  • @michaeljavert4635
    @michaeljavert4635 Рік тому +18

    Box is likely grounded, but better practice is to bond it to the ground. The steel armor and box are conductive, so it's grounded that way. Also the ground screw on receptacles also have continuity to the metal parts that screw the receptacle to the box, so there is a ground present even in the absence of a ground wire, in that case. But always use the ground wire and always bond it.
    Also use the top and bottom screws and a nut. The center screw can come loose, and also the pressure of plugging things in can weaken the outlet and wear it out prematurely.

    • @boltkane6827
      @boltkane6827 10 місяців тому +3

      That's right. It is a code violation to install a receptacle to a cover the
      way it is is done in this video. NEC 406.5(C)

  • @nathangriffin9893
    @nathangriffin9893 Рік тому +8

    I work at southwire mc plant where this cable is manufactured, you do not need that tool. Break the armoring and cut it with tin snips.

  • @richarda.valdes1197
    @richarda.valdes1197 9 днів тому +1

    I was searching the subject to see what should be done about the raised rib on the metal post

  • @michaelking42
    @michaelking42 Рік тому +2

    Mate, I'm an electrician from Australia, living in Florida now. I find it crazy how difficult you yanks make electrical work. Living here, I almost have to relearn the entire trade. Thanks for the info, and also to the commentary above and below for their input. Makes it a little easier to figure this stuff out.

  • @JohnThomas-lq5qp
    @JohnThomas-lq5qp 2 роки тому +9

    Best practice is to use the two provided 6 - 32 screws to attach receptacles to metal cover rather then only the center screw that usually comes loose. After cutting Type AC or MC cable cut the sharp edge at a 45 degree angle then install red anti short bushing.

    • @ericarona8599
      @ericarona8599 Рік тому

      Those screws aren't "provided"? It comes with only one in the center

    • @JohnThomas-lq5qp
      @JohnThomas-lq5qp Рік тому +1

      The 1900 duplex receptacle covers that I purchased at several electrical supply houses always had two 6/32 screws along with hex nuts that often had flimsy lock washers attached or small piece of metal for 6/32 screws to screw into. I always had a plastic hinged storage box that contained an assortment of 6/32 & 8/32 screws, flat washers, hex nuts & lock washers.

    • @ericarona8599
      @ericarona8599 Рік тому +1

      @@JohnThomas-lq5qp The cover plates had those break off tabs that I just used and worked great

  • @mikeryan6277
    @mikeryan6277 2 роки тому +11

    Box needs to be bonded as well as grounding the devise, and MC Cable needs to be secured.

    • @cannoncolossus2449
      @cannoncolossus2449 2 роки тому

      Good comment. The ground should be bonded to the box and MC cable secured. The way presented in this video is potentially dangerous in the long term and will not pass inspection. Otherwise good video.

    • @tot2600hrs
      @tot2600hrs 2 роки тому

      Forgot the anti chaffing grommet inside MC cable.

    • @sercansakizoglu967
      @sercansakizoglu967 11 місяців тому

      exactly he didn't ground the box right ?

  • @manuelfuentes8741
    @manuelfuentes8741 6 місяців тому +1

    Good job my friend

  • @domofishing9316
    @domofishing9316 3 роки тому +12

    Notice the switch has bottom screw with yellow cap which would ground, but will it need a pigtail to the metal box to ensure proper grounding?

    • @bsmith8564
      @bsmith8564 2 роки тому +1

      Yes on a raised cover.

  • @bigbawls81
    @bigbawls81 3 роки тому +1

    Very informative. Thanks for sharing Big Dan.

  • @fatherappel1792
    @fatherappel1792 10 місяців тому +1

    I understand that the socket should be grounded to a metal outlet box. However, I've also read that you can never ground to the structure. So what should be done when using a metal box on a metal frame??

  • @randellwolfe4555
    @randellwolfe4555 Рік тому

    Great video!, helped me as it was first time I have installed outlet in metal box

  • @heted1
    @heted1 2 роки тому

    Great video. Thanks for sharing.

  • @DJsHotRodFab
    @DJsHotRodFab Рік тому

    Thank you for passing on your knowledge.

    • @barryely1
      @barryely1 Рік тому +1

      There isn't much knowledge here. This video should he deleted. Box isn't bonded and anti short bushing wasn't used.

    • @DJsHotRodFab
      @DJsHotRodFab Рік тому

      @@barryely1 you are correct. I used anti short bushings on my wiring and bonded all metal boxes

  • @randybarnes6661
    @randybarnes6661 2 роки тому +1

    Thanks for sharing your knowledge buddy

    • @barryely1
      @barryely1 Рік тому

      There isn't much knowledge here. This video should he deleted. Box isn't bonded and anti short bushing wasn't used.

  • @Steven-eh9qs
    @Steven-eh9qs 3 роки тому +3

    I want more videos like this, hes seems very knowledgeable.

    • @JBarnes917
      @JBarnes917 3 роки тому +3

      To bad he missed the box being bonded with the ground. This is an NEC code issue.

    • @CHEECHMUN
      @CHEECHMUN 3 роки тому +1

      @@JBarnes917 So is an extra wire from the green screw, needed to go directly to metal box?

    • @JBarnes917
      @JBarnes917 3 роки тому +1

      @@CHEECHMUN exactly, there is a spot in the back of the box that a ground screw is made to go in. You can get pre made pigtails that have the screw and a short green wire on it.

    • @CHEECHMUN
      @CHEECHMUN 3 роки тому

      @@JBarnes917 Thank you!!!

    • @barryely1
      @barryely1 Рік тому +2

      There isn't much knowledge here. This video should he deleted. Box isn't bonded and anti short bushing wasn't used.

  • @NYTROeast
    @NYTROeast Рік тому +3

    Should you be doing a jumper from the ground to the box so the box is grounded also since it is a metal box fastened to a metal building?

  • @Geno-j5g
    @Geno-j5g Місяць тому

    Why didn’t you make hooks on the screws? 1st yr apprentice here I was always told to hook it this is so much easier!

  • @garbo8962
    @garbo8962 11 місяців тому +1

    And where are the two screws that come with the cover? Would not pass inspection in my area with just the flimsy single 6/32 screw .Hospital that I did a lot of electrical work in would only allow connectors that used locknuts. Smart using type MC cable that has a insulated copper real deal ground conductor verses the flimsy #16 or 18 guage aluminum wire that's inside type AC ( BX ) cable. You should have use a ground screw to ground the metal box. Extremely dangerous if the two 8/32 screws come loose or fall out then box is not grounded.

  • @jimcole6423
    @jimcole6423 2 роки тому +3

    You can use any jacketed conductors in a metal building that will be enclosed.

  • @LiloUkulele
    @LiloUkulele 2 роки тому

    After my shop burned down I'm rebuilding with metal. Time to learn how to use shielded cable.

  • @donaldlee6760
    @donaldlee6760 2 роки тому +1

    At 1:04 - that cutting disk reminds me of a dremel cutting disk. I wonder if one has a dremel tool and they don't need to cut MC cable as part of their daily job, then one could just use their dremel?

    • @michaelking42
      @michaelking42 Рік тому

      It would be very easy, but easy to cut the wire insulation as well.

  • @jasnapon
    @jasnapon 11 місяців тому +1

    That outlet should be grounded to the metal box as well

  • @brandonm922
    @brandonm922 3 роки тому +8

    Box wasn’t grounded, receptacle wasn’t wrapped in electrical tape on the conductors and ground should go up but everything else was right to me. Great way of explaining!

    • @trustme7731
      @trustme7731 3 роки тому +8

      Tape isn't necessary or required. There is no requirement for the position of the ground.

    • @ABflanagan523
      @ABflanagan523 2 роки тому +2

      I agree that the box wasn’t making direct contact to the ground wire but the MC and metallic box is an equipment grounding conductor.

    • @JBarnes917
      @JBarnes917 2 роки тому +8

      @@ABflanagan523 needs a ground pig tail period… THIS WILL FAIL A REAL INSPECTION.

    • @jcjammer1
      @jcjammer1 2 роки тому +1

      No red bushing before connector?

    • @jimchang9394
      @jimchang9394 2 роки тому +3

      It's bounded,The 20 A receptacle with the gold clip is a self-bonding mechanism.

  • @keithharrington8715
    @keithharrington8715 2 роки тому +2

    As an electrical guy, I know that videos are there to inspire. Please do not take them as a step by step instruction as the code allows each building department (Jurisdiction) to adjust (interpret) the code as written.
    Many commentors pointed out several code misses:
    210.8. Gfci for homes puts "out buildings" under garage requirements.
    547. Is for "AGRICULTURAL BUILDINGS" with wiring method restrictions based on the animals kept there.
    Anyone can put a wire under a screw, but which screw is where the money is made. You can learn and do yourself, but calling the building inspectors or a local guy that just did that same job last week might get you a solution to a problem you never knew you had.

  • @nsbconstruction9698
    @nsbconstruction9698 3 роки тому +8

    No ground to the box?

    • @JBarnes917
      @JBarnes917 3 роки тому +4

      Glad I’m not the only one yelling at the screen. These residential rats shouldn’t be teaching.

    • @Faruk651
      @Faruk651 2 роки тому

      these are hacks

    • @jcjammer1
      @jcjammer1 2 роки тому +1

      I Always use metal conduit.
      No chance of getting snagged and unraveled.
      just my personal choice.😄

    • @joselovos6708
      @joselovos6708 Рік тому

      @@JBarnes917 old stile

    • @JBarnes917
      @JBarnes917 Рік тому

      @@joselovos6708 old? It’s illegal and it’s dangerous

  • @kenjares6719
    @kenjares6719 3 роки тому

    Thanks. I was looking for this info

    • @barryely1
      @barryely1 Рік тому

      There isn't much knowledge here. This video should he deleted. Box isn't bonded and anti short bushing wasn't used. I hope you search for other videos showing the correct way of doing this.

  • @sammymiller5967
    @sammymiller5967 Рік тому +2

    You need to add a red ear on your MC cable first

    • @tomnorman5461
      @tomnorman5461 Рік тому

      It's called an 'anti-short bushing' in my neck of the woods. The snap-in connector he's using has this built-in.

    • @TerryRGraham
      @TerryRGraham 10 місяців тому

      @@tomnorman5461 No, that built-in doesn't replace the anitishort bushing. It will fail inspection.

  • @stevevojack9092
    @stevevojack9092 2 роки тому +3

    Using the 14 gauge stripper on the 12AWG nicks and compromises the conductor (especially when you rotate it), no anti-short bushing installed. What I expect from a 6 month apprentice.

    • @mattozx6rr
      @mattozx6rr 2 роки тому +3

      The anti short bushing is only required on AC cable. You do not need it on MC cable if you use a roto cutter then clean the square end up for a flush mount in the connector. That said I would still use an anti short bushing just for extra insurance and peace of mind.

  • @timothymcvay7286
    @timothymcvay7286 3 роки тому

    Awesome video

  • @santiagodominguez2522
    @santiagodominguez2522 3 роки тому

    Good job!!!

  • @JohnThomas-lq5qp
    @JohnThomas-lq5qp 2 роки тому +1

    No such thing any more in the NEC called a neutral. AHOLES changed one of the most common electrical term that was used for over a hundred years to " Grounded Conductor " . Best to spend a little extra & purchase at least Spec grade receptacles. Will last a lot longer. Now must use a torque driver or torque wrench to tighten All ELectrical terminals. Not a plug , A plug goes on the end if a cord to plug into a receptacle.

  • @Kevin-wj4ed
    @Kevin-wj4ed 3 місяці тому

    What are the violations?

  • @stevestewart3816
    @stevestewart3816 Місяць тому

    At 2:47 he realized he fucked up lol

  • @blainekeener6100
    @blainekeener6100 3 роки тому +5

    Counted 4 code violations

  • @F16_viper_pilot
    @F16_viper_pilot 8 місяців тому

    Um, no ground to the box?? That ground wire should be attached to the box, not the outlet, and a grounding pigtail attached from the box to the outlet grounding screw.

  • @jesseexum1084
    @jesseexum1084 5 місяців тому

    What size fittings are these and where did you get them?

  • @effthegop
    @effthegop Рік тому +2

    No "special tool" required. I retired after 45 years and never used a roto tool. Just bend carefully until the sheath comes apart and snip it with your sharp diagonal cutters. Quicker, easier and no extra cumbersome tools to carry.

    • @tomnorman5461
      @tomnorman5461 Рік тому +1

      Although 'dikes' will work in a pinch, a 'ROTO-SPLIT' is faster and does a much 'cleaner' job of stripping the MC.

    • @effthegop
      @effthegop Рік тому

      @@tomnorman5461 Sounds like a wager :).
      I'll take it !

  • @blacksteel2434
    @blacksteel2434 3 роки тому +1

    You didnot wrap your wire around the outlet screws what in the word

  • @christopherdegarmo9826
    @christopherdegarmo9826 3 роки тому +2

    bond the box.......

  • @Trumptrain2024Vance
    @Trumptrain2024Vance 3 роки тому +2

    What company did you use for the building!!!

  • @sammymiller5967
    @sammymiller5967 Рік тому +2

    The man seems like a nice guy but he is doing it all wrong do not do it his way

  • @michaelblanton9782
    @michaelblanton9782 5 місяців тому

    Where is the ground connection to the metal box?

  • @JuanGarcia-nj9dk
    @JuanGarcia-nj9dk 3 роки тому

    Whats was your investment this building including your concrete slab?

  • @gguerrero5503
    @gguerrero5503 Рік тому

    What's the name of the fasteners used at 3:09 and following?

  • @sercansakizoglu967
    @sercansakizoglu967 11 місяців тому

    did he ground the box as well ?

  • @hightowerelectricllc6132
    @hightowerelectricllc6132 3 роки тому +9

    FAILED!
    1) No anti-short bushing for your MC
    2) Receptacle is not GFCI protected, all garages need to be
    3) MC cable not properly supported
    4) Did not properly support the receptacle devise to the RS cover. That middle screw is not a means of support only the top and bottom yoke

    • @recon1314
      @recon1314 3 роки тому +1

      The type of connector he used has a built in "anti short" sleeve in the throat. 100% on board with a fail for everything else

    • @jimyeats
      @jimyeats 3 роки тому +2

      @@recon1314 That redhead at the end of the connector is just to protect the wires from the end/edges of the connector, you still need a redhead at the end of the mc cable where the wire would rub on that. Really truly.

    • @garagekeys
      @garagekeys 2 роки тому +1

      Anti-short bushing I thought is not required with MC that is optional

    • @jimyeats
      @jimyeats 2 роки тому

      @@garagekeys Maybe in certain codes and jurisdictions? Do you want your thinly coated wire rubbing on a sharp MC edge? Super easy and cheap insurance.

    • @garagekeys
      @garagekeys 2 роки тому

      @@jimyeats yeah, I looked in the NEC 320.40 states AC cable needs the bushings not MC it's optional it looks like if you follow NEC

  • @soullessdevice
    @soullessdevice 2 роки тому

    Well yeah, everything is easy

  • @jamesbrenneman6841
    @jamesbrenneman6841 3 роки тому

    Thanks great video

  • @surferdude642
    @surferdude642 2 роки тому

    I assume that the box is grounded by the mc, but you should use the ground wire to ground the box and there is no need to attach a wire or pigtail to the receptacle. When the receptacle is mounted to the cover and the cover is mounted to the box everything is grounded. The receptacle has a self grounding strap on the lower yoke. The cover comes with screws and nuts to mount the receptacle securely and you didn't use those. The screw connection between the receptacles becomes optional.
    The 20 amp receptacle is ok, but unnecessary, a 15 amp commercial spec grade would be my choice, 15 or 20 amp circuit, it doesn't matter.

    • @JBarnes917
      @JBarnes917 2 роки тому

      1. You need to learn difference between “grounded” and “bonded”.
      2. That receptacle needs a ground wire going to the box. Please read NEC 250.146, cover mounted wiring devices are NOT considered grounded.

    • @surferdude642
      @surferdude642 2 роки тому

      @@JBarnes917 Thank you for the comment, but I believe that it's justified in this case. See NEC 250.146 exception (A). If he was using a receptacle with a self grounding strap, such as a Leviton spec grade, exceptions (A) and (B) would apply. Am I missing something here?

    • @JBarnes917
      @JBarnes917 2 роки тому

      @@surferdude642
      NEC 2005 Handbook commentary:
      The main rule of 250.146 requires an equipment bonding jumper to be installed between the device box and the receptacle grounding terminal. However, 250.146(A) permits the equipment bonding jumper to be omitted where the metal yoke of the device is in direct metal-to-metal contact with the metal device box and at least one of the fiber retention washers for the receptacle mounting screws is removed, as illustrated in Exhibit 250.52.
      Cover-mounted wiring devices, such as on 4-in. square covers, are not considered grounded. Section 250.146(A) does not apply to cover-mounted receptacles, such as the one illustrated in Exhibit 250.53. Box-cover and device combinations listed as providing grounding continuity are permitted.

  • @sammymiller5967
    @sammymiller5967 Рік тому

    You first need to ground your box then your plug in

  • @brents927
    @brents927 2 роки тому +2

    I don't want the camera man's comments

  • @garagekeys
    @garagekeys 2 роки тому +1

    I don't think you should be using that MC cable if it's not going to be covered up, I thought that it was not supposed to be exposed locations where there can be damage

    • @caliguy1500
      @caliguy1500 2 роки тому +1

      Section 330.15 states: Exposed runs of cable, except as provided in 300.11(A), shall closely follow the surface of the building finish or running boards. Exposed runs shall also be permitted to be installed on the underside of joists where supported at each joist and located so as not to be subject to physical damage.
      Type MC Cable without an outside nonmetallic jacket can be installed in an “other space used for environmental air” in accordance with Section 300.22(C). These cables can be installed either indoors or outdoors and in exposed and concealed locations. ... They can be installed in a cable tray or in any raceway.

  • @imbradleymi
    @imbradleymi 3 роки тому

    What box is this? I would like to use them for my shop.

  • @OU8Aspark
    @OU8Aspark 3 роки тому

    Can you tie multiple outlets together?

  • @ourv9603
    @ourv9603 3 роки тому +1

    I bought a brand new house. The contractor was thoughtful
    enough to give me 5 outlets on each wall. The outlets are fed
    with 20Amp breakers. Each outlet is wired with yellow 20Amp
    romex. HOWEVER, each outlet is 15Amp. How that passed
    inspection is beyond me. I'm having to replace all the outlets
    with 20Amp.
    !

    • @frank480
      @frank480 3 роки тому +10

      NEC allows the use of 15 Amp rated outlets on 20 Amp branch circuits.

    • @wheelzup7597
      @wheelzup7597 3 роки тому +7

      That will definitely pass code, it’s within spec.

    • @garagekeys
      @garagekeys 2 роки тому +7

      I believe you are allowed to use 15 amps outlet on 20 amp circuit, just not a 20 amps plug on a 15 amp circuit can't do that

    • @donaldlee6760
      @donaldlee6760 2 роки тому +2

      FYI - the reason it passed inspection is because it is safe to use 15 amp outlets on a 20 amp circuit. Obviously it is dangerous to do the opposite (plug your 20 amp device on a 15 amp circuit and possibly causing a fire).

    • @KevinCoop1
      @KevinCoop1 2 роки тому +2

      @@TheBigDanShow You stayed metal buildings are required to have 20 amp receptacles on 20 amp circuits. Where does this rule come from?

  • @santiagodominguez2522
    @santiagodominguez2522 3 роки тому

    We build those metal shops where you buy yours

  • @davidvelen9835
    @davidvelen9835 22 години тому

    Outlet is not bonded to the metal box, wire not wrapped into a "J hook" and attached to the screw terminals correctly. Wiring is no hobby, call an electrician.

  • @markdesilvey454
    @markdesilvey454 2 роки тому +6

    Many violations. Nowhere close to a professional install.

    • @Kevin-wj4ed
      @Kevin-wj4ed 3 місяці тому +1

      What are the violations? I want to learn.

  • @timothymcvay7286
    @timothymcvay7286 3 роки тому

    So how do you wire the panel

    • @JBarnes917
      @JBarnes917 2 роки тому

      If you have to ask here then you shouldn’t be doing it

  • @justincloncs1116
    @justincloncs1116 Рік тому

    Box needs grounded

  • @oldnbroke1544
    @oldnbroke1544 Рік тому

    You should pull this video...box isn't bonded, the receptacle is upside down...you sir are unsafe...

  • @brandonrippeonphoto
    @brandonrippeonphoto 11 місяців тому +1

    No red eye; no box bonding. amateurs should not be making how to videos for electrical work…

    • @TheBigDanShow
      @TheBigDanShow  11 місяців тому

      Lol

    • @wisdomcalls2475
      @wisdomcalls2475 11 місяців тому

      Q. Shouldn’t you be bonding the metal frame building to ground due to lightning strikes 🤔

  • @JBarnes917
    @JBarnes917 3 роки тому +5

    Guy didn’t bond the box with the ground.. this is basic NEC code knowledge. You WILL fail an electrical inspection and it’s just not safe. He should stick to changing light bulbs.

    • @ABflanagan523
      @ABflanagan523 2 роки тому +1

      Outlet is grounded due to the yoke making contact with the metallic box. I agree there’s no pigtail from the 12-2 to box and box to outlet but it is grounded, just not the way you’d expect.

    • @JBarnes917
      @JBarnes917 2 роки тому +1

      @@ABflanagan523 wrong… open your code book. 250.148(c) if you have a metal box it needs a ground screw and pig tail. Again this install will fail an inspection.

    • @Faruk651
      @Faruk651 2 роки тому

      @@ABflanagan523 We use metal boxes for residential and commercial in Ontario, Canada. No plastic crap. And we have to ground the metal boxes and devices by code.

    • @ABflanagan523
      @ABflanagan523 2 роки тому +1

      @@JBarnes917 250.146 (A) Surface Mounted Box. Where the box is mounted on the surface, direct metal to metal contact between the device yoke and the box or a contact yoke or a self grounding receptacle shall be permitted to ground the receptacle to the box.

    • @JBarnes917
      @JBarnes917 2 роки тому

      Wrong
      NEC 2005 Handbook commentary:
      The main rule of 250.146 requires an equipment bonding jumper to be installed between the device box and the receptacle grounding terminal. However, 250.146(A) permits the equipment bonding jumper to be omitted where the metal yoke of the device is in direct metal-to-metal contact with the metal device box and at least one of the fiber retention washers for the receptacle mounting screws is removed, as illustrated in Exhibit 250.52.
      Cover-mounted wiring devices, such as on 4-in. square covers, are not considered grounded. Section 250.146(A) does not apply to cover-mounted receptacles, such as the one illustrated in Exhibit 250.53. Box-cover and device combinations listed as providing grounding continuity are permitted.

  • @DAVADMDAVAD
    @DAVADMDAVAD 2 місяці тому

    I need tu git ma Prescribe fer ma medsin.

  • @garyhobbs249
    @garyhobbs249 3 роки тому +3

    He didn’t ground the box lmao

    • @morehp1
      @morehp1 3 роки тому +3

      It’s a structure metal building the the panel is grounded to the structure, that box is screwed to the building, metal to metal, it’s grounded.

    • @garyhobbs249
      @garyhobbs249 3 роки тому +2

      If you had your master electrical license then you’d understand

    • @ABflanagan523
      @ABflanagan523 2 роки тому

      @@garyhobbs249 Seems you don’t. I agree good practice would be to run a pigtail from the box to the outlet for a solid ground but with a metallic box and MC it’s an EGC.

    • @JBarnes917
      @JBarnes917 2 роки тому

      @@morehp1 no ground screw or ground tail in box so it’s not bonded. Learn the difference between grounded and bonded…. When you get an electrical license let us all know

    • @garagekeys
      @garagekeys 2 роки тому

      @@morehp1 is that allowed by code?

  • @terrydougherty7078
    @terrydougherty7078 2 роки тому

    Please don’t follow any of these “tips”. Call a professional.

  • @trustme7731
    @trustme7731 3 роки тому +14

    Multiple code violations. Leave the electrical work to the professionals.

    • @trustme7731
      @trustme7731 Рік тому +1

      @@TheBigDanShow It doesn't meet the NEC requirements which are minimum requirements.
      Fire is not the only hazard with electricity.

    • @jaxchristian6408
      @jaxchristian6408 9 місяців тому +15

      Ya . Keep it a secret. Act like you guys are the only ones that can install an outlet

    • @jessicakeefer5077
      @jessicakeefer5077 2 місяці тому

      Come down on your prices and we will 😌

    • @trustme7731
      @trustme7731 2 місяці тому

      @@jessicakeefer5077 Would you shop for the cheapest heart surgeon?

    • @trustme7731
      @trustme7731 2 місяці тому

      @@jessicakeefer5077 So, you are willing to live with, or die from, illegal electrical work?

  • @theshop5331
    @theshop5331 6 місяців тому

    good grief

  • @garagekeys
    @garagekeys 2 роки тому

    Do yourself a favor.... Call a pro