Jazakaallah bhai... please provide us the details of standard valve package connections in AHU & FCU including btu meter, inlet which valves are used & outlet which valves are used for constant & vfd type flow...
Normally it is installed on the return line because of following reasons. 1. ASHRAE Recommendations. 2. The coil of the unit should be flooded in case the valve is closed. 3. With a control valve on the return side, the water is at a higher pressure through the coil, reducing off gas, thereby lowering dissolved oxygen content. Lower dissolved oxygen extends equipment life by minimizing the air entrapment. 4. If it is a hot system, some manufacturers have temperature limitations on the actuators. If there is a180°F limit on the actuator (common to some actuators), the return side is preferred as it will operate at a cooler temperature. 5. If it is a cold system, it is always better to have less thermal breaks on the colder side (e.g.42°F water) than on the warmer return side (e.g.,56°F water). The return side installation reduces sweating on the electronic actuator, which is more prone to failure when wet.
@@TanweerAhmed hvac drafting video for G+1 2 floor like how to draw duct, fcu ahu Or other components related to hvac like eccentric reducer concentric reducer elbow
Automatic Balancing Valve link: ua-cam.com/video/S370MfPwxg0/v-deo.html
Three way valve chiller which are youse
What do you want to say?
@@TanweerAhmed He wants to say that what is the purpose of using 3-way valve in chilled water line ?
Nice explained sir
U are a gem I am preparing watching your video for hvac engineering
Thanks
Ap ki video boht informative thi sir jzak allah
Thanks and Alhamdullah
Jazakallahu khaira. your videos are really helpful to understand deeply.
Welcome
Jazakallah....Thanks for the explanation...you have strong knowledge about the subject
Thanks a lot
Bhut khoob sir
Thanks
Great explanation!
Thanks
good explanation sir
Thanks and welcome
Please post a video of difference between DRV and PICV.Also can we balance FCU with only DRV ?
Watch my other videos of PICV and balancing valve for deep understanding
Very nice sir
مھربانی
Very informative. Jazakallah
Thanks
Good very helpful
الحمدللہ
Thank you so much for your help.
Welcome
Very very nice sir g
Thanks
Great Ada
Thanks dear 💓
Jazakaallah bhai... please provide us the details of standard valve package connections in AHU & FCU including btu meter, inlet which valves are used & outlet which valves are used for constant & vfd type flow...
Insha'Allah
Good explanation, expecting more and let me known which is the good book to learn
Thanks, these are taken from catalogue of equipment
Sir why we fix drv in return line please answer
Normally it is installed on the return line because of following reasons.
1. ASHRAE Recommendations.
2. The coil of the unit should be flooded in case the valve is closed.
3. With a control valve on the return side, the water is at a higher pressure through the coil, reducing off gas, thereby lowering dissolved oxygen content. Lower dissolved oxygen extends equipment life by minimizing the air entrapment.
4. If it is a hot system, some manufacturers have temperature limitations on the actuators. If there is a180°F limit on the actuator (common to some actuators), the return side is preferred as it will operate at a cooler temperature.
5. If it is a cold system, it is always better to have less thermal breaks on the colder side (e.g.42°F water) than on the warmer return side (e.g.,56°F water). The return side installation reduces sweating on the electronic actuator, which is more prone to failure when wet.
@@TanweerAhmed thanks sir.. quick response. Jazakallah
Welcome
Tanveer pa g, plz guide me about fcu fresh air supply control & location of it & also control fcu air throw control.
Ok noted
v good sir
Thanks
Helpful.
Thanks
DRV FCU K IN LINE PAR LAGTY HAN YA OUT PAR. ???
Out pipeline
Aw sir aik drafting video banae small villa ka hvac ka.
I don't understand. What you want to say
@@TanweerAhmed hvac drafting video for G+1 2 floor like how to draw duct, fcu ahu Or other components related to hvac like eccentric reducer concentric reducer elbow
@@qumartanweer6589 Sorry, I don't know drafting work. AutoCAD draftman know this work.
@@TanweerAhmed ok Sir thanku, aapki videos se bahut help hote hai Thank a lot
Welcome
PICB AND DRV both are same please reply
My both videos are available on these topic, watch & understand
Purpose installing Drv in Chilled water return main line
Watch this video, I hope that you will understand
How to balance chilled water with metter
Explained in video
Assalamualaikum sir
If u have CCU unit(PAC) unit vedio please send link
Watch in HVAC playlist i.e. package FAHU unit
Chilled line k ooper red color kyun liya jata he
I haven't seen like this
I need your help for some license query for global trading
I don't know about globel trading
Types of balancing
What do you want to say?
I want to know how many types of balancing valve?
I have explained in this video and also will make more videos
What is the function of double regulating valve. Can u explain in English
I will subtitles on this video
Messenger I'd or anything by which I can contact you it is big project pls discuss with me
WhatsApp 🇵🇰 +923332472721
Assalamu aleikum bhai jaan aapka mo no Chahiye
Join my Telegram group and its link is given in each video's description and also community tab
Your lecture is full of confusion....
Okay