LIVE Testing on a 3 Phase Dis-Board - External Earth Fault Loop Impedance Ze, PEFC, PSCC AM2 & AM2S

Поділитися
Вставка
  • Опубліковано 30 січ 2025

КОМЕНТАРІ • 114

  • @TheJordaneh
    @TheJordaneh 2 роки тому +42

    Not sure if you guys will see this but just wanted to say a massive thank you, passed my AM2 first time and your videos absolutely carried me through, thank you!!!

    • @GSHElectrical
      @GSHElectrical  2 роки тому

      Fantastic news 👍🏻 congratulations from team GSH

    • @skabbymuff111
      @skabbymuff111 2 роки тому +1

      Yes, thanks guys, about to undertake this myself and your videos are invaluable 👊

    • @Dailymailnewz
      @Dailymailnewz 2 роки тому

      @@GSHElectrical He should have done Zs at DB as well...

    • @pvegod1484
      @pvegod1484 9 місяців тому

      @@Dailymailnewz isnt that only relevant if this is a sub main ?

  • @callumsimpson7483
    @callumsimpson7483 2 роки тому +8

    My level 3 teacher is currently drilling me with three phase testing and fault finding as Iv handed my design project in well early. I’m so glad because once you start doing the three phase it’s so much different. I can honestly say I feel confident to do my 2391 and am2 and watching these videos now make a lot more sense than when I watched it without doing three phase.

    • @GSHElectrical
      @GSHElectrical  2 роки тому

      All the best and thanks for commenting 👍🏻

  • @marcusleung7515
    @marcusleung7515 8 місяців тому +3

    the best demostration i found on YT so far , Cheers

  • @GSHElectrical
    @GSHElectrical  3 роки тому +10

    == 🕐 Time Stamps - Cut to the action 🕕 ==
    00:00 - Ze and PFC tests
    00:54 - Isolating the 3 phase distribution board
    01:58 - Disconnecting the earthing conductor to remove parallel earth paths created by the bonding
    02:55 - External earth fault loop impedance test Ze test on a 3 phase dis-board
    05:11 - Reconnect the earthing conductor
    05:19 - Prospective earth fault current PEFC test (PFC)
    06:34 - Prospective short circuit current PSCC test (PFC)
    08:00 - Rule of thumb double your highest reading from PSCC test for a 3 phase supply
    09:48 - Testing PSCC between the 3 line conductors of a 3 phase supply

  • @jonathanrose456
    @jonathanrose456 3 роки тому +6

    Great video!
    Lots of real world training missing online.
    H&S… I wear VDE gloves when working/testing live. Just mitigates the risk. Easy enough to fall forward on to the live terminals, especially so on older 3ph boards & working off a ladder, etc..

  • @Bari_Khan_CEng_CMarEng
    @Bari_Khan_CEng_CMarEng Рік тому +1

    Another great video and demonstration, much appreciated

  • @JohnCanty93
    @JohnCanty93 3 роки тому +2

    Thanks guys make it so much easier to understand seeing it 👍🏼

  • @EricTheHiking
    @EricTheHiking 3 роки тому +3

    Thank you guys for all test. Some of them I wasn't sure 👍👍👍

  • @vite_nado_vijti_8171
    @vite_nado_vijti_8171 2 місяці тому

    Молодцы ребята,очень полезная информация 👍👍👍

  • @peterjesus816
    @peterjesus816 2 роки тому +3

    It was more than helpful, God bless u

  • @Mok-l5i
    @Mok-l5i 3 роки тому +3

    Thanks ,you make it easy to understand

    • @GSHElectrical
      @GSHElectrical  3 роки тому +1

      Thanks for commenting and watching 👍🏻

  • @Big-T-
    @Big-T- 3 роки тому +5

    Thanks very much, been looking for a good ze, pfc vid in a 3p DB. Getting ready for my fica at the end of this year👍🏾.

  • @jonerasmus9399
    @jonerasmus9399 2 роки тому +1

    Plz do many more videos. Great job chaps

  • @ollieb7394
    @ollieb7394 3 роки тому +4

    Great video guys! Not sure how strict and to the book the assessors will be in the am2 but GN3 does recommend dividing the line to line value by 0.87 if measuring Ipf between phases.
    Edit:
    After some research online I believe this figure is a guide to working out a simultaneous fault between all phase conductors with a fault of negligible impedance.

  • @dominic_8652
    @dominic_8652 2 роки тому +1

    Great Video Guys, very well explained

  • @shiamjad
    @shiamjad 2 роки тому +1

    Thank you for the explanation

  • @dimitrisblane6368
    @dimitrisblane6368 Рік тому

    Thank you so much for these videos. Really helpful information!
    One question. Why we take the PFC measurement with the main switch off and on the source side? When using the system all breakers etc are on. Why take the rest of the system out of the equation? the PFC surely would be different when the whole system is connected and turned on?
    Thank you

  • @krazylad84
    @krazylad84 2 роки тому +1

    massive thanks !

  • @kilowatt7960
    @kilowatt7960 8 місяців тому

    Excellent Video! Very well explained. I have just one question please to clear my mind. In theory, line to line fault is 3phase fault multiply by 0.866, therefore can I just use the fault current measured in L-L (4.11 kA) divided by 0.866 to get the 3phase fault instead of doubling the max fault measured in L-N?

  • @rowles13
    @rowles13 2 роки тому +1

    Brilliant guys

  • @willd4102
    @willd4102 2 роки тому +3

    I didn’t double the figure and I failed on the PFC test so I had to resit the full inspection and testing segment

  • @dooz100
    @dooz100 2 роки тому +1

    Great video, possible to do video on 3 phase rcd 300mA

  • @redroutemaster
    @redroutemaster 11 місяців тому

    Good video, informative.
    After 29 years of data cabling/engineering a flooded market of poor quality engineers the last few years reducing rates I started an electrical training course a month ago and enjoying it (should of started years back).
    Would the incomer earth be better with a ring crimped connector?

  • @krishtheobald4227
    @krishtheobald4227 2 роки тому +4

    I do believe the highest L-L reading has to be divided by 0.87 to get a simultaneous 3 phase fault PSCC.
    Someone else also mentioned this. Was there a reason you didn’t mention it in this video?

  • @detroutspinners9933
    @detroutspinners9933 Рік тому

    I’m assuming as it’s a live test you’d need the tails to have voltage to actually get a reading on the Ze and PFC tests? For example on the AM2 rig if they’ve isolated it remotely, I’d need to lock off the main switch on the board, then energise the isolator?

  • @michaelcostello6991
    @michaelcostello6991 2 роки тому +2

    Does that earth wire go back to supply transformer or is it just linked to the neutral at the cut out. Is 3 phase the same as single phase domestic in this regard. Thanks

    • @TheMattSturgeon
      @TheMattSturgeon 2 роки тому +1

      On a TN-S the earth goes all the way to the transformer separately from the neutral,. They're then connected together at the transformer.
      On a TN-C-S (shown in the video) the earth and neutral are joined at the cutout, and continue as a "PEN" conductor to the transformer (protective earth/neutral).
      On a TT the earth doesn't go to the transformer at all. Instead it connects to the consumer's earth electrode.

  • @EdwardBretherton
    @EdwardBretherton 11 місяців тому +1

    great video , big thumbs up and i want that red car , where is this filmed

    • @GSHElectrical
      @GSHElectrical  11 місяців тому

      Thanks for the support 👍🏻

  • @kingofthetrowel1725
    @kingofthetrowel1725 2 роки тому +1

    Sorry if this is silly question as I’m still a beginner adult learner etc but why do we have to use a,,3lead high or 3lead low? what’s difference and why do it etc 👍👍

  • @Dibbo1979
    @Dibbo1979 3 роки тому

    Great video, once again. Could you tell me how too test a 3phase rcbo please?

  • @earthrelated
    @earthrelated Рік тому

    Thank you!

  • @jackninnu9719
    @jackninnu9719 Рік тому +2

    2 kings ❤

  • @johnwaby4321
    @johnwaby4321 2 роки тому +1

    Brilliant

  • @OllyDunne24
    @OllyDunne24 3 роки тому +1

    Hi thanks for this I didn’t realise you have to double the PFC, is this just on a three faze board?

    • @GSHElectrical
      @GSHElectrical  3 роки тому +1

      Yes 👍🏻

    • @OllyDunne24
      @OllyDunne24 3 роки тому

      @@GSHElectrical thank you! is the PFC is the only one you write down on the schedule of tests?

    • @callumsimpson7483
      @callumsimpson7483 2 роки тому

      @@OllyDunne24 you write down the highest reading you get out the two I believe

  • @bernardcharlesworth9860
    @bernardcharlesworth9860 3 роки тому +1

    Thanks

  • @naqshAli786
    @naqshAli786 3 місяці тому

    Hi, would I have to carry out the PSCC between phases on a 3ph db. Or just each phase to neutral and double it?

  • @adambrammeld9286
    @adambrammeld9286 2 роки тому

    Don’t you have to actually times by square root of three and not double it For three phase PFC? It’s not double to work out single to three phase?

  • @giubaca
    @giubaca 10 місяців тому +2

    Theoretically the value is x1.73. However is much easier to double it

  • @louisdibra2136
    @louisdibra2136 Рік тому

    Should the right hand side dial be set on zmax when doing pscc 2lead high?

    • @saggers87
      @saggers87 16 днів тому +1

      No, the Zmax function is only used to record the highest Zs reading on the screen when you’re carrying out multiple Zs tests. For example, a ring main consisting of 8 sockets.
      I hope this helps 👍🏻

  • @thetruth6693
    @thetruth6693 3 роки тому +1

    Would you double it on a domestic install as well?

    • @GSHElectrical
      @GSHElectrical  3 роки тому +4

      Only on 3 phase installation 👍🏻

    • @dezire8470
      @dezire8470 3 роки тому +2

      Only on 3 phase Because of the potential between 2 different phases

  • @munyentwarithomas1884
    @munyentwarithomas1884 9 місяців тому

    Show how to measure insulation and RCD.

  • @Dawber1994
    @Dawber1994 Рік тому

    do you have to test between L1-L2 and so on or can you just do the L’s -N and double it?

    • @GSHElectrical
      @GSHElectrical  Рік тому +3

      If your tester can test between line conductors you take that as the heights reading if not it’s line neutral and double it 👍🏻

  • @17italyman
    @17italyman 2 роки тому

    for the am2s would we need to test between line conductors for PSCC or is testing between line and earth and line and neutral and doubling it enough ? Also would the reading from line and earth ever be higher than line to neutral ?

    • @adambrammeld9286
      @adambrammeld9286 2 роки тому +1

      Should be times by square root of three I thought becuase of the different between Line and Phases?

  • @Death88758
    @Death88758 Рік тому

    Just failed my 2391 because i got lost at the PEFC testing. Isnt there a 3 lead test with this megger or thats just for single phase

    • @pvegod1484
      @pvegod1484 9 місяців тому +1

      pfc requires a 2 lead test

  • @Dawber1994
    @Dawber1994 Рік тому

    Hi, why do you bother testing the PEFC on 3 phase if it doesn’t get recorded?

  • @SantoshYadav-k8g
    @SantoshYadav-k8g 10 місяців тому

    Ma'am bahut accha padte hai m

  • @harrygroves172
    @harrygroves172 3 роки тому

    What about if there is an rcd when taking the pscc, is there a way to test this on a 3 low setting?

  • @JoeMorsie
    @JoeMorsie 2 роки тому

    In guidance note 3 the PEFC shows a 3 lead test. does it matter if you do a 2 or 3 lead test?
    i have my AM2 in 2 weeks. Thanks

    • @BenHardie-dm1ix
      @BenHardie-dm1ix Рік тому

      I’ve always done a 3 lead test, seeing this has thrown me and I have my AM2S in a week and a half. How did yours go?

  • @clemfandango8777
    @clemfandango8777 2 роки тому

    Why double why not tripple...surely if the armoured was destroyed and 3 phase was shorted with the netural it would be higher than doubled?

    • @tezbtezb
      @tezbtezb 2 роки тому +1

      If I'm right you can only sort between 2 lines so line voltage is 400V giving highest fault current possible. E.g 400V ÷ 0.10ohm =4000A

    • @travoltasbiplane1551
      @travoltasbiplane1551 2 роки тому +1

      I can hear you Clem. Technically if you measure line to line you should then divide by 0.87 to account for the bolted fault shorting all lines at the same time that you describe! Doubling the line neutral pscc accounts for this already. Hope that helps. 👍

    • @keirstitt8277
      @keirstitt8277 2 роки тому

      Even if you had a three way fault - which is a two fault situation so we don't usually consider these. But the three phases are like the corners of an equaliateral triangle - so each is 400V from each other. When you short all three you'd get approximately the same fault current on each line conductor as the additional current would be balanced across three instead of two conductors.

    • @travoltasbiplane1551
      @travoltasbiplane1551 2 роки тому

      @@keirstitt8277 not according to the iet you wouldn't... It's in GN3 👍

    • @keirstitt8277
      @keirstitt8277 2 роки тому

      ​@@travoltasbiplane1551 you must have a different GN3 because it doesn't say any such thing in there.
      Appendix 14 of BS7671 maybe.

  • @MuratAydogdu98
    @MuratAydogdu98 2 роки тому

    Would you fail if you measure PSCC on the load side of the main switch?

    • @pvegod1484
      @pvegod1484 9 місяців тому

      if its locked off you cant

  • @salamsaloom2477
    @salamsaloom2477 Рік тому +1

    👍👍👍👍👍👍

  • @jamieseymour8437
    @jamieseymour8437 Рік тому

    On the am2 you don’t test for the zs you calculate it, this can fail you

    • @GSHElectrical
      @GSHElectrical  Рік тому +1

      This test is external impedance Ze 👍🏻.

  • @reomangham2022
    @reomangham2022 7 місяців тому

    l not have 2 phase l good vid Brilliant

  • @InTheGrooove
    @InTheGrooove 2 роки тому

    What is AM2 ?

    • @GSHElectrical
      @GSHElectrical  2 роки тому

      An end point assessment for apprentice electricians 👍🏻

  • @callammatthews2235
    @callammatthews2235 6 місяців тому

    Where’s your lock off kit 👿

  • @johndeer4545
    @johndeer4545 Рік тому

    great video guys, and surprised me how fluentJean Reno in english

  • @sidneyhall3639
    @sidneyhall3639 Рік тому

    No lock on your board. Safe isolation .

  • @velusamypothiraj2300
    @velusamypothiraj2300 7 місяців тому

    Bla bla not useful

  • @ampscoffeemachines3610
    @ampscoffeemachines3610 11 місяців тому

    Thanks