Honeywell UDC3500 Configuration Temperature Controller
Вставка
- Опубліковано 23 лис 2024
- #HoneywellUDC3500
Hi Guys!
In this video I will show you how to set up the Honeywell UDC3500 Controller such as a Temperature Controller.
Power Supply is 90-220 VAC.
I use a Temperature Calibration for the Thermocouple Type k.
I configurate one analog output 4-20 mA and I set two Alarms.
Alarm No1: 740°C High and
Alarm No2: 680°C Low
Thanks for watching!
Enjoy! - Наука та технологія
Hi, The Cold Junction Sensor that you are using is for the UDC5000, it should not be used for the UDC3500. It will give you erroneous readings for a UDC3500 unless the ambient temperature is close to 25'C/77'F. They are both ~500 ohms around 25'C/77'F but they have different tempcos so the farther the ambient temperature is from 25'/C/77'F, the worse will be the compensation.
I have one with a failed display. Have you tried recovering the parameters via modbus?
@@Firespidey05 Not yet
How about using a little narration?
I'm not that good with words😄😄😄
Привет. Нужна помощь. Стоит прибор honeywell DC3002-0-30B-1-00-0111 сбились все настройки. Стоит на вакуумнаой печке elterma. Не контролирует нагрев.
Do you know how to install and set up a Honeywell dr4500?
Sorry i do not know how to set up a Honeywell dr4500. Also you can use the manual here.www.honeywellprocess.com/library/support/Public/Documents/44-45-25-24c.pdf
Hi I'm having an error message while changing the programs and is shows “key error” can you please help me to resolve
“key error”
When a key is pressed and the prompt “Key Error” appears in the lower display, it will be
for one of the following reasons:
• Parameter not available or locked out
• Not in setup mode, press SET UP key first
• Individual key locked out.
@@Panagiotis_Temertzidis h
hello dear i have need relay output set points change.pls send a video. UDC2500 controller.
I do not have a controller to do this. You can follow the manual, see the type of your controller and make your application.
Thank you very much!
www.honeywellprocess.com/library/support/Public/Documents/51-52-25-127.pdf
How to measure output analog voltages?
I think you have to choose "Input Actuation" Milliamps or Millivolts or Volts. I m not sure. This pdf can help you.
prod-edam.honeywell.com/content/dam/honeywell-edam/pmt/hps/products/pmc/process-instruments/controllers-and-programmers/1-4-din-controllers/udc3500-din-controller/pmt-hps-51-52-03-40.pdf?download=false
Thanks
Y el audio
i have a problem with the audio
Alarm 1 controls Relay #5