Replacing Lochinvar Gas Valve

Поділитися
Вставка
  • Опубліковано 7 вер 2021
  • I am replacing a gas valve on a Lochinvar boiler. I was here a few days earlier, and found that the gas valve faulty. Main control board sent 24vac power to the gas valve. The valve would not open to allow gas into burner. Here is a link to the previous service call. Troubleshoot Lochinvar Gas Valve : Flame Failure/ Ignition failure • Troubleshoot Lochinvar...
    After replacing I test the new valve.

КОМЕНТАРІ • 22

  • @watermanone7567
    @watermanone7567 2 роки тому +2

    Good work, what a terrible design by the mfg. to half to go thru all that work to change a simple gas valve. Thanks for the video.

  • @Ted_E_Bear
    @Ted_E_Bear 2 роки тому +1

    Hacker, you always amaze me with your skills !

  • @tonydelgrego2906
    @tonydelgrego2906 2 роки тому +3

    Need to try the new nylon .
    It doesn’t stain and if you get it on your clothes it washes out.

  • @hkhsm359
    @hkhsm359 2 роки тому

    Nice video
    Thanks for sharing

  • @thesilentonevictor
    @thesilentonevictor 2 роки тому

    Great work

  • @PBS-nm1uu
    @PBS-nm1uu 2 роки тому

    please do more on these boilers, thanks

  • @plumbworker
    @plumbworker 2 роки тому +2

    That boiler needs a combustion analysis after a gas valve swap for sure. Those Dungs negative gas valves aren’t “factory” set. Fitting UA-cam name 🤪

    • @thehvachacker
      @thehvachacker  2 роки тому +1

      I did a combustion test afterwards. I believe I mention it needed a combustion test. Yet to keep video shorter I excluded it. A combustion test is definitely needed. I do a combustion test every year when I do maintenance.

    • @plumbworker
      @plumbworker 2 роки тому +1

      @@thehvachacker ok beg my pard..

    • @thehvachacker
      @thehvachacker  2 роки тому +1

      If I was president I would pardon ya. I’m just a hvac guy. No power to pardon, no hard feelings. I would hope that noone would work on a high efficient boiler, or power flame without a combustion analyzer

    • @SombraLocs
      @SombraLocs 2 роки тому

      Do you set the gas pressure on the actual gas valve?

    • @plumbworker
      @plumbworker 2 роки тому +1

      @@SombraLocs No. This is a negative pressure gas valve. Valve opens under negative pressure the blower sucks the fuel into the air/gas Venturi that mixes to the burner. The combustion is set by adjusting air gas ratios / carbon dioxide/ 02 / CO excessive air etc. with a combustion analyzer.

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 2 роки тому +1

    Invest in a couple different strap wrenches, personally I would've used pipe wrenches with a cloth towel.
    🥃🥃🍺🍺🍺🍇🏌🏻‍♀️
    Stay safe.
    Retired (werk'n) keyboard super tech. Wear your safety glasses.

  • @mingo1142
    @mingo1142 Рік тому

    Clean work, what size are those red knipex pliers? 10 or 12”

    • @adamyaw
      @adamyaw Рік тому

      Looks like a 10” and 12” both he had in his hand

  • @stephwaylonwells3218
    @stephwaylonwells3218 2 роки тому

    👍

  • @Eddy63
    @Eddy63 2 роки тому

    Good replacement Hackster ... 1st ... Lol ...

  • @scottfarides5516
    @scottfarides5516 2 роки тому

    Is That a commercial knight boiler? I've installed many residential knight boilers the gas valves are pretty simple to replace. Why would they make it so complicated? I only use rector seal #5; if you use soap, it won't stain anything.🤣

  • @AmericanFarmerHVAC2024
    @AmericanFarmerHVAC2024 2 роки тому +1

    Talk a about a complicated piece of garbage. I hate these goddamn things with all my might...

  • @billsimpson604
    @billsimpson604 2 роки тому +2

    Looking at all that natural gas heating equipment helps appreciate why Obama's Secretary of Energy, Ernest Moniz (Doctorate in theoretical physics from Stanford) recently said that achieving net zero carbon emissions would cost over a hundred trillion dollars. Imagine replacing all that gas burning equipment with heat pumps with electric resistance heaters for when it gets really cold.

    • @KenKen-ui4ny
      @KenKen-ui4ny 2 роки тому

      We are already seeing inflation at the service station pumps and grocery stores, from the trillions being spend and printed by the our current administration on that sort of fantasy junk, they think we are made of that type of money, but reality is, we are not.

  • @realestateservicessaleshea99
    @realestateservicessaleshea99 2 роки тому

    🥃