DSE Training : DSE 4520/4510 how to program from front panel without laptop | dse configuration

Поділитися
Вставка
  • Опубліковано 22 сер 2024
  • DSE Training : DSE 4520/4510 how to program from front panel without laptop | dse configuration
    BUY here : amzn.to/3PfSIae
    DSE7420 MKII Original - Made in UK |
    BUY here : amzn.to/3P0AgSI
    DSE4520 MKII Auto Mains (Utility) Failure Control Module
    BUY here : amzn.to/3R5p2iu
    New Original Deep Sea DSE3110 Generator Controller DSE 3110 Diesel Generator Genset Controller
    BUY HERE : amzn.to/3sJBEBM
    Generator Controller, DSE6120 Deep Sea Electronic Generator Controller
    BUY here : amzn.to/3sGY1b4
    Original Deep Sea Controller DSE7320 Generator Genset Auto Start Control Module New Electronics
    about video :
    here are the steps on how to manually program a DSE 4520 controller through the front panel:
    Make sure that the DSE 4520 is turned off.
    Press and hold the Menu button until the Programming menu appears.
    Use the Up and Down buttons to select the parameter that you want to program.
    Use the Enter button to change the value of the parameter.
    Repeat steps 3 and 4 for all of the parameters that you want to program.
    Press and hold the Menu button to exit the programming menu.
    Turn on the DSE 4520.
    The changes that you made will be saved to the DSE 4520's memory.
    Here are some of the parameters that you can program on a DSE 4520:
    Start and stop settings
    Battery monitoring settings
    Load control settings
    Fault reporting settings
    For more information on how to program a DSE 4520, please refer to the DSE 4520 Operator Manual.
    Here are some additional tips for programming a DSE 4520:
    Be careful not to change any parameters that you are not familiar with.
    If you make a mistake, you can always restore the DSE 4520 to its factory settings by pressing and holding the Reset button for 10 seconds.
    I hope this has been helpful. If you have any questions, please leave a comment below.
    ‪@DieselGeneratortraining‬
    #dse4510 #configuration #dsetraining
    Other videos of DSE 45xx series :
    dse 4510/4520 electrical wiring diagram explained
    • Dse 4510/4520 wiring d...
    dse 4510/4520 wiring diagram explained Hindi Urdu
    Dse 4510/4520 laptop configuration
    • Dse 4510/4520 pc suite...
  • Наука та технологія

КОМЕНТАРІ • 63

  • @DieselGeneratortraining
    @DieselGeneratortraining  Рік тому +2

    ua-cam.com/video/yBtMaPMOXbE/v-deo.html

  • @user-wq9my5uj9t
    @user-wq9my5uj9t 6 місяців тому +1

    Nice video sir, this controller they have cooldown for stopping the genset, thanks

  • @T-Rex_Slap
    @T-Rex_Slap Рік тому +2

    Thank you for the help!

  • @sabelozulu5456
    @sabelozulu5456 10 місяців тому +1

    HI please can you show me how to remove the due service light.

  • @kwadwoboakye3190
    @kwadwoboakye3190 9 місяців тому +1

    thank you so much for this lessons. I have a 20kva diesel generator but does not have a DSG controller, it uses a key switch.. How can I add a DSG controller to the generator

    • @DieselGeneratortraining
      @DieselGeneratortraining  9 місяців тому +1

      Glad it helped

    • @jadgeagea8
      @jadgeagea8 7 місяців тому

      THANKS FOR WHAT EXACTLY ? ALL THE videos is that he reads whats on the screen like any 10 yo can do

  • @modadessdplessonsandmore4820
    @modadessdplessonsandmore4820 2 місяці тому +1

    please how do I enable fuel level on this panel?

  • @laeeq5227
    @laeeq5227 8 місяців тому

    Fuel solonoide ko dg off krwany k liye Kon c setting use krni ho gi

  • @JasmineTom-kz8sv
    @JasmineTom-kz8sv 7 місяців тому

    Where can I connect the two sensor wires for remote start from my ats panel to dse4520 controller?

  • @imman1945
    @imman1945 Рік тому +2

    HI Can you explain DSE 9130 and HMI 211 connected with PCC 1302

    • @tanveerahmad-xv3ed
      @tanveerahmad-xv3ed Рік тому

      Me also want this ....
      When load high need second generator automatic on off & synchronized

    • @aklilA
      @aklilA 11 місяців тому

      Me too want a video about PCC1302 and HMI211

  • @rxgarage5724
    @rxgarage5724 6 місяців тому

    Which number connect to ats? In eicher already I see remote wire connecting so where i connect help me plz

  • @thapelofme6944
    @thapelofme6944 9 місяців тому

    Hello do you change parameters while generator is running?

  • @aklilA
    @aklilA 11 місяців тому +1

    Thank you from Ethiopia. I faced a problem that the generator shuts down in 10 seconds by displaying low oil pressure alarm on the screen. Oil is changed and its level is okay, oil viscosity is okay, oil pressure sendor is okay. The generator is new, run only 65 hours. The generator type is perkins 45KVA and the controller is DSE4520. Please help me!
    Thank you for your help in advance!!!

    • @asifsh1
      @asifsh1 10 місяців тому

      We had same issue with a 150kVA Perkin generator in Pakistan at around 1050 hrs. We changed the oil pressure sensor but it didn't fix the issue. We replaced this control panel with a new unit, and the issue resolved.

  • @nuredinsuleman5294
    @nuredinsuleman5294 7 місяців тому

    Thank you so much

  • @khalidafridi4800
    @khalidafridi4800 3 місяці тому +1

    Sign from 931 to 940 shows and generator not started plz guide

  • @mohammedimran5425
    @mohammedimran5425 6 місяців тому +1

    Deep see 4520 Not show u hz metr

  • @nizamujemal3136
    @nizamujemal3136 Рік тому +1

    What can i do if it isunable to start

  • @user-bb4bi5hx5l
    @user-bb4bi5hx5l 10 місяців тому

    how do you read a fault on the controller

  • @dogookodanku2904
    @dogookodanku2904 8 місяців тому

    What is the meaning of service alarm

  • @user-dh9zs7oj9i
    @user-dh9zs7oj9i 10 місяців тому

    Ok sir thanks super 🎉 🎉🎉

  • @user-ds4vv1cv1p
    @user-ds4vv1cv1p 9 місяців тому

    How to set a remote start on input 14

  • @user-ro8sg7fl8l
    @user-ro8sg7fl8l 6 місяців тому

    How to reset oil filter maintain alarm

  • @emmanuelosiaje3996
    @emmanuelosiaje3996 Рік тому

    My office generator with the DSE control panel is experiencing a fault. The stop button is blinking continuously and generator can't start. How can i clear or reset it

  • @iqbalmughal3349
    @iqbalmughal3349 3 місяці тому +1

    Salf cutoff prgram

  • @anandjoy902
    @anandjoy902 2 місяці тому +1

    Tnk u

  • @nicomilolo578
    @nicomilolo578 Рік тому

    Hello, my 45KVa generator shows warning alarm signal on the screen and can’t start

  • @adekunleadewale13
    @adekunleadewale13 11 місяців тому

    please how do i configure my 4510 for a 40kva generator. i am particular about the ampere settings.

  • @syedawais7640
    @syedawais7640 3 місяці тому

    How I can rest the engine hours in the madeul

  • @rickurtis
    @rickurtis Рік тому

    Thanks you bro

  • @nuredinsuleman5294
    @nuredinsuleman5294 7 місяців тому +2

    As wr wb
    Does this Control panel (DSE4520) has password??

  • @rajatsingh9082
    @rajatsingh9082 8 місяців тому

    10 kva 3 phase gen can change only 1 phase use without unbalance load

  • @NKELECTRICALDOST
    @NKELECTRICALDOST 9 місяців тому +1

    Nice

  • @user-kx6vr8tt7y
    @user-kx6vr8tt7y 11 місяців тому

    I want to know how to adjust the running hours of the generator

  • @akmaldin9030
    @akmaldin9030 11 місяців тому +1

    Mashallah

  • @akmaldin9030
    @akmaldin9030 11 місяців тому +1

    My Gernater start than 5 secend off

  • @user-sr6oe6sx3g
    @user-sr6oe6sx3g Рік тому

    Hi. Do I connect Gen start signal from Inverter to Digital Input 1 and 14? Is any programming required?

    • @minghongwu7198
      @minghongwu7198 Рік тому

      Hi, have you found the way to do it pls. could you share pls

  • @user-xp8bc9oi3z
    @user-xp8bc9oi3z 4 місяці тому +1

    Hy

  • @FVCK11
    @FVCK11 Рік тому

    How to check the continue on in automode

  • @WaqasAhmed-qi3uo
    @WaqasAhmed-qi3uo 3 місяці тому

    Hi

  • @mohammedimran5425
    @mohammedimran5425 7 місяців тому +1

    Sir Mary paas 4520 lga Howa Hy lakin amp show ni ho rha plz help me

    • @DieselGeneratortraining
      @DieselGeneratortraining  7 місяців тому

      Three phase generator hai ya single aur current transfer lagay huway hai k nahi 😐

    • @mohammedimran5425
      @mohammedimran5425 6 місяців тому +1

      @@DieselGeneratortraining 3 fhase hy transfer ni lgya howa

    • @DieselGeneratortraining
      @DieselGeneratortraining  6 місяців тому

      CT laganay hongay phir current show hoga

    • @mohammedimran5425
      @mohammedimran5425 6 місяців тому

      @@DieselGeneratortraining ct aue conacshon bhai kr diy han fir bhi ni àaya

    • @DieselGeneratortraining
      @DieselGeneratortraining  6 місяців тому

      OK wait karain ek video banata ho phir ajai ga

  • @engineertuwere6028
    @engineertuwere6028 Рік тому

    How to clear error code on dsc4510?

  • @somasekhar3766
    @somasekhar3766 7 місяців тому

    My generator is getting off in 5 sec when i on the generator, and again itself automatically starts the generator and getting off.. Like a cycle.. Please help me

    • @DieselGeneratortraining
      @DieselGeneratortraining  7 місяців тому

      Please always share in details what is the engine ,alternator controller n alarm on screen

    • @somasekhar3766
      @somasekhar3766 7 місяців тому

      @@DieselGeneratortraining it's a 4510 MKll controller and engine is Leroy's somrey

    • @nasirakbar8148
      @nasirakbar8148 3 місяці тому

      Check battry voltage may be battry voltage less than 12 v

  • @WaqasAhmed-qi3uo
    @WaqasAhmed-qi3uo 3 місяці тому

    G