No Hot Water - How To Test Plate Heat Exchanger - Combi Boiler not working

Поділитися
Вставка
  • Опубліковано 9 лют 2025
  • Plumber Training. How to check why your hot water isn’t working. Gas Engineer Training.
    How to repair gas boilers. Testing to see if a plate heat exchanger is blocked.
    How to test and how to find the correct parts.
    Boiler not working how to check.
    Combi Boiler not working, No hot water.
    Blocked plate heat exchanger.

КОМЕНТАРІ • 110

  • @efrygasservices6169
    @efrygasservices6169 4 роки тому +15

    Love this video. This fella showing this test is bang on. In the real world, if you can’t achieve the desired flow rate to carry out the test, you have to use your noggin’ a little more and that is where experience comes in. To the apprentices watching, listen to the old fart that is trying to teach you. We may not be ‘cool’ but the odd few of us know a thing or two. Top effort. 👍

    • @kevincranfield5235
      @kevincranfield5235 4 роки тому +2

      i think that was a compliment? even though you called me an old fart and not cool....?

    • @efrygasservices6169
      @efrygasservices6169 4 роки тому

      @@kevincranfield5235 I’m have often been called an old fart and the working day should be 10:00 haha

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      😂😂😂😂You are both amazing.

    • @antoniogalluccio4213
      @antoniogalluccio4213 9 місяців тому

      When you say if you can't achieve the desired flow rate you are obviously speaking about the secondary side of the plate right. And in this case what would you do?

  • @joedefloat7802
    @joedefloat7802 4 роки тому +16

    Fair play to that man for taken the time to educate both me and others a very informative video thank you.

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @saedsorean378
    @saedsorean378 2 роки тому

    Thanks to Allan and the a lot whoever made the video.this is an amazing video, there no more you need for that particular fault, it is basically a significant help.

  • @RajeshBangera-x8i
    @RajeshBangera-x8i 11 місяців тому

    Very informative video of diagnosis. Also especially finding the ideal boiler parts. Cheers for that.

  • @robwoods8160
    @robwoods8160 4 роки тому +3

    Very good video. Good to share the knowledge. Can't understand why some thumbs down? 👍👍

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @jamesdelaney440
    @jamesdelaney440 2 роки тому +1

    What a fantastic video. Never seen the 2nd test, brilliant and thank you

  • @kevinbrown6066
    @kevinbrown6066 4 роки тому +3

    Great video Alan.
    A big thank you to Ideal man.
    Next video leak in main heat exchanger 👍😂 please.

  • @julianhawker7672
    @julianhawker7672 4 роки тому +3

    Thanks Mr Ideal for taking the time.

  • @mmc537
    @mmc537 4 роки тому +2

    Hi Allen, thanks for your videos. Always learning something new.
    You mentioned that Kevin is sending you lots of in depth videos. Any chance you could put them all in a playlist?

    • @AllenHart999
      @AllenHart999  4 роки тому

      Mr Ideals videos are absolutely brilliant, I also have some other guests on the channel soon. Thanks

  • @michaelrose7258
    @michaelrose7258 3 роки тому

    Absolutely brilliant video Alan. Tried this today at work.
    Thank you

  • @faridratni6799
    @faridratni6799 4 роки тому +3

    This is one of the best video Thank you so much

    • @AllenHart999
      @AllenHart999  4 роки тому

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @avnishkumar9118
    @avnishkumar9118 4 роки тому +1

    Best video to diagnose plate heat exchanger!well done

  • @hamzaparvais3948
    @hamzaparvais3948 3 роки тому +1

    Thank u for sharing knowledge brilliant video help alot bless ya

  • @antoniogalluccio4213
    @antoniogalluccio4213 9 місяців тому

    So to recap first test between hot and cold and check for 35⁰C temperature rise and stable reading. Then test between hot water outlet and pipe between pump and main heat exchanger, there were 20⁰C difference and there should be zero or close to zero. But when it finally became 0 on third attempt, is it because you cleaned the plate or you put the clamps somewhere else? Thanks advance!

  • @SteveN-pw4dj
    @SteveN-pw4dj 3 місяці тому

    Good to know you say competent also as i have had many gas safe engineers do a shit job! Obviously they can pass the tests but are not competent as with a lot of drivers with a licence.

  • @slipperyWhenWatered
    @slipperyWhenWatered 4 місяці тому

    Excellent presentation.
    Thank you.

  • @foxy1960
    @foxy1960 4 роки тому +4

    Very good video ,
    sorry if this question seems silly, On a boiler with a 3 speed pump, Does the speed setting of the pump have any bearing on the heat transfer temperature from the main heat exchanger to the domestic hot water at the plate heat exchanger or will there be no difference what ever the pump speed is

    • @lestc8579
      @lestc8579 4 роки тому +1

      Yes it does..you stick it on 1 on a 3 speed and it will cause you probs

  • @zhangzetong3
    @zhangzetong3 3 роки тому +2

    Hi Allen, i have hot water running very slow in all tap in my apt,do you think is cause block exchanger? Many thanks

    • @Ali-co3xp
      @Ali-co3xp 3 роки тому

      Most likely

    • @rayc1503
      @rayc1503 3 роки тому

      Double check that the water inlet isolation valve hasn't been turned down. The hot water flow usually stays about the same on a blocked plate. As it usually the flow circuit from the main heat exchanger which gets blocked . Check your mains water tap is open fully and follow the cold water feed from the boiler back. Sometimes there's an isolation valve or something similar fitted. This could also reduce the flow to all hot water outlets.

    • @daleprosser350
      @daleprosser350 3 роки тому

      @@rayc1503 the cold water inlet to the plate exchanger could be blocked up with scale if he’s living in that type of area

  • @md4159
    @md4159 2 роки тому

    Great video. Very well explained. Top stuff.

  • @lostinthoughtscalminsilenc8167

    Where did you get the 35c from?

  • @mehransayad
    @mehransayad 4 роки тому +1

    Very good and helpful thank you Allen

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      Glad it was helpful!

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @markstewart1807
    @markstewart1807 2 роки тому

    Thanks Allen have really enjoyed your videos and learned a lot.
    Is it common to have initially very hot water then going luke warm if the Heat Exchanger is block or faulty?

  • @mcginn002
    @mcginn002 4 роки тому +2

    Very informative video 👍

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

    • @mcginn002
      @mcginn002 4 роки тому

      I already am Allen 😉

  • @kevinhancock4064
    @kevinhancock4064 2 роки тому

    Not sure of its a separate issue but a) lack of hot water via taps . Mostly goes cold ..... kitchen tap (,been fine 3+ years now is the only tap mainly that don't cause boiper to ignite . 9ccasionally it'll stop getting up upstairs bath over head shower (mixer. Both are ) a head ache indeed .
    New vaove cartridge here and diverter pump
    Thanks 4 your help

  • @conand1413
    @conand1413 4 роки тому

    Great video and just one quick question:
    What I understand is that the heat lost in the primary circuit between flow and return should be gained by hot water side.?
    Lets say the primary flow was 75c then return 40c. Then the hot water would be 40c? How is that. Bec i thought the hot water temp = cold water in temp + (diff between primary flow and return)
    So lets say cold water is 8 c and the pFlow 75 preturn 50c( meaning a 25c lost to heat hot water) then hot water is 8c+25= 33c
    Sorry if that looks naive

  • @gregbenham5586
    @gregbenham5586 Місяць тому

    The easiest way to test the plate heat exchanger is to touch the top left of the plate and then touch the top right of the plate and if the right hand side is a lot cooler then the plate is getting blocked

  • @tommyblackman7119
    @tommyblackman7119 4 роки тому +3

    Excellent video Allen, great tips and something to take on board. I have the testo probes myself and use for boiler commissioning..
    Can you do a video on balancing radiators using the testo probes... I’ve tied but struggle to get the ideal 11 degree difference between flow and return

  • @simoncarpenter9119
    @simoncarpenter9119 4 роки тому +1

    Brilliant video thanks 👍

  • @davidtwist9242
    @davidtwist9242 4 роки тому +1

    Another excellent video x

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @Mad4plumbing-ltd
    @Mad4plumbing-ltd 3 роки тому

    Brilliant. Engineer 👌

  • @gibfear
    @gibfear Рік тому

    Can anyone help me diagnose my issue - basically turn tap on, might get a little bit of hot for a few seconds (in the PHE?) then cold - then takes ages, a minute maybe of completely cold water, then the hot starts to come through. Once flowing it's fine, stays how, flow rate no problem, runs all day.
    I swapped the DHW spinner last year, when you turn on a tap the sensor lights up solid instantly, boiler seems to start.
    I removed the diverter valve and stripped it, cleaned it in ultrasonic cleaner, put in new seals, rebuilt it with lashings of silicone grease
    Actuator works fine, tap on, tap off it moves in and out and the plunger pushes in no problem in the valve (did before cleaning anyway) - heating outlet not getting hot when waiting for water
    PHE off and cleaned with drain cleaner and in ultrasonic, just a bit of rusty crap coming out, no sludge in there and it's a soft water area so no limescale.... Water flows though both sides well from hose pipe.
    Again once running hot water is more than adequate, heating works fine
    Waiting for a plumber friend to come check gas pressures etc as very rarely do get an ignition failure - can't see it being that as it locks out after 3 failed starts and it's very rare (maybe 1 this year)??? Boiler did have a gas valve about half it's life ago as it had turned into a vuvuzela....
    I'm stumped!! Help lol 😄

  • @rayc1503
    @rayc1503 4 роки тому +1

    Great information there guys. What is pre ABK & ABK onwards when it relates to ideal boilers? Any answers people? 👍

    • @kevincranfield5235
      @kevincranfield5235 4 роки тому +2

      It’s the prefix, the 3 letters before the 15 numbers of the serial number. So for instance if you had a prefix which read ABE that’s pre ABK, and onwards would be alphabetic letters after that?!! Does that make sense.

    • @rayc1503
      @rayc1503 4 роки тому

      @@kevincranfield5235 excellent understood, thank you. Thanks for the clarification 👍

  • @peterhyatt6751
    @peterhyatt6751 4 роки тому +1

    Mate how much would you charge to do install training? I’m gas safe, but all my gas is servicing, I want to push into installs and breakdowns but there’s no where for me to actually learn installs properly.

    • @adamwilliams5372
      @adamwilliams5372 4 роки тому

      I'm in the same boat as you mate it's tricky. I took a job on installs and was told I would be trained. then when starting someone turned up to "watch me" change a system to combi. made me feel like a right nob then laid me off 2 weeks before Christmas after I'd been honest and told them I wasn't an experienced installer at the interview. I left a well paid job fitting meters for that as well. Awful company

  • @edmetcalfe8974
    @edmetcalfe8974 3 роки тому

    I'm assuming the tests in this video apply to all makes/models of Combi Boiler, not just Ideals?
    Is it also correct that you can check the temperature of the primary circuit flow and return in and out of the PHEX and that a temperature difference of more than 20 degrees indicates a blocked PHEX? I'm sure I've read this somewhere but can't recall where.

    • @kevincranfield5235
      @kevincranfield5235 3 роки тому

      No this is just the logic only due to its design, other designs may vary slightly in temperature depending on where you put your temp clamps.

  • @chrisi970
    @chrisi970 4 роки тому +2

    Thanks very helpful 👍

  • @douglaughton7626
    @douglaughton7626 4 роки тому

    At the very end I found the part number ID to be very helpful , sick of wasting time with wrong parts. Unfortunately though he said the part was 121 and this then showed two listed 121 plate heat exchangers. I assume for different kw outputs. But which one would you chose. My supplier is clueless and I have to order exact part numbers. I would love to say get mea plate heat ex for ....
    But I then would get the wrong part.

    • @kevincranfield5235
      @kevincranfield5235 4 роки тому +2

      177529 - 24kw, 177530 - 30 & 35kw, this is the latest model, on older models this would obviously be a different part no.

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @iheggis86
    @iheggis86 4 роки тому +2

    what would happen if you put a 35kw plate on a 24kw ideal combi?

    • @kevincranfield5235
      @kevincranfield5235 4 роки тому +2

      Not a lot really unless you reprogrammed the pcb and changed the injector.

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      👍👍👍

  • @markplampton7539
    @markplampton7539 Рік тому

    Excellent info

  • @marksawyer708
    @marksawyer708 3 роки тому

    Very knowledgeable....cheers.

  • @brendanmoran9516
    @brendanmoran9516 3 роки тому

    Great video 👍😊

  • @kraglelove5013
    @kraglelove5013 4 роки тому +1

    Good video

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @alienbear892
    @alienbear892 3 роки тому

    Im relatively new to boilers and I was inspecting a hot water issue today with a eco Tec pro 28 combi boiler. Visually I could see major scale at the cold inlet to the plate heat exchanger. In addition the hot water appeared to be running well until suddenly it stopped coming out the faucet, then continued after about 12 seconds. I'm pretty sure it was the plate but does anyone have any other ideas? Wasn't isolation valves as none existed on the pipework....note: the water did reach requested temperature prior to cutting out. My guess is it's a sedement blockage, but any other suggestions are welcomed. Thanks ppl.

  • @frosty_soda
    @frosty_soda 3 роки тому

    how did you calculate the cold water temperature rise (the 35 degrees)?

    • @daleprosser350
      @daleprosser350 3 роки тому +1

      It’s in the manufacturers instruction, they state what the boiler is able to deliver (temperature rise) and the maximum flow rate it can give you that rise at

    • @frosty_soda
      @frosty_soda 3 роки тому

      @@daleprosser350 do you mind explainging what that means, in the manual it has:
      DHW Flow Rate (for C 35) at 35 degree's C temp. rise = 14.5 l/m
      DHW Specific Rate (for C 35) = 16.9 l/m
      What is Specific Rate and I am a little baffled with the two Rates. Thanks again mate

    • @daleprosser350
      @daleprosser350 3 роки тому

      @@frosty_soda to be honest I’m not sure about Specific Rate and why they have the two rates

  • @B1cam
    @B1cam 4 роки тому +2

    Good tip that. 👍🏽

  • @Exgasman9072
    @Exgasman9072 4 роки тому +1

    couldn't the diverter valve be letting by not giving the temp rise?

    • @kevincranfield5235
      @kevincranfield5235 4 роки тому +2

      If you listen in the beginning I mention that the diverted valve or stepper paddle could be passing heat down the flow pipe

    • @AllenHart999
      @AllenHart999  4 роки тому

      👍👍👍👍

  • @julianterziiski9511
    @julianterziiski9511 4 роки тому

    Hi,
    What is the reason of having a hot water coming out only when is on full flow rate and when reduce the flow rate is getting cold?
    Regards
    Julian

    • @AllenHart999
      @AllenHart999  4 роки тому

      Blocked plate maybe?

    • @AllenHart999
      @AllenHart999  4 роки тому

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

    • @daleprosser350
      @daleprosser350 3 роки тому

      I would think the flow sensor for the hot water may be faulty and the low flow rate may not be registering with the sensor

  • @reghy2008
    @reghy2008 4 роки тому +2

    Good 👌

  • @jassinghIG45
    @jassinghIG45 4 роки тому +3

    I always worked on the principle a max of 5c dt it’s ok. Good to know though. I was working on Vaillant parameters.

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @simonmander4314
    @simonmander4314 4 роки тому

    Can anyone recommend good temp clamps that fit Anton analysers? Not sure if any clamps are interchangeable with any analyser???

    • @kevincranfield5235
      @kevincranfield5235 4 роки тому +1

      All you need are the AS10 clamps, think they are about £20 ish, they should for in Anton and Kane analysers. 👍

    • @vipergas5542
      @vipergas5542 4 роки тому +1

      to fit a Anton the connection is K type connection

  • @veronicahart450
    @veronicahart450 4 роки тому +1

    👍👍👍👍👍👍👍 very good

  • @leaturk11
    @leaturk11 3 роки тому

    Great stuff

  • @jameshawkins5280
    @jameshawkins5280 4 роки тому

    Great video yet again from ideal man only thing I would add is he should have tested the cold water flow rate as it could be the cold feed could have only been 10 litres per minute so putting a 35kw boiler in and thinking you would achieve 16 litres , always check water pressure and flow rates on a cold tap before you install a boiler .

    • @kevincranfield5235
      @kevincranfield5235 4 роки тому +4

      I never thought I would achieve 16 litres per minute when I installed my boiler, I put a larger boiler in knowing I would infact get a better delta t, temperature rise because I had a lower water flow rate, I just forgot what my flow rate was when I was making the video and then realised I could not get the 16, it was the reason you saw in the video why I put in.a 35kw so I could get a temp diff way over 35 degrees.

  • @antonybuckley2645
    @antonybuckley2645 3 роки тому

    Brilliant

  • @baitrunner1000
    @baitrunner1000 4 роки тому +2

    You’ll only getting 10 litres a min out that tap because it has a restrictor in it. Otherwise that tap would spray out the sink!

    • @jamesbroadbent2574
      @jamesbroadbent2574 4 роки тому

      That's a bath

    • @kevincranfield5235
      @kevincranfield5235 4 роки тому +3

      Ya know, your probably right and it makes sense when you say that, but it never crossed my mind, I will level with you all, you may think from my videos that I know a lot about our industry but infact I don’t, I have never been a plumber, only a gas engineer, trained by BG, never done any renewables but stuck to my one discipline in the theory I can get really really good at the one subject rather than spread myself too thinly across a broad range of products, and be average at them all, that was my thinking so I really do not know much about plumbing etc. So I will share what I know and hopefully be educated too along the way. 👍

    • @adamwilliams5372
      @adamwilliams5372 4 роки тому +1

      @@kevincranfield5235 fair play to you mate at least you're taking time to try and educate. so few people want to help anyone in this trade who wants to actually learn

    • @AllenHart999
      @AllenHart999  4 роки тому

      You are doing an amazing job educating people with these videos. I really enjoy them and are very grateful. Thank You

  • @songzhou
    @songzhou Рік тому +1

    If reduce to 10mins, much better.

    • @AllenHart999
      @AllenHart999  Рік тому +1

      What do you mean? Thanks.

    • @AllenHart999
      @AllenHart999  Рік тому

      Thanks very much for your comment, please consider subscribing to support the channel 🙂

  • @rogerford30
    @rogerford30 4 роки тому +1

    👍

  • @vipergas5542
    @vipergas5542 4 роки тому

    👍👍👍

  • @secondchance4498
    @secondchance4498 4 роки тому +1

    Having watched Toms top tips ua-cam.com/video/CeVRy_QQDeY/v-deo.html do I need to bother watching? :p
    Edit: Great video. I'm training, so perhaps more useful to me than for others, but some valuable info.

    • @AllenHart999
      @AllenHart999  4 роки тому +1

      I love to watch Tom,s Videos. I would love to meet him one days.

  • @paulb8340
    @paulb8340 3 роки тому

    You Need some editing skills a tripod and a decent microphone if your gonna do these vidz!!