Honeywell UDC3500 Configuration Temperature Controller

Поділитися
Вставка
  • Опубліковано 23 лис 2024
  • #HoneywellUDC3500
    Hi Guys!
    In this video I will show you how to set up the Honeywell UDC3500 Controller such as a Temperature Controller.
    Power Supply is 90-220 VAC.
    I use a Temperature Calibration for the Thermocouple Type k.
    I configurate one analog output 4-20 mA and I set two Alarms.
    Alarm No1: 740°C High and
    Alarm No2: 680°C Low
    Thanks for watching!
    Enjoy!
  • Наука та технологія

КОМЕНТАРІ • 18

  • @tonydigiulian1840
    @tonydigiulian1840 2 роки тому

    Hi, The Cold Junction Sensor that you are using is for the UDC5000, it should not be used for the UDC3500. It will give you erroneous readings for a UDC3500 unless the ambient temperature is close to 25'C/77'F. They are both ~500 ohms around 25'C/77'F but they have different tempcos so the farther the ambient temperature is from 25'/C/77'F, the worse will be the compensation.

  • @Firespidey05
    @Firespidey05 4 місяці тому

    I have one with a failed display. Have you tried recovering the parameters via modbus?

  • @jamesdoughty5530
    @jamesdoughty5530 2 роки тому +1

    How about using a little narration?

  • @udm-18reg
    @udm-18reg 3 роки тому

    Привет. Нужна помощь. Стоит прибор honeywell DC3002-0-30B-1-00-0111 сбились все настройки. Стоит на вакуумнаой печке elterma. Не контролирует нагрев.

  • @thekrazyitalian8108
    @thekrazyitalian8108 3 роки тому

    Do you know how to install and set up a Honeywell dr4500?

    • @Panagiotis_Temertzidis
      @Panagiotis_Temertzidis  3 роки тому

      Sorry i do not know how to set up a Honeywell dr4500. Also you can use the manual here.www.honeywellprocess.com/library/support/Public/Documents/44-45-25-24c.pdf

  • @harshchawda193
    @harshchawda193 2 роки тому

    Hi I'm having an error message while changing the programs and is shows “key error” can you please help me to resolve

    • @Panagiotis_Temertzidis
      @Panagiotis_Temertzidis  2 роки тому

      “key error”
      When a key is pressed and the prompt “Key Error” appears in the lower display, it will be
      for one of the following reasons:
      • Parameter not available or locked out
      • Not in setup mode, press SET UP key first
      • Individual key locked out.

    • @malikshafique6365
      @malikshafique6365 Рік тому

      @@Panagiotis_Temertzidis h

  • @mdshohelrana2544
    @mdshohelrana2544 4 роки тому

    hello dear i have need relay output set points change.pls send a video. UDC2500 controller.

    • @Panagiotis_Temertzidis
      @Panagiotis_Temertzidis  4 роки тому

      I do not have a controller to do this. You can follow the manual, see the type of your controller and make your application.
      Thank you very much!
      www.honeywellprocess.com/library/support/Public/Documents/51-52-25-127.pdf

  • @baguscaesarmuharam5900
    @baguscaesarmuharam5900 3 роки тому

    How to measure output analog voltages?

    • @Panagiotis_Temertzidis
      @Panagiotis_Temertzidis  2 роки тому

      I think you have to choose "Input Actuation" Milliamps or Millivolts or Volts. I m not sure. This pdf can help you.
      prod-edam.honeywell.com/content/dam/honeywell-edam/pmt/hps/products/pmc/process-instruments/controllers-and-programmers/1-4-din-controllers/udc3500-din-controller/pmt-hps-51-52-03-40.pdf?download=false
      Thanks

  • @nilrob1980
    @nilrob1980 4 роки тому

    Y el audio

  • @sunyoungg5634
    @sunyoungg5634 10 місяців тому

    Alarm 1 controls Relay #5