HEAT SEQUENCER Operation, Timing, & Testing

Поділитися
Вставка
  • Опубліковано 31 гру 2024

КОМЕНТАРІ • 122

  • @acservicetechchannel
    @acservicetechchannel  5 років тому +7

    Support The Channel- www.patreon.com/acservicetech
    Tool List- www.amazon.com/shop/acservicetech
    For those that are looking for the tools used in the videos: (Linked Below)
    UEI DL479 Multimeter with temp sensor amzn.to/2jtsUbJ
    Valve Core Removal Tool amzn.to/2uYr8WL
    Blue Vapor Yellow Jacket Gauge- amzn.to/2Ju7pan
    Red Liquid Yellow Jacket Gauge- amzn.to/2sSFmGH
    Quick Coupler for the Gauges- amzn.to/2sTk8Ze
    JB Test Gauge High Side- amzn.to/2ruQb0l
    JB Test Gauge Low Side- amzn.to/2qR0utM
    Manual Copper Tube Swage/Expander- amzn.to/2WRPa1M
    Uniweld Hydraulic Swaging Tool- amzn.to/2MlrI8m
    Uniweld Swage and Flare Kit- amzn.to/2T55jyn
    Ameriflame Oxy Acetylene Torch Setup- amzn.to/2SRm3JF
    #2 Tip for Oxy Acetylene Torch- amzn.to/2SPDaeD
    Cap-N-Hook Tip for Oxy Acetylene- amzn.to/2MbhpUk
    Air Acetylene Torch Setup- amzn.to/2aQalsb
    15% Silver Brazing Rods- amzn.to/2gVLyLc
    Nitrogen Regulator- amzn.to/2bXdR5f
    Nitrogen Flow Meter- amzn.to/2brvoBg
    NitroVue Flow Reg- amzn.to/2MiulYv
    Ultrasonic Leak Detector- amzn.to/2Lw4Zpr
    UEI DL479 Multimeter with temp sensor amzn.to/2jtsUbJ
    Magnet Jumpers- amzn.to/2PyKPQZ
    Alligator Jumpers- amzn.to/2PxqJXn
    Fieldpiece ST4 Dual Temp Meter amzn.to/2wc1ME3
    Fieldpiece Bead K Type Temp Sensor amzn.to/2DBwKfs
    Fieldpiece Wet Bulb Temp Sensor amzn.to/2RRI7Tw
    Fieldpiece TC24 Temp Clamp amzn.to/2qHLyjZ
    Yellow Jacket Refrigerant Gauge Set amzn.to/2aenwTq
    Refrigerant hoses with valves amzn.to/2aBumVI
    Yellow Jacket Gauge set & hoses amzn.to/2vLVkV9
    Yellow Jacket 4 Port Manifold w Hoses amzn.to/2BkuGIq
    FieldpieceSMAN360 Digital Manifold Set amzn.to/2BdoaD4
    FieldpieceSMAN460 Digital Manifold Set amzn.to/2nB4Fe6
    Compact Ball Valve for Refrigerant Hose amzn.to/2KUisW8
    QuickDisconnect 90 for refrigerant hose amzn.to/2MMtVcg
    JB 6 CFM Vacuum Pump amzn.to/2nqbvo8
    Appion Blue 3/8" to 1/4" Vacuum Hose amzn.to/2uYlVyc
    Appion Red 3/8" to 1/4" Vacuum Hose amzn.to/2uYg6Ro
    Appion Valve Core Removal Tool amzn.to/2uYr8WL
    Yellow Jacket 1/4" by 1/4" hose amzn.to/2umtcod
    CPS Vacuum Micron Gauge amzn.to/2v1nM3O
    Supco Vacuum Micron Gauge amzn.to/2v1JRiA
    RectorSeal Bubble Gas Leak Detector amzn.to/2ckWACn
    UEI DL389 Multimeter amzn.to/2xAdaJf
    Other tool links can be found in the video description section.
    Shop through Amazon! Your Purchases through Amazon provide a means for channels such as mine to earn advertising fees from all purchases after clicking through. Prices are the same as normal- www.amazon.com/shop/acservicetech

  • @tuta6820
    @tuta6820 5 років тому +26

    I'm on my way to the Skills USA competition as I'm watching this. You're still my favorite teacher.

    • @acservicetechchannel
      @acservicetechchannel  5 років тому +7

      Wow Chris, I am so happy you are there! Please let me know how you make out! I am happy to have taught you for those two years!

    • @NROhvac
      @NROhvac Рік тому

      He’s the best teacher I’ve ever had and I never met the man. Thank you Craig you are valued very much in our community

  • @takleung7130
    @takleung7130 5 років тому +15

    One of the best channel for newer and older techs! Really appreciate you taking the time and effort to dismantle the parts and show how things work. Thank you!

  • @jaimiegarcia9863
    @jaimiegarcia9863 Рік тому

    Thanks for your teaching, patience and your knowlege!!!!!

  • @David-eb5rx
    @David-eb5rx 5 років тому +5

    Great video, I live in SWFL and we don't really deal with Heat too much but when we do I get lost because I forget everything. This video was extremely informative and broke it down real smoothly. Thanks!

  • @chesstime356
    @chesstime356 Рік тому

    As always I like your videos and watching over and over getting more good information every time

  • @aaronclark1599
    @aaronclark1599 2 роки тому +1

    This man is the best at explaining things..

  • @danjarvis6980
    @danjarvis6980 2 роки тому

    Outstanding training vid. Doing a surgical autopsy on the components to see their innards is most enlightening.

  • @michaelorwig6609
    @michaelorwig6609 2 роки тому

    hi im a business owner and most heaters are gass around here and ao electric heat is kind of my weakness but i fill so condident after watching this video and the electric heat video that you did thank you so much

  • @TonySaprano
    @TonySaprano 4 роки тому

    (Time 4:22) Yep, I found the same burnt contacts on mine after working 11 years.
    The give away was the fan kept running with the strip heaters on from the contacts sticking intermittently.
    Great Vid and Thank you AC Service Tech and keep making those vids :)

    • @HsingSun
      @HsingSun 2 роки тому

      I hope that your second line would be true. I just got my Sequencer after two months, and I will put it in work tomorrow.

  • @unclemarksdiyauto
    @unclemarksdiyauto 3 роки тому +2

    Great explanation of a sequencer. Thanks for posting this quality video! I have had problems with furnace in the past and wish I would have seen this simple explanation at that time.

  • @davidnecky8524
    @davidnecky8524 2 роки тому

    great explanation of how the sequencer works. Your explanations are excellent and easy to understand!!!

  • @themayorofairconditioning2868
    @themayorofairconditioning2868 2 роки тому

    Such an excellent video among other extremely useful videos, AC Service Tech 👍

  • @MrRalph438
    @MrRalph438 4 роки тому

    Mr. Craig M.. is like the yoda of HVAC!!! full of knowledge.

    • @AllTattedUp13
      @AllTattedUp13 4 роки тому

      Hes like a hvac mad scientist. He's awesome!!!

  • @mazenkano1811
    @mazenkano1811 Рік тому

    your videos has helped me so much

  • @Cleon433
    @Cleon433 2 роки тому

    Awesome video! Always wondered how these worked!

  • @Conk102
    @Conk102 4 роки тому +2

    Thank you for doing this awesome video! Very well presented and explained. I appreciate this.

  • @levikamensky7353
    @levikamensky7353 4 роки тому +1

    This guy is a genius

  • @maxeyac
    @maxeyac 5 років тому +2

    I really enjoy your videos. Please dont stop. EVER! lol

  • @aaronr164
    @aaronr164 5 років тому +6

    Great video! Can you do a video on belts and pulleys?

    • @acservicetechchannel
      @acservicetechchannel  5 років тому +1

      Aaron, thank you for letting me know what you would like to see!

  • @MOfus101
    @MOfus101 3 роки тому

    Best explanation so far thank you

  • @DM-jf3lg
    @DM-jf3lg 5 років тому +1

    A great refresher for me. Thanks so much. How about a video on troubleshooting a gas ignition module? Honeywell and Whiterogers.

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      Thanks DM, have you looked up "acservicetech ignition playlist" I have a bunch of videos out on that subject, thanks

  • @seandacey8346
    @seandacey8346 3 роки тому +1

    Excellent video.

  • @HahahaVille
    @HahahaVille Рік тому +1

    Question, my heat is not cutting off all the time ( even turning it off at the themostat it stays on ) I have to cut the heat off at the breaker for it to completely shut off. This problem is intermittent but it’s becoming more common. Could the heat sequencer be going bad,getting stuck? I’ve already replaced the themostat and the wires to the themostat seems to look good ( and none are touching- so I don’t think I have a short )

  • @atch_n_sons
    @atch_n_sons 5 років тому +1

    Clear and concise explanation

  • @acrepairnearme
    @acrepairnearme 5 років тому +1

    Yes, this I didn't understand, because most working with gas furnaces and heat pump. If you can make a couple of the videos about the sequence of operation electric heater and troubleshooting those, that would be great)))) thank you!

    • @acservicetechchannel
      @acservicetechchannel  5 років тому +1

      Hey Tapch, did you see this video on the electric strip heater voltage path? I started linking related videos in the description sections, thanks!- ua-cam.com/video/7_-x6u9uzhU/v-deo.html

    • @acrepairnearme
      @acrepairnearme 5 років тому +1

      AC Service Tech LLC thanks )! I'll watch

  • @HsingSun
    @HsingSun 2 роки тому +1

    Thank you for your video. I have very hard time to find a "new part" for my Sequencer: PN# 14SH22 H24V 305886 4/5 H1-15 C45-110, 1/3 H20-45 C1-30.

    • @tjmoses7384
      @tjmoses7384 Рік тому

      I’m looking for almost the same part my only difference is the H20-45 on yours is a H20-40 on mine. What did you do to get a new part I can’t find one that’s the exact same anywhere

  • @g.martinez2871
    @g.martinez2871 5 років тому +1

    Great video! Thank you for all your instructional videos!

  • @michaelcostello6991
    @michaelcostello6991 3 роки тому

    Excellent demo. Thanks

  • @tonycanard8051
    @tonycanard8051 3 роки тому

    Excellent tutorial. Thank you

  • @sajjanlama1ify
    @sajjanlama1ify 5 років тому +1

    Your vdo is really nice its easy to understand how to work these things

  • @MultiMaverix
    @MultiMaverix 2 роки тому

    I apprecite this. Thanks.
    So what is the sequencers job function?

  • @sergiodjf
    @sergiodjf 3 роки тому +1

    Great demonstration! Very didactic 👍

  • @valdeksaltykov7845
    @valdeksaltykov7845 4 роки тому +1

    great explanation!

  • @Jamie-lb7eh
    @Jamie-lb7eh Рік тому +1

    Can this cause an intermittent problem with the HVAC blower starting but sometimes not? I changed my motor capacitor, HVAC runs fine but sometime the fan blower does not start.

  • @Eddy63
    @Eddy63 5 років тому +1

    Great explanation Craig ... Much appreciated ...

  • @johnwaters5571
    @johnwaters5571 2 роки тому

    I'm a tech. Great job!

  • @JC-sc9rx
    @JC-sc9rx 4 місяці тому

    Should we be reading resistance to powered circuits? Safe because it's only 24v?

  • @michaelcalderon5986
    @michaelcalderon5986 Рік тому

    Thank you for all the help you’ve provided me along my way! Question though, isn’t it risky to test ohms like that on sequencers? Since you’re getting 240v after the bottom thermodisc?

  • @sangnitedatarecovery3203
    @sangnitedatarecovery3203 3 роки тому

    Awesome video 📹 👏 👌 👍 🙌 😀

  • @DreamLand20
    @DreamLand20 Рік тому

    Very helpfull. Thank you

  • @Davidandgoliathhvac
    @Davidandgoliathhvac 9 місяців тому

    Excellent!

  • @zesty2023
    @zesty2023 5 років тому

    I love cutaways they explain all.

  • @tonybasham7141
    @tonybasham7141 2 роки тому

    Good information thanks

  • @johnjacobsen1915
    @johnjacobsen1915 3 роки тому

    GREAT INFO! TY!

  • @Sctronic209
    @Sctronic209 2 роки тому

    As the sequencer is heated is it dropping the rod or pushing the rod?

  • @TheMaximomex
    @TheMaximomex 5 років тому +1

    Great video. Thank you.

  • @dg7197
    @dg7197 2 роки тому

    good stuff. Thank you sir.

  • @antonionibarillas8255
    @antonionibarillas8255 3 роки тому

    So great thanks

  • @dyershvac5884
    @dyershvac5884 11 місяців тому

    Heat sequencers reading 118ohms on the coil would mean bad sequencer? i had a few new heat kits read high out of box.

  • @rb7491
    @rb7491 5 років тому +1

    great video

  • @osiel9203
    @osiel9203 5 років тому +1

    Thank you once again.

  • @francispiche4177
    @francispiche4177 4 роки тому

    Very instructionnal Thank you for you time

  • @robertsmith2956
    @robertsmith2956 2 роки тому

    I found an interesting problem with digital thermostats I never ran across before.
    When they house is 32 degrees, the "AAA" batteries shut down in about 12-15 minutes with a low battery display, and no more use out of thermostat signals. So you need to work REAL fast or lose the control signals.

  • @andrewnielsen8032
    @andrewnielsen8032 5 років тому +1

    If a sequencer is cold will it take longer for the bimetal disc to heat up and close the contacts???

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      Since the sequencer's bi-metal disc will flex due to heat, yes but once a little heat is generated, it is insulated by the plastic surrounding the disc so the heat will build fairly quickly. I don't think you will notice much of a difference in timing unless the seconds were counted critically, thanks and good observation!

  • @SerenoOunce
    @SerenoOunce 6 днів тому

    Why would there be a sequencer along with a fan limit switch? Wouldn't the limit make a sequencer redundant?

  • @Dusterplugless
    @Dusterplugless Рік тому

    Dumb question do you take heater wires off sequencer and turn breaker and thermostat on and then check continuity or can you leave breaker off and just turn on thermostat?

  • @Ian-iu2tl
    @Ian-iu2tl 5 років тому

    Really good explanation.
    I am having difficulty trying to figure out exactly how the thermal disc can drop the rods for the contactors at different times.
    Can you give a more detailed explanation for this?

    • @acservicetechchannel
      @acservicetechchannel  5 років тому +5

      Instead of just a snapping action, think about a slowly bending disc with the two rods in slightly different locations on the disc, thanks!

  • @murtazaahmadi7623
    @murtazaahmadi7623 5 років тому +1

    Thank you

  • @shanegreen9019
    @shanegreen9019 10 місяців тому

    Ok still little confused. If the heater snaps or moves just one time, how is there a difference in timing of the switches? Should both rods move at the same movement time as well?

  • @mohammedalobaidi9981
    @mohammedalobaidi9981 2 роки тому

    Amazing…thanks.

  • @winstonledford3507
    @winstonledford3507 4 роки тому

    where does the motor fan wire go on which contact

  • @tenncutt
    @tenncutt 2 роки тому

    Got a furnace with no control/circuit board that blew a transformer (no fuse) replaced transformer and added fuse and blows the fuse instantly when i turn the power on! Any thoughts?

  • @robertsmith2956
    @robertsmith2956 2 роки тому

    I guess it saves wire. But after a good night sleep and reading the wiring diagram my head scratching is ended.
    The upper coil is wired in series, and taps off to blower motor. Couldn't figure out why it isn't always on. The blower just makes a big loop back to L1, so the entire circuit is just a big bus bar looking for a way out that the contractor supplies to L2, and the blower gets power backwards if relay doesn't kick on. Since AC doesn't care which way it works, all good.

  • @l.crossjr
    @l.crossjr 5 років тому +1

    Gracias

  • @ilovenythismuchilovenewyor5801
    @ilovenythismuchilovenewyor5801 3 роки тому

    so if im getting 21 volts at the wires going to the intermittent pilot module that are supposed to send power to the gas valve... that sequencer is the culprit ??!! I am getting correct voltage every where but at that point.... so the sequencer or the wires leaving the sequencer to the intermittent pilot are the culprits

  • @kenb3279
    @kenb3279 4 роки тому

    So I was practicing with my multimeter on a working electric furnace that has no problem works normally. I shut the breakers off, thermostat is off. I tested the sequencer for continuity across the top prongs which I thought should be open, yet I got a continuity beep. I did not take any wires off the sequencer. Should I take the wires off to test? Do I have to take all the wires off? Thanks for video

    • @HsingSun
      @HsingSun 2 роки тому

      Yes, you should take off all the wires on any devices before you do continuity test.

  • @brainwashed7244
    @brainwashed7244 Рік тому

    Do 240v hvac transformers supply 24v dc or ac current?

    • @chrisdeanndavison3626
      @chrisdeanndavison3626 9 місяців тому

      Almost always AC. Some air handlers do use 22v or 28v DC relays, but that is accomplished by a rectifier. The transformer is still 24v AC.

  • @good0and0bad
    @good0and0bad 5 років тому

    Hey can you do a video for transducer troubleshooting furnace

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      Hey AJ, I think you mean transformer troubleshooting. Just look up "acservicetech transformer" for a video on that, thanks

    • @good0and0bad
      @good0and0bad 5 років тому

      @@acservicetechchannel not transformer. I need some help with Modulating Furnace Transducer Troubleshooting

  • @james8632
    @james8632 10 місяців тому

    What would be the voltage between 4 and 5?

    • @chrisdeanndavison3626
      @chrisdeanndavison3626 9 місяців тому

      The voltage would all depend on the application. In an air handler where the sequencer is switching a heating element, you're typically going to read 120v across 4 & 5 when the switch is open (as long as there are no other devices that are open in the circuit). Then you would read 0v across 4 & 5 when the switch is closed (heat is operating).

  • @Jamie-po9zk
    @Jamie-po9zk 4 роки тому

    what happens if the contacts get stuck closed?

  • @soneeeee4440
    @soneeeee4440 4 роки тому

    hi when these sequencers are failing, do you get chatter/machine gun sound? i'm up north, first freezing cold day today since the winter, -13c. heat pump is off as too cold, aux heat strips took over in the air handler. It is a Trane 4tee3f37b1000aa, system about 12 years old. Noticed when the aux heat starts, there's a machine gun rapid fire/chatter sound at the air handler, right about where the red 20KW line comes in. i'm not really familiar with relays but could it be relays that turn the strips on and off?? (sounds like a machine gun, fairly loud if i put my ear on the panel). Once the heat gets going and the fan is up to speed, it seems to stop, and then starts again a bit when the heat cycle shuts off. I'm still getting aux heat but not sure if the 4 strips are all working 100%. if i lost a strip or 2 out of 4 would the others continue to work or would they all stop?, Is there a fire hazard if either a strip is burnt or relay coils chattering furiously. Or could this noise be something else like arcing at the strips? the system cycles on and off a lot when it's too cold for the heat pump, nothing new but i guess that's normal, since the air is hotter, it gets back to temp fast compared to heat pump. If its a relay, how long can it function like this? is failure imminent? i am diy, have diagnosed and fixed blower motor, module before and other things like outdoor cap.
    Does this sound like a relay problem? thx I can easily open the from panel, just not sure what to look for.

  • @sailingeden9866
    @sailingeden9866 5 років тому

    Is the heat sequencer what causes short cycling?

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      Short cycling can be caused by many different problems. You could turn the power off and then disconnect the heat strips and blower and then turn the power back on to test the low voltage circuit for problems, thanks!

  • @texture6
    @texture6 5 років тому +1

    Normally closed and Normally open. I’m trying to grasp the concepts. Is it On/Off or Off/On. Thanks.

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      yes you will see NC and NO on electrical wiring diagrams or an open line on the circuit if it is NO, thanks

    • @Discretesignals
      @Discretesignals 5 років тому +1

      Normally closed and normally open basically just means what state the switch is in when no power is applied. Most of the time it refers to relays, contactors, sequencers, momentary switches, and devices that have a default position.

  • @mohammedalobaidi9981
    @mohammedalobaidi9981 2 роки тому

    👍👍👍

  • @battlefielding
    @battlefielding 5 років тому

    hey i have a commercial hvac interview saturday... anyone give me any tips or hvac questions they may ask ?

    • @acservicetechchannel
      @acservicetechchannel  5 років тому +1

      Service they may go a little hard on you but if it is mainly an installation position, they will likely be more interested in your safety, lockout tagout, situational awareness, communication with others, and being there before time- not on time. I have had them watching me on camera before my interview in the waiting room so from the time you get out of your car until you get back in your car, make sure you are in tip top shape. Good luck and let me know how you make out, thanks!

    • @battlefielding
      @battlefielding 5 років тому

      AC Service Tech LLC Thanks. i’ll let you know

  • @ralphriffle1126
    @ralphriffle1126 4 роки тому

    So. Cal. Gas calls it a clicks on disc.

    • @acservicetechchannel
      @acservicetechchannel  4 роки тому +1

      Yes it is a bimetal disc that sits on the pan heater and Klixon and Sensata are the manufacturers

    • @ralphriffle1126
      @ralphriffle1126 4 роки тому

      @@acservicetechchannel standard safty inspection for a new water heater with the unitrol valve requires turning up the thermostat nob until the dic clicks verifying its operation. I enjoy your videos.

  • @jolyonwelsh9834
    @jolyonwelsh9834 Рік тому

    What a flimsy design!

  • @DM-jf3lg
    @DM-jf3lg 5 років тому +1

    A great refresher for me. Thanks so much. How about a video on troubleshooting a gas ignition module? Honeywell and Whiterogers.

    • @acservicetechchannel
      @acservicetechchannel  5 років тому

      Thanks DM, have you looked up "acservicetech ignition playlist" I have a bunch of videos out on that subject, thanks