Daikin Minisplit Not Cooling Normally. Finding and Repairing a Refrigerant Leak EP92

Поділитися
Вставка
  • Опубліковано 16 лип 2022
  • Found a Daikin Minisplit was not cooling properly. Weighed the charge and found the unit was short 1 lb and change. I performed a nitrogen pressure test found and repaired the leak. Also how to use a CPS torque wrench.
    nighthawkhvac
    nighthawk_hvac
    Intro and Outro Music
    "Alive" by CHOIX
    #nighthawkhvac #hvac, #hvaclife, #airconditioning #maintenance, #trane #varitrac #heating, #cooling #refrigerator, #refrigeration #refrigerationcycle #airflow #refrigerant #techlife #installation, #hvachacks, #tools, #furnace, #tech, #electric, #residential, #commercial, #heat, #comfort, #ac, #hvacservice, #hvactools, #repair#toolreviews #fieldpiece #aircon #zoning #honeywell #zonedamper#packageunit #howto #VAV #exhaustfan #Ignitor #trane #TXV #expansionvalve #Intellipak #Trane #Self-contained #Boiler #Coolingtower #noisyinducer #noisyidm #failedIDM #condenserinattic #failedinducerdraftmotor #howtocleancoils #condensercoilcleaning #sparkignitor #nospark #minisplit #mitsubishi #ductless #powerboard #powerboardreplacement #short #outdoortxv #watersourceheatpump ###highpressuretrip#bloweralwayrunning #daikin #torquewrench #sparkignitor #ICM #reversingvalve #nucalgon #iwaveR#iwave
  • Навчання та стиль

КОМЕНТАРІ • 15

  • @nethoncho
    @nethoncho 2 роки тому +1

    Thanks for sharing your video. Nice to find an easy fix

  • @deanmartin1966
    @deanmartin1966 2 роки тому

    Nice job. Thanks for sharing.

  • @williamhawkes7194
    @williamhawkes7194 2 роки тому +1

    Great looking pressure kit

  • @tonydelgrego2906
    @tonydelgrego2906 2 роки тому

    Nice troubleshooting and repair

  • @scottk0623
    @scottk0623 Рік тому +1

    Nice job👍

  • @NTalache
    @NTalache Рік тому

    Do you not remove the schrader cores? The access to service valves on these units are horrible for a 5/16 Schrader core remover. Is it easier to just leave them in and use the 45 ball valves like you got here?

  • @sergiodoordie319
    @sergiodoordie319 6 місяців тому

    My recovery machine is a home depot bucket

  • @sameermohammed3949
    @sameermohammed3949 11 місяців тому

    What torque wrench is that that you're using ?.

  • @eddiegomez3628
    @eddiegomez3628 2 роки тому +1

    I have a question about vacuum and getting under 500 microns. Since you pulled under 500 micron mark, Does it matter that the micron numbers jump back up as your getting ready to charge the system?

    • @NighthawkHVAC
      @NighthawkHVAC  2 роки тому +1

      As long as it stays well below 1000 microns you’re good.

    • @eddiegomez3628
      @eddiegomez3628 2 роки тому

      @@NighthawkHVAC Thank you for that 😀

  • @kellsieevans3847
    @kellsieevans3847 Рік тому

    I have three daikin heads. They all connect to the compressor outside. My two bedroom heads are perfect and blow ice cold. My living room only blows ice cold when they top it off with refrigerant . A week later it goes from blowing warm air for a while then back to cool air but never ice cold like the bedrooms. They came out snd said they found a leak. But a week later here we are and the same thing is happening. What is going on !!!

    • @bolinsapark
      @bolinsapark Рік тому

      probably like an electrical issue. did they fix it ?

  • @Thomas-iq8zk
    @Thomas-iq8zk 2 роки тому +2

    Daikins are forever leaking

    • @jonjensen6036
      @jonjensen6036 Рік тому +1

      This is clearly installation error, daikin didn’t make those flare joints..