      Stud Pack are a great group and fun to watch, but I would not want them building my home without GC to supervise.

  • @l0gic23
    @l0gic23 9 днів тому +7

    Can we get an equivalent video with a house done right?

  • @brickhousedesignbuild5760
    @brickhousedesignbuild5760 8 днів тому +2

    Would be interesting to hear the engineer’s thoughts on this. We need a response video😂

  • @trickstothetrades1801
    @trickstothetrades1801 9 днів тому +1

    Love the design breakdowns of do’s and don’ts very helpful. Thanks

  • @machickman4041
    @machickman4041 9 днів тому +1

    Awesome video!! Please provide more informative videos like this!!

  • @jonsnow5943
    @jonsnow5943 День тому

    1) 💡What is interesting about this rant, is that the P.E. may have welcomed your observations and appreciated the help. Which, IMO, would make a more interesting video showing how collaboration wins over isolation, everyday. 2) Make Up Air for the Rangehood ✅ 3) Zone level air cleaner 4) The ERV OSA/EXA is missing the air monitoring device to prevent objectionable air entering the close space environment. 5) The house is the largest duct system 5) Ductless heads do not have any level of IAQ, the included air filters are for coil fouling prevention 6) The “missing” RR EF may be a local or regional design omission. For example, In Montana, the HVAC contractor is responsible for the EF. But in California, the electrician is responsible for the EF. In both of these cases, direct consultation with the homeowner or GC is typical. With a RenewAire or similar ERV, recovery energy from the RR, in lieu of a EF, maximizes the energy recovery as well as the cost efficiency. 7) Mold spores only grow on organic materials. No SA in closets, please. 8) Regarding the Loft/Library, it does not look like a closed space, No doors or walls on 4th perimeter. Meaning, the Engineer was just circulating air (ASHRAE 55). In this case, the building pressurization comment doesn’t seem germane.

  • @chriscermak3188
    @chriscermak3188 9 днів тому +1

    Excellent Corbett.

  • @dosadoodle
    @dosadoodle 9 днів тому +6

    This is crazy that a professional team did this with a Zehnder system, because Zehnder provides room-by-room supply/extract design details as part of buying their system. I don't know why the installers felt compelled to throw that plan out the window.

  • @ricsoares8169
    @ricsoares8169 8 днів тому +1

    These two guys are doing God's work.

  • @D2O2
    @D2O2 9 днів тому +1

    Curious if you discussed this with the engineering firm and what they had to say regarding the details that you pointed out?

  • @jonsnow5943
    @jonsnow5943 2 дні тому

    The one powder room with 20 SA & 30 EA is actually in a negative space pressure. IMO-Since the PWDR RM is a transient and mostly unoccupied space, adding SA doesn’t merit the costs.

  • @jonsnow5943
    @jonsnow5943 День тому

    Corbin, what is the purchase proposition for the Zehnder when compared with less expensive ERV offerings like the RenewAire or Broan or Panasonic?

  • @TomLap-qd6xc
    @TomLap-qd6xc 9 днів тому +1

    Always very informative! Have you heard of the CERV from Build Equinox?? Would love a review or opinion on them.

    • @TomLap-qd6xc
      @TomLap-qd6xc 9 днів тому

      FYI: they claim their unit can handle kitchen exhaust (CERV by Build Equinox)

  • @jonsnow5943
    @jonsnow5943 2 дні тому

    Do I understand correctly that Zehnder does not have the capacity to recover energy from the restrooms? I look forward to your reply. Thank you.

  • @jonsnow5943
    @jonsnow5943 2 дні тому

    Single Line Diagram - Represents two pipes or two wires or indicated some connectively, not electrical conductors. Single Line Diagram.

  • @gabrielfarrar11
    @gabrielfarrar11 9 днів тому

    Great video Corbett! Do you see any issue with a broan AI erv using the zehnder distribution system?

    • @HomePerformance
      @HomePerformance  9 днів тому

      Yes, I believe they’re not meant to run at high static pressures.

    • @JoshSmith-vm6nx
      @JoshSmith-vm6nx 6 днів тому

      ​@@HomePerformance is Zehnder functioning at high static pressure? I know they're small tubes that are used in other high velocity systems, but with the low flow rates I thought static pressure wasn't very high?

  • @ryansoo4000
    @ryansoo4000 9 днів тому

    Hello. There's a recent video from the Green Home Institute you might find interesting called "What's Up With the Taylorville High, Net Zero Pretty Good House Student Build" that features the consulting work of Build Equinox on the HVAC design. They mention that they use their ZEROs free to use house design software. Have you heard of it before? The lecturer also mentions at minute 45:30 that by using today's inverter-drive speed control heat pumps you can use two 1 ton heat pumps running at 50% capacity and they will be 20-30% more efficient than one 1 ton heat pump running at 100% capacity. Is that true?

    • @tweake7175
      @tweake7175 8 днів тому

      in theory kinda true, but in reality no. the dual system would basically have bigger coils and airflow, which can lead to higher efficiency. however if you install 2 ton into a space meant for 1 ton, then you will be grossly oversized which will make it very inefficient in real world conditions. some manufactures make units with oversized coils to perform better in colder conditions, but they cost more. hope that helps.

  • @ryansoo4000
    @ryansoo4000 7 днів тому

    Hi Corbett. If people send you the names of other videos that are related to what you are teaching, do you actually view them? I saw an interesting video from UA-camr Healthy Home Guide called "Most Hepa Purifiers Are a Scam (There's a Better Option)" and he gave a lot of great scientific information on how a DIY Corsi-Rosenthal box fan filter is better at removing particulate matter than a Hepa filter - even for wildfire smoke. He also features a company that makes inexpensive box filters that are even more effective than a DIY model. Given your recent videos on wildfire smoke and cleaning, you might be interested in what he has to say.

    • @HomePerformance
      @HomePerformance  6 днів тому

      Alex is s client of mine, yes I know that vid. He’s mostly focused on the CADR, the airflow of those systems.

    • @ryansoo4000
      @ryansoo4000 5 днів тому

      @@HomePerformance Hello! So is his information valid? Is his air filter design more effective at removing particulates than other filters, especially at removing wildfire smoke?

    • @HomePerformance
      @HomePerformance  4 дні тому

      @ryansoo4000 you can see the research chemists of CIE saying someting similar in the video that drops today, and the one that’s linked within it.

  • @lukemorton5196
    @lukemorton5196 8 днів тому

    How did the engineer respond to your comments and observations?

  • @tweake7175
    @tweake7175 9 днів тому

    Did i hear that right, 0.46ach ventilation rate. I know quite a few that run 0.5.

  • @antonkachulkin6980
    @antonkachulkin6980 9 днів тому

    Can I ask “stupid” question? What is wrong to use regular fans in the bathrooms or kitchen and open windows and doors ones in the wile? I want to build icf home and that is a big topic everyone is talking about! Thank you in advance!

    • @tweake7175
      @tweake7175 8 днів тому +1

      not a stupid question at all, even i see this a bit. i hope he has a proper answer for you.
      if your building a high performance home, the last thing you want to do is let dirty air come into the house. so your not going to be opening windows. also the big advantage of being air tight is your now able to keep outside and inside air separate. with ventilation you do that with an erv. inside heat and moisture stays inside, and outdoors stays outside. so you don't want to be running normal bath fans and ruin that. with a rangehood you have to because of the large air volume, it has its own make up air.
      what i tend to see is some people trying to do a high performance home and also trying to run them like a low performance home. to me its one or the other, you can't do both. its also a huge waste of money to run it as a low performance home. (some people here build passive houses for the name, so they can sell for higher profit instead of actually using them as a passive house).

    • @HomePerformance
      @HomePerformance  8 днів тому

      Not stupid, already have a vid for you:
      Borderline of Balanced Home Ventilation: When Do I Need an ERV because Bath Fans Won't Work?
      ua-cam.com/video/lnOCAPPVT5g/v-deo.html

  • @MarkRose1337
    @MarkRose1337 10 днів тому +1

    That plan was truly bizarre.

  • @andreycham4797
    @andreycham4797 8 днів тому

    Yea , put air intake next to front porch , so someone in your family or your guests could go there to smoke

  • @superspeeder
    @superspeeder 8 днів тому

    Building my own place, every bedroom closet, bathroom and the kitchen will have an exhaust. Every bedroom, living room, family room, dining room will have a supply. Not hard.

  • @drdroop2163
    @drdroop2163 9 днів тому

    We all have a bad day at work, apparently.

  • @infinitybeyond6357
    @infinitybeyond6357 9 днів тому

    On the Ground Floor,
    is it literally an "Airlock", like in space, where only one door can operate at a time?
    Is the "Airlock" a security feature? or an atmospheric control feature?
    why is there only a supply air register in the "Airlock"?
    why is the "Airlock" door swinging into the middle of the Hallway?
    will likely hit people walking in the Hallway.
    does the "Airlock" means something else in your local area?
    is it like a mudroom or foyer?
    Garage for 1 car only?
    A Real Greenhouse is a great place for CO2 and O2 exchange, yet nothing designed for the area, seems like an opportunity lost.
    Great Room,
    is that a fireplace in there?
    is that why there are tons of supply air register in there?
    the plan looks detailed and professional,
    but design is bad.
    i don't know what to think.

  • @Th3120ck
    @Th3120ck 8 днів тому

    Wonder how much money the builder paid for this plan....