Overview of the Siemens SIPART PS2

Поділитися
Вставка
  • Опубліковано 26 гру 2024

КОМЕНТАРІ • 76

  • @marcuscosta1627
    @marcuscosta1627 4 роки тому +1

    I would like to thank you for that film, it helped me a lot, that tip of potentiometer, it wasn't so much clear on the manual, and with your explaination it was so much easier. Thank you very much!!!

  • @lrcustomspty
    @lrcustomspty 2 роки тому +1

    Thanks for the video! It help me a lot!

  • @waubers7814
    @waubers7814 Рік тому +1

    Thanks a lot! Very clear and straight to the point! Show de bola!

  • @saifalniamah9002
    @saifalniamah9002 10 днів тому

    Thank you sir.
    When the calibration is done, appears on the display (EXDWN) and i can't change it's mode to automatic.
    Do you have any idea about this issue ?
    Regards,
    Saif

  • @tripatsinghbatra3517
    @tripatsinghbatra3517 2 роки тому +1

    Nicely explained sir

  • @meiamini857
    @meiamini857 4 роки тому +1

    This solved my problem, thanks a million

  • @goldenfarms2934
    @goldenfarms2934 6 років тому +3

    Extremely helpful video, thanks for sharing. 👍🏼🇺🇸

  • @humanbeing4097
    @humanbeing4097 Місяць тому

    Greattt Greattt & Greattt detailed video explained perfectly, pls keep it up.

  • @gracehernelpanzou2200
    @gracehernelpanzou2200 4 місяці тому

    thanks so much sir for this great video

  • @bigkikocisneros7726
    @bigkikocisneros7726 9 місяців тому +1

    Thank you

  • @aaronpadilla7558
    @aaronpadilla7558 4 роки тому

    Very Helpful Video. Thanks a lot sir

  • @jitubabusay2826
    @jitubabusay2826 6 місяців тому

    What to do. 100% open in 19 ma current?????

  • @900_z_rider
    @900_z_rider 2 роки тому

    What does it means during calibration as you mention we need to rotate the potentio meter wheel. What is the reason if that potentiometer wheel is not turning? I am facing this issue hence asking.
    Your valuable inputs are really appriciated.
    TIA

    • @Lesman
      @Lesman  2 роки тому

      Your wheel may not turn if your positioner is damaged or if you’re not using enough force to turn the wheel. Please contact Siemens technical support at 1-800-333-7421 for specific questions.

  • @gamalabuzaid2529
    @gamalabuzaid2529 4 роки тому

    If its part-turn and i want to adjust it fail to close instead of fail to open, how can i do it?

  • @rajaselvatvm
    @rajaselvatvm 2 роки тому

    When I install the new positioner to double acting actuator it goes straight away 100% and I can't close and initialize..also the + and - not operating...can anyone give suggestions please

  • @shahid8639
    @shahid8639 Рік тому

    So nice of you sir for the information. recently I have calibrated the same positioner on our Siemens gas turbine. Due to the position deviation. After I have done the calibration now it’s working normal. My question is why it has position deviation? And also elaborate the the frequency of calibration.

    • @Lesman
      @Lesman  Рік тому

      Typically, something changed mechanical for some reason. Could be a loose screw on his linkage, mechanical wear somewhere in the valve and or linkage. How often should he calibrate? Not unless he sees a deviation again because whatever is wearing, continues to wear. He could also use his diagnostics on the PS2 to tell him when he reached his error(deviation) limits and then he would know when to recalibrate.
      Or just do an annual recalibration.
      Typically, something changed mechanical for some reason. Could be a loose screw on his linkage, mechanical wear somewhere in the valve and or linkage. How often should he calibrate? Not unless he sees a deviation again because whatever is wearing, continues to wear. He could also use his diagnostics on the PS2 to tell him when he reached his error(deviation) limits and then he would know when to recalibrate.
      Or just do an annual recalibration.

  • @mohammadtahirhussain3788
    @mohammadtahirhussain3788 4 роки тому

    Very simple and nicely teach thanku

  • @kamelunion8297
    @kamelunion8297 4 роки тому

    Great explanation ! Thank you

  • @AnwarHossain-lb5eb
    @AnwarHossain-lb5eb 5 років тому

    very good explanation and cleared described.....thank you very very much.

  • @3174jason
    @3174jason 2 роки тому

    I e done everything, even reset the unit
    My unit keep actuating to the open position. How can I correct this.

    • @Lesman
      @Lesman  2 роки тому

      It's difficult to troubleshoot without knowing your configuration. Contact Siemens Technical Assistance Center at 800-333-7421 for help. They'll be able to work through the issue with you.

  • @bigkikocisneros7726
    @bigkikocisneros7726 Рік тому

    Thank you 🎉

  • @marcing8610
    @marcing8610 5 років тому

    Thanks for the film, it helped me a lot

  • @tahmidchowdhury
    @tahmidchowdhury 4 роки тому

    Our valve is roatary type and it is not responding at all in auto mode. Current input is ok. Also works in the auto mode. Can anyone some with a suggestion?? Can re-calibrarion fix the problem?

  • @pokegold100
    @pokegold100 8 місяців тому

    How to repire relay for this positioner....?

    • @Lesman
      @Lesman  7 місяців тому

      Relays are not repairable. You may need to purchase a new relay board. Call 800-333-7421 for help troubleshooting. Once the issue is confirmed, call your local Siemens rep if a replacement part is required.

  • @mohanrajganesan5026
    @mohanrajganesan5026 Рік тому

    what about the flow adjustment in positioner

    • @Lesman
      @Lesman  Рік тому

      The PS2 has speed control valves internal as a standard. On single acting there is one, and on double acting there are two.
      These valves can be used to restrict the air exhaust output, and therefore slowing down the speed at which the valve can close or open depending on how it is designed to act in a fail position event. The factory default is to have them completely open, for the fastest response. If for some reason you want to slow the stroke speed, adjust the screw to make this adjustment.
      Call Siemens at 1-800-333-7421 to speak with their technical support.

  • @ericrocha4693
    @ericrocha4693 4 роки тому

    Very helpful video. Only issue I am running into now is when its in auto and modulating, the positioner indicates on the LCD screen an oFL code and the number 127.9, I'm not sure to how to resolve this issue.

    • @rajaselvatvm
      @rajaselvatvm 2 роки тому

      I also facing same issue please share the knowledge if u solved this issue

  • @satyadeepakchinnideepak9718
    @satyadeepakchinnideepak9718 4 роки тому

    Great Video. I am facing a problem regarding with my rotary actuator. The valve is opening and closing manually, but the potentiometer value doesn't change. Tried to do initialisation, confused with the parameters. So kindly post the parameters for a rotary actuator. Thanks in advance.

  • @mr.nizamulhoq851
    @mr.nizamulhoq851 4 роки тому

    Hello Sir,
    Have a good day.
    I have recently facing problem in a newly buying Siemens PS2(2wire, 4-20ma, 2 wire, without HART) smart positioner connect with my existing Single acting, air to open linear actuator(pneumatic control valve) having 20mm stroke when I am going to newly calibation.
    During commissioning this new positioner with existing control valve/actuator in initial condition its display shows P 85 and NOINI mode, at that time when if i press (+) and (-) button then the actuator
    totally doesn’t not move.only small clicking sound hearing inside the positioner and little air Release from actuating pressure line(Y1) of positioner , however pneumatic(4kg air pressure) and electrical(4ma , 24VDc) connection is there. Interesting is if i place old existing positioner there then it easily move the actuator after pressing (+) and (- ) key in NOINI mode. Is there any problem of lever setting or restrictor setting there.i don’t change any restrictor setting in this newly buying positioner during commissioning there.i am confused if there any setting required in restrictor at positioner during newly commissioning?
    Anybody here who can advice me kindly please to fix this problem.

  • @lorenzoteatini3974
    @lorenzoteatini3974 7 років тому

    it here any version intrisically safe for ATEX Zone 0? (Eexia=?)

  • @_your.aditya_
    @_your.aditya_ Рік тому

    thanks Sir

  • @sultanhussain6051
    @sultanhussain6051 5 місяців тому

    Super Demonstration Sir love you from karachi Pakistan.

  • @2018GEORGE
    @2018GEORGE 6 років тому +1

    very detailed video!

  • @madhavrabari4756
    @madhavrabari4756 2 роки тому

    Thank you very much sir.. very useful video for me..

    • @Lesman
      @Lesman  2 роки тому

      You are most welcome

  • @alivarolbasaran5953
    @alivarolbasaran5953 Рік тому

    Thanks a lot

  • @vikramsinghrathore6693
    @vikramsinghrathore6693 5 років тому

    Great presentation, keep it up.

  • @kakarkuyuk317
    @kakarkuyuk317 5 років тому

    Very good and helpful video thanks

  • @신룰라룰라
    @신룰라룰라 6 років тому

    아주 자세히 설명을 잘하시네요...

  • @jdnoble6945
    @jdnoble6945 3 роки тому

    Absolutely brilliant video, I have identified my problem , my actuator was starting at 100% and therefore could not do the auto initialise. Can anyone say how to reverse the 100 to 0% using parameters 7 and 38. rise and FALL. when you have done' rise' or'fall' to reverse the action do you just go back to idle or do you initialise again?

    • @rajaselvatvm
      @rajaselvatvm 2 роки тому

      Hi u have solved this issue ..bcoz I also facing same issue

    • @azereliyev3563
      @azereliyev3563 Рік тому

      ​@@rajaselvatvmsalam siz nasil yaptidiniz

  • @aadeshjain6430
    @aadeshjain6430 6 років тому

    hello, can u plz tell me the inner parts like i/p converter etc. of a ps2 smart positioner.. plz reply me

    • @smartlife4369
      @smartlife4369 4 роки тому

      are u got answer than share with me

    • @aadeshjain6430
      @aadeshjain6430 4 роки тому

      @@smartlife4369 no..i didnt get yet..

  • @supercriticalburner
    @supercriticalburner 5 років тому

    Can I skip the leak test?

    • @jimhaldeman9443
      @jimhaldeman9443 5 років тому

      Yes, the leak test only occurs when it is initiated by the user.

  • @metlaani
    @metlaani 4 роки тому

    Hi, Thank you for this video. It will be helpful If you guide us on the following point.
    When we remove Fieldbus signal cable - all control valves goes to closed position (fail close). => which is OK.
    When we reconnect Fieldbus signal cable - some control valve stay in same closed position (=> which is OK) where as few control valves slowly moving to open position which is not correct (=> in this case positioner set point automatically change to 100% while connecting signal cable; set point is not coming from DCS).
    We check positioner setting in both cases and unable to identify the reason for different action.

  • @muhammedshabbirkaithwi4447
    @muhammedshabbirkaithwi4447 6 років тому

    Thanks a lot engineer

  • @Technology3674
    @Technology3674 6 років тому

    Very good sir

  • @shahzebali8281
    @shahzebali8281 6 років тому

    How can we factory reset it ?? Kindly rep plz

    • @jimhaldeman9443
      @jimhaldeman9443 5 років тому

      50.PRST
      Preset
      Reset all parameters which can be reset by 'Init', 'PArA' and 'diAg'.
      ALL
      Reset initialization parameters '1.YFCT' to '5.INITM'.
      Init
      Reset parameters '6.SCUR' to '49.LIM'.
      PArA
      Parameter assignment
      9.3 Tabular overview of the parameters
      SIPART PS2 with and without HART
      Operating Instructions, 02/2016, A5E00074631-AB 151
      Parameter
      Function
      Parameter values
      Unit
      Reset parameters A to P of the extended diagnostics function as well as parameter '52.XDIAG'.
      diAg

  • @shahrukhsatkut4119
    @shahrukhsatkut4119 7 років тому

    difference between 2 port & 3 port seimens valve positioner

  • @inzamamulhaq2650
    @inzamamulhaq2650 5 років тому

    Good explanation....!

  • @satyaprakash9263
    @satyaprakash9263 6 років тому

    thanks

  • @basavarajbasava8450
    @basavarajbasava8450 3 роки тому

    Nice

  • @walterengeeletrica
    @walterengeeletrica 3 роки тому

    Muito boa a explicação! Parabéns !!!

  • @petersantos5322
    @petersantos5322 5 років тому

    muito esclarecedor obrigado.

  • @mr.nizamulhoq851
    @mr.nizamulhoq851 4 роки тому

    Dear sir,
    have a good day.
    Thanks for uploading such type of excellent video.
    i have recently facing problem in a a newly buying Siemens PS2 positioner connect with existing Single acting linear actuator , 20mm stroke.during comissioning this new control valve/actuator in initial condition its display shows P 85 and NOINI mode, at that time when i press + and - button the actuator totally not move.only small sound hearing inside the positioner and some air release backside of positioner , however pneumatic and electrical connection is ok.if i place old existing positioner there then it easily move
    the actuator after pressing + and - key in NOINI mode.
    Moreover when i go in Log 5 ,NOINITM mode 30% open the valve in both YEND1 and YEND2 once i press both + and - key.once i release button then actuator go to zero condition.it doesn't hold at all.
    If its abnormal what can i do.would you please advice me.
    if i press only either + or - button then actuator not move in YEND1 and YEND2
    mode.but when i press both + and - button simultaneously then it open actuator only 30% but not hold at all then when press hand button its display range message.
    will you please advice me its normal or abnormal?
    Really i am facing a horrible condition for this positioner at my site and i am apologetically wish to get you kind advice please.
    Thanking You,
    Engr.Nizamul hoq.
    proprietor.
    United Mechatronics Engineers.
    Bangladesh.
    Email: united.mechatronics@gmail.com
    Mobile :
    0088-01814792505 and 0088-01935675378(whatsapp)
    Skype: nizamul.hoq1

  • @satyaprakash9263
    @satyaprakash9263 6 років тому

    nice video sir

  • @didinachtergaele
    @didinachtergaele 5 років тому

    Great video, but I have a problem today ....... all ok, just, it works invert. 20mA = closed - 4mA is open (ballvalve valve - 90°) ? Who can help me. Many Thanks :-)

    • @didinachtergaele
      @didinachtergaele 5 років тому

      I'll try again tomorrow, exactly as you described.

    • @jimhaldeman9443
      @jimhaldeman9443 5 років тому

      3.21 Reversing the Action
      There are two ways to invert the action and display, one requires re-initialization.
      No re-initialization procedure
      This procedure inverts the physical action and display of the positioner.
      ● Parameter "SDIR" reverses the physical action
      - From AUT or MAN mode, press button for 5 seconds. Observe parameter name in
      the lower right corner.
      - Continue to press button until "SDIR" Parameter is reached.
      - If "SDIR" Parameter displays "riSE" change to "FALL" or vice versa.
      Use and/or buttons to change option.

  • @Diwa94
    @Diwa94 Рік тому

    ABB ???

  • @agusnugraha2610
    @agusnugraha2610 Рік тому

    Sir, one quesition

  • @bustroff
    @bustroff 4 роки тому

    Difficult. Need easy maintaining

  • @mohcinekarafy1636
    @mohcinekarafy1636 2 роки тому

    mielleur explication

  • @amindaneshpajooh4602
    @amindaneshpajooh4602 2 роки тому

    Excellent explanations, thank you.

    • @Lesman
      @Lesman  2 роки тому

      Glad it was helpful!

    • @sukantomahakur2050
      @sukantomahakur2050 Рік тому

      @@Lesman 1st I want to give you thank you for nice explanation.
      sir I am facing problem that p run 1 error.. kindly advise me what I have to do