Why Neutrals and Grounds are Separated in a Sub Panel

Поділитися
Вставка
  • Опубліковано 21 гру 2024

КОМЕНТАРІ • 4,6 тис.

  • @DiamondBackRS
    @DiamondBackRS 3 роки тому +22

    I am a Factory certified York, Trane, Carrier, (list goes on) Chiller Technician, and Factory Freq Drive Tech. HVAC, Controls Tech. 25+ years. I just wanted to say to you, that you are very knowledgeable, and make some excellent training videos. I point my apprentices here quite often. Great Job!!!

    • @bradvincet1848
      @bradvincet1848 2 роки тому

      How much do you enjoy being a factory rep as compared to working for a privately owned HVAC contractor? Thanks.

    • @DiamondBackRS
      @DiamondBackRS 2 роки тому

      @@bradvincet1848 For me, There was good and bad. The smaller shops don't have a lot of the support but working for the Factory, there is way more corporate bullshit you have to deal with. It all depends on what you can tolerate. When I worked for York, it sucked completely. Corporate would take all of our profits from our office division, and then peddle back pennies for our tools etc... Siemens was the same way. I work for the largest privately owned contractor on the west coast, now, a Union Shop, and we have almost 100 HVAC techs in Service.

    • @DiamondBackRS
      @DiamondBackRS 2 роки тому

      I'm turning 57, and my body can't take a lot of the knees and carrying around 28ft extension ladders. I do straight piping construction install now. Working at Microsoft building their new 80 acre campus in Redmond wa Thumbs up!!! No more oncall!!!

  • @TomSmith-bd3lb
    @TomSmith-bd3lb 3 роки тому +97

    Great Job!! I am a licensed electrical contactor (in NC) with my Unlimited License and you have explained "Why Neutrals and Grounds are Separated in a Sub Panel" very accurately. Thanks for the time and knowledge you have shared with others!

    • @ZILAwelds
      @ZILAwelds 2 роки тому +3

      I still dont understand why you connect them in the main panel .... ?? in Europe people NEVER connect neutral and ground in any panel .. not the sub panels not the main panels .. ever ....

    • @TheFenrirulfr
      @TheFenrirulfr 2 роки тому

      @@ZILAwelds What.. what are you talking about? Yes we do?

    • @bcubed72
      @bcubed72 2 роки тому +3

      We've had electrical service for over a century. If it took them until 2008 to put the kibosh on this, it can't be THAT great a safety risk, can it?

    • @smoke7877
      @smoke7877 2 роки тому

      @@ZILAwelds u guys dont have lightning in europe?

    • @kakepko
      @kakepko 2 роки тому +1

      @@bcubed72 Your observation is correct. This has been in the NEC for well over 50 years.

  • @stop2kare472
    @stop2kare472 4 роки тому +11

    It's crazy how life works.. 3months ago (11 months into my apprenticeship) I did not understand a word this guy was saying.. I would just watch something else.. now?! I understand so much more! I always come back and I learn something new.

    • @matthewjackson9615
      @matthewjackson9615 3 роки тому +1

      You said something important here , namely online learning is valuable. I agree fully.

  • @jimchristy573
    @jimchristy573 Рік тому +57

    I learned years ago that electricity doesn't just flow in the path of least resistance, it flows in every path available with the majority going to the path of least resistance.

    • @henryptung
      @henryptung 8 місяців тому +3

      You can really think of electrons in the conductor like a nearly incompressible fluid in pipes. Flow is established via propagation of pressure waves back and forth until equilibrium is reached - on non conducting paths, equilibrium just means static voltage/pressure rather than flow along a voltage/pressure gradient.

    • @mahmoodmirza3301
      @mahmoodmirza3301 7 місяців тому

      I suppose bonding the EGC to the Neutral conductor on Sub-panels would force MCB's to erratically not break the circuit spontaneously in case of overloads ?
      Certainly current loops would cause data corruption on data lines between devices present on different sub-panels.

  • @scottg444
    @scottg444 4 роки тому +302

    You did a great job explaining this. I’m 36 years into this trade and this was one of the better explanations I’ve listened to.

    • @4biz79
      @4biz79 4 роки тому +7

      Agree Have 36+ myself and THIS explanation IS the best by far

    • @scottg444
      @scottg444 4 роки тому +7

      4Biz surfing around UA-cam I’ve seen so many guys giving how to videos on various wiring methods and Installations that have no business teaching anyone. It makes me sick. Unfortunately someone’s going to follow their advice and get someone killed or burn someone’s house down. There’s been a couple things his done on some of his other videos that sort of made me cringe a little and I think man if I could just show him a few things it would really help him and he’d really excel

    • @mdrmoose
      @mdrmoose 4 роки тому +2

      Damn shame 36yrs in trade calling yourself an electrician, and your taking tips from this amateur.

    • @scottg444
      @scottg444 4 роки тому +70

      Dre Day where did I say I was taking tips. I heard this try to be explained by so many “electricians and trade teachers and even engineers” and all I said was this was one of the better explanations I heard given. You need to read what I wrote a little closer. I said I’d love to be able to show him a few things. Besides that I am always learning new things, you have to in todays world because things change so rapidly. I don’t use methods today I used 30 years ago. If you think you know everything and are unwilling to adapt your not much of a electrician. Although Maybe your one of those people that know everything.

    • @erlycuyler
      @erlycuyler 4 роки тому +7

      @@scottg444 I like to get other opinions,too. I'm 30+years in the trade,but I'm rewiring my 132 yr old house and I'm not a residential guy. Industrial control work and commercial are completely different. Im not a know it all who wired the sun. As a side note,another electrician could tell an ind/comm guy did this work by looking at the EMT piping for my porch ceiling fans and lights. My wife loves it. Lol.

  • @rustylindsay4265
    @rustylindsay4265 4 роки тому +314

    Ben I am a master electrician and wanted to say your demonstration was spot on and is an excellent teaching tool to show the importance of bonding and always trying to handle your loads. In Maryland we use to bond to gas pipes and had to install ground jumpers across unions on gas pipes . I subscribed to your site and will be checking your videos out. Keep up the good work !

    • @kayjet64
      @kayjet64 4 роки тому +12

      But why say power and not current.

    • @edduanchavez3346
      @edduanchavez3346 4 роки тому +3

      I’m 2 years into my own apprenticeship 🥺 also MD :o

    • @robertkat
      @robertkat 4 роки тому +13

      Never ground to a gas line. gaslines are plastic! The black pipe is only 2.5 feet long.

    • @flagmichael
      @flagmichael 4 роки тому +2

      @@robertkat If I understand right it is propane; metal but still very short and should be wrapped where it is contact with the soil.

    • @robertkat
      @robertkat 4 роки тому +10

      It is a natural gas pipe line underground 3 feet, yellow plastic. Comes up to the meter with black steel pipe covered with polyurethane. No ground contact. BC Canada. Groundrods are steel rods electroplated
      with a thick copper layer.

  • @jimmejean4130
    @jimmejean4130 3 роки тому +189

    There is a load somewhere in the system that connects its ground and its neutral. I would check the leaking current while switching each individual breaker off until identifying all ground and neutral connections.

    • @Brian10369
      @Brian10369 3 роки тому +22

      Could be induction as well. I see they followed the 90 degree rule on all those grounds (after the 90 up is a little close to that second leg) we see in the video but, I would have routed them the long way around to avoid this. Just my 2 cents.

    • @scottsmith8088
      @scottsmith8088 3 роки тому +8

      Maybe he has a 3 wire range or dryer in his house. Not sure if that is why but I'm just speculating.

    • @ironphill911
      @ironphill911 3 роки тому +8

      Dimmers and electronics sometimes leak a small amount to ground. Or possibly some leakage on the coax ground.

    • @chrisowen2925
      @chrisowen2925 3 роки тому +24

      @@ironphill911 LED lights, UGH I have to connect the Ground Neutral then HOT to keep from getting a buzz to the hand.
      Surprisingly when I connect the neutral after the ground many times I see an arc.
      So not sure those Chinese are following NEC and UL specs all that closely.
      MADE IN CHINA is the new warning label.

    • @michaelkeller7789
      @michaelkeller7789 3 роки тому +2

      Likely it is inducted.

  • @StraitClownin909
    @StraitClownin909 2 роки тому +1

    4th year apprentice here. This is the best explanation I've seen on this topic thus far. We should play this video at my trade school. Well done.

  • @thomasjefferson1457
    @thomasjefferson1457 4 роки тому +16

    Great video. I also worked as an electrician during my career (now retired) and knew some of this but didn't realize there were so many other paths for the electrons to find their way back to ground. Proves that we never stop learning.

    • @JulesBartow
      @JulesBartow 4 роки тому +1

      If you're retired, the reason you have to keep learning is because of CRS. I learn the same thing 4-5 times per week according to my great grandchildren.

  • @jessehooper8491
    @jessehooper8491 4 роки тому +60

    I worked for the Gas company for 35 years. A fellow employee and close friend was changing a gas meter on the side of the house. He was on his knees as he attempted to stand up due to limited room on the side yard. He put his hand on the fence and the other hand on the meter set assembly to get up and was electrocuted and fell unconscious.
    The house was feeding electricity back through the gas line. As a result employees now use a low voltage tester to test the meter set assembly before working on the gas meter. The employee after several years regained use of his arms after severe nerve damage.
    Thank you for this video, very educational.

    • @Rick-the-Swift
      @Rick-the-Swift 4 роки тому +1

      I always wondered how people get shocked when touching a grounded piece of metal. Was it perhaps a very dry sandy climate? Otherwise it seems like the electricity would normally take the path of less resistance, and a metal pipe being buried for miles under ground would seem the natural path.
      Or Can the gas co. use plastic or other insulating materials as pipes or junction points? Maybe they do this to protect themselves?
      Appreciate your thoughts and insight.

    • @jessehooper8491
      @jessehooper8491 4 роки тому +7

      @@Rick-the-Swift
      The employee completed the ground by touching the hot house line and current went through his body to the chain link fence.
      The employee had removed the gas meter prior to touching the fence.
      On all gas meters sets an insulating bushing or Union is installed if the gas service is steel.. Over the last 40 years or so only plastic service and mains are installed.
      The incident occurred due to improper house wiring. Just an example if wiring is not done correctly.
      Thank you for your input, I hope this explanation helps.
      By the way, the employee was nick named
      “SPARKY” and was called Sparky for many years after.

    • @Rick-the-Swift
      @Rick-the-Swift 4 роки тому +2

      That makes sense that the gas pipe was insulated while the metal fence wasn't. Regarding the bad wiring, I've encountered times when grounds were "borrowed" for neutrals because I'm guessing whoever wired it that way likely didn't have the proper amount of wires when installing or didn't want to fish for a neutral. Combine that with the fact that many people have their panels grounded to a gas or water pipe and I could see the potential for these things to happen. Thanks for helping to make me feel a bit smarter.

    • @Shroommduke
      @Shroommduke 4 роки тому

      I love a good anecdote!

    • @junmanacmol8671
      @junmanacmol8671 4 роки тому

      @@jessehooper8491 this guy sparky channel right now?

  • @danperkins2430
    @danperkins2430 3 роки тому +91

    Awesome video. Suggestion: To identify the possible source(s) of leakage to ground, turn off all breakers, monitor the current on your sub panel ground conductor, and turn on one breaker at a time. Note which breakers cause current to be present on the ground wire.

    • @willie9397
      @willie9397 3 роки тому +7

      process of elimination right

    • @ottoroth3066
      @ottoroth3066 2 роки тому +5

      There is some bonding on the furnace if you are getting a reading on a gas line. Look for a ground clamp inside the furnace service panel that installed by the installer.

    • @RobertKarlBerta
      @RobertKarlBerta 2 роки тому +9

      I am a retired electricl engineer that worked for a power company for 36 years. If you have current on the gas pipe it is VERY dangerous. . Case grouns connect the case of stove, clothes washers, refrigerators so that if you touch one appliance and another and the hot leg/ground is reversed you get a bit of a shock. A case ground/neutral should never be connected to the actual ground. That current showing at the gas pipe could cause damage and gas leak through the pipe and than a fire. Don't fool around if you are at all nervous about working with electricity. I would recommend a licensed electrician.....many "electricians" ARE NOT licensed and while they may be OK....they could also make a mistake. Should you have a fire the insurance company would most likely check if wiring was incorrect and if it was the homeowner that did the work...THEY could be SOL.
      When i see UA-cam videos trying to show how to do something like his it scares the hell out of me. There is a good reason why cities require work like this to be inspected after done. There are also issues with balancing the load across both circuits but I won't get into that.

    • @douglundy5755
      @douglundy5755 2 роки тому +9

      @@RobertKarlBerta I do electrical work and find plenty of licensed electricians who miss half this stuff. Its about education and support to pay for the needed work to be done correctly. Ive followed these guys around for a full day troubleshooting a job and they never solved the issue and the next day I located the problem myself and corrected it. And you cant believe the BS song and dance Ive heard from licensed professionals which I know is totally false in order to charge for repairing "broken wires" in the walls. And Ive paid top-dollar electrical contractors and had them leave me with an "Open Ground" which messed up the voltage, creating about 90 volts house-current, after the inspector checked the work as ok. And I called the inspectors back and they called for corrections ASAP. (I wont name any names, but they're well known in my home town) You cant depend on a certification, it simply gives you leverage on the need to correct bad work.

    • @stuarth43
      @stuarth43 2 роки тому +7

      @@RobertKarlBerta just because one is licensed or not, means little, people with no training can be very very clever and pick up stuff quickly, they can read and absorb stuff and apply it to practice, licensed house electricians know zilch, they are unemployable in industry, mining, aviation and ships engine rooms and reticulation, I do all my own stuff, switching in star/delta etc, I wire the vessels i build but get it signed off by a licensed person
      sure you are correct about the furnace, this guy just put up a good vid, give him some praise

  • @jeffhill6861
    @jeffhill6861 2 роки тому +42

    I spent years working on electric controls for cranes and conveyors but never had any reason to work on service entrance panels or sub panels. You did a great job of explaining why the neutral and ground need to be separated in the sub panel. I really appreciate your teaching skill.

    • @stringlarson1247
      @stringlarson1247 Рік тому

      I did a lot of industrial controls work when I was a EE engineering co-op and transitioned into the software side. This was in the early 80's and our dainty little circuit boards had to live with 3ph motors, etc. This was in the early 80s, and a lot of the heavy stuff was not as sophisticated as they are now. Man, talk about EMF, current, etc.
      Purdue had a lab in the basement full of motors, caps, coils, and big wires we had to connect up various scenarios for dealing with startup and phase shift andetc. All 440 3ph. Just the potential (pun intended) for disaster forced one to think, re-think, check, re-check many times before throwing the switch.

  • @randyhinson9115
    @randyhinson9115 4 роки тому +6

    From a master electrician best explanation and proof why to separate that I've seen my local inspector didn't know this! You sir have done a great job with this video!

    • @jmb9518
      @jmb9518 3 роки тому

      Inspectors are only failed contractors or someone who could not make it in the real world contracting...they do not know shit unless they can find it in a book or conjure it in their their little shit heads....Virginia...I do not know about other localities.

  • @CCEASER2002
    @CCEASER2002 3 роки тому +107

    The weird current you're getting can also be from your stove or dryer not having the neutral/ground separated out when they made them 4 wire. There is a bonding jumper added to both dryers and ranges for 3 wire configurations that use to be allowed.

    • @paulobarcelos3630
      @paulobarcelos3630 2 роки тому +3

      Stoves for sure

    • @Greasyfingers60
      @Greasyfingers60 2 роки тому +3

      I didn’t think of that. I am going to check this in my house now.

    • @fitybux4664
      @fitybux4664 2 роки тому

      This just smells like "ah, more work for a licensed electrician to charge for and fix". 😁 (Run a new feed that has four wires so ground is properly done.)

    • @ronmaynard7424
      @ronmaynard7424 Рік тому +5

      My issues was my hot water tank, and I never found it till one time we lost one leg of power to the shop and a few lights on the down leg glowed slightly and I turned off the hw breaker and it quit. Now any phantom loads I always start turning off 220 breakers til it quits...

    • @carsonconlee6277
      @carsonconlee6277 Рік тому

      The bonding jumper is usually pre installed on the equipment so if the installer doesn’t know that they need to take it off then RIP

  • @raymondsevert3589
    @raymondsevert3589 4 роки тому +61

    I really appreciate someone who has gained enough knowledge and experience that they are able to explain concepts to people in a clear manner. That is a skill not many people have, even in their supposed area of expertise. I congratulate you. And thank you. I am learning a lot from you, even in my old age.

    • @hkelly1623
      @hkelly1623 3 роки тому +1

      It helps to understand the reasons for the requirements of the NEC. (Bot: "NEC" is the acronym for National Electrical Code.)

    • @soilmanted
      @soilmanted 2 роки тому +1

      I also appreciate it when someone can explain ideas clearly. I agree not many people have that skill. And I don't think Benjamin Sahlstrom has that skill. He is not always choosing his words carefully, and sometimes he ends up saying something that could be interpreted more than one way, he says something ambiguous and therefore I don't know which of the 2 or more possible meanings is the correct meaning. He does this quite freqently.

  • @88v98
    @88v98 2 роки тому +102

    In your panel the two black "hot" conductors are passing over the ground wires coming from the various outlets in the home. Although they are insulated, the AC current in the hot conductors generates a changing magnetic field which will induce a small current in the ground wires. This follows the same principle as to how your Clamp Amp Meter is able to measure current flow. Other devices in your home that draw lots of power could be doing something similar (ie. inducing current on the ground wire).

    • @markrobinson2435
      @markrobinson2435 Рік тому +9

      Exactly.

    • @crellis2000
      @crellis2000 Рік тому +6

      The reason that in the main panel the neutral and the ground wire are connected together is that if the neutral wire becomes disconnected (e.g.falling tree limb) then the main panel may end up with unbalanced voltages (e.g. 160 volts across 1 hot leg and 80 volts (240-160) across the other hot leg. This means that by separating the neutral and the ground at the sub panel then the same 🎉disasterous situation could occur if the neutral to the sub panel is disconnected for any reason.

    • @crellis2000
      @crellis2000 Рік тому +1

      To add, the possibility of a neutral break in the line between the main an sub panels would be unlikely since the wire is enclosed in pipe. The falling tree limb scenario would not happen with this neutral line

    • @SteveSmith-nh6ms
      @SteveSmith-nh6ms Рік тому

      @@crellis2000 Why would this cause an unbalanced voltage? Also, would the return current now be returning through the grounding electrodes?

    • @crellis2000
      @crellis2000 Рік тому +1

      @@SteveSmith-nh6ms sorry Steve, I didn’t answer the second part of your question. Yes, if both the neutral and the grounding wire are connected, and the neutral wire is broken, i.e. falling tree limb, then the ground will provide the route back.

  • @johnnyb8629
    @johnnyb8629 4 роки тому +37

    yup, absolutely, I work in HVAC and I had a service call once at an old farm house in Kane Co Illinois here. I went to pull the panels off their old furnace in basement, kneeling on the damp concrete floor and got nailed. I got nailed about 3 times before I realized the furnace and gas line was electrified with about 90 volts. I touched the panel of the furnace with one lead of my Fluke and touched the concrete and got 90 volts. After some investigating I found the grounding rod strap was broken off the grounding rod by lawnmower and the panel still had the bonding strap installed. So, I learned about all this the hard way and sometimes, that is the best way to learn them because you;ll never forget.

    • @jimmyb1451
      @jimmyb1451 4 роки тому

      Same thing happened to me (well similar thing). My last rental house, had a chrome pedestal fan in the shed. After a few days rain, in bare feet, went to move the fan and almost latched onto it. Measured from the neutral to a steel rod on the concrete and got 140v. On further inspection, it turned out whoever had replaced the feed from the house to the shed had only run twin. No earth at all.

    • @johnnyb8629
      @johnnyb8629 4 роки тому

      @@jimmyb1451 lol, no Earth ground at all. That'll do it.

    • @jimmyb1451
      @jimmyb1451 4 роки тому +1

      @@johnnyb8629 well.... in this case, yes.
      There are times when a floating supply is far safer than an earthed one.
      But yes, given that it's grid power... no earth'll do it every time.

    • @katemoon7476
      @katemoon7476 4 роки тому

      You mean a sub-panel still had the bonding strap installed, right? Because there is no bonding strap in a furnace. Also, they must not have had two grounding rods pounded in. Redundancy is important for something like this. And another thing, I bet the rust on the bottom of the furnace made it insulated, because if you got a shock, then it had to be electrically isolated.

    • @johnnyb8629
      @johnnyb8629 4 роки тому

      @@katemoon7476 It was the strap that connects the grounding rod to the panel broken off by lawn mower or something, and yes they still had the ground buss connected to neutral buss. everything was electrified, the furnace chassis , the gas pipe, was 90 vac from chassis to concrete floor.

  • @TheJustReyes
    @TheJustReyes 4 роки тому +21

    Im SO glad you reconsidered your idea to disconnect your neutral wire.

    • @beltrams
      @beltrams 4 роки тому +4

      If you disconnect the large neutral wire as you know, you'll send all the neutral return current through the jumper. Now at the moment you did this test, you didn't have a great many loads running in the house - only about 15-16A, but because you turned off every other breaker, you caused a pretty unbalanced load between the two hots. If more and larger loads happen to come on, you could easily see 40, 60, or more amps on that jumper wire and of course it doesn't have overcurrent protection either. Well, at least you'd be there to respond to the melting jumper wire.

    • @rogerf7229
      @rogerf7229 3 роки тому +1

      Whoah. Sounds really dangerous. You know that warning sticker...DO NOT PLAY ON OR AROUND its for kids. You need 1 on your breaker box!
      Or how 'bout KEEP CLOSED

    • @rogerf7229
      @rogerf7229 3 роки тому

      This is essentially the ongoing argument...
      3 wire 220 stove vs
      4 wire 220 stove. Grounded chassis or not..
      btw Some 220 v. Pool Equipment won't work with Neutral shorted to Ground. Best they're kept separate. Ground is for grounding the electrical chasi. Only. I do understand you're looking for leakage. Trying for safety. I'd unplug 1 appliance at a time until I find them. Vampire draw.. parasitic draw..
      Motion sensors... TV actively searching (watching) for remote control signal to power up, well that consumes power!
      Thank you 4 food 4 thought!

    • @vinquinn
      @vinquinn 3 роки тому +2

      An unbalanced load without a neutral can destroy all your lamps and appliances.

  • @azstanp
    @azstanp 3 роки тому +152

    The reason you are still getting current (albeit much less current) flowing through every single pathway to ground is because current is flowing from your main panel (which IS tied to neutral) through every single possible parallel pathway to any ground source. So some current is back flowing from the main panel ground/neutral back to the subpanel ground wires to anything that is connected to the earth (chassis, copper pipes, etc.). Electricity takes ALL available paths. Remember, even paths of relatively high resistance that are in parallel with other paths of low resistance will pass current. Think of it like a big water tank sitting on a hill. Sure, most of the water will flow through the biggest pipes, but even a pin hole will allow droplets to weep out too.

    • @BenjaminSahlstrom
      @BenjaminSahlstrom  3 роки тому +19

      Excellent explanation.

    • @azstanp
      @azstanp 3 роки тому +14

      @@BenjaminSahlstrom Thank you for your kind words. Electricity is a fascinating force, and I don't think we realize how little we really know about it.

    • @billbest9483
      @billbest9483 3 роки тому +1

      So, you can disconnect to ground back to Main panel outside and measure your neutral to see if the 2.2A is added to your remaining grounded (neutral) measurement.

    • @WVProfessor
      @WVProfessor 3 роки тому +8

      If you have bonding as you said then there is a path from all of your earth grounds to the earth ground at the power pole which is connected to the neutral of the transformer. That path is in parallel with the neutral wire from the pole to the house and can take some of its current. If you don't have bonding anywhere in your house system then there is still a tiny current because of high resistance leakage and even more by capacitance inside of equipment. I once connected a transformer to the line and measured 80 volts from the secondary to ground using a VOM. You can determine the presence of AC by feel if you are grounded (a high resistance ground is safer) and you lightly rub your hand against a live metal surface (it is safer if the metal is painted). The feeling is a buzz which is present only while your hand is moving and it is caused by the electrostatic attraction that is present with the voltage. This is called a poor man's voltmeter.

    • @brucerickey8328
      @brucerickey8328 3 роки тому +9

      Your response makes sense and alludes to other potential sources: Induced electricity, such as can occur when current passes through one wire and the other wire picks up a charge when the two wires are close together, spinning motors or other means. When I am teaching basic electrical system theory I use the water pipe theory. Black is your water supply line, the sink is the equipment where work is done, white wire, like PVC pipe is your drain or return/neutral line and the ground wire is the bucket you put under the drain in case it leaks. The ground is never intended to be a primary source of drainage. That in general helps most people visualize residential energy flow. I explain that bonding is a type of grounding that connects various systems to the ground. So, to your point, if it was your intention, is that current in ground systems can flow both from the panel or to the panel. I have a suspicion that the energy flow could very well be flowing into the panel and out the ground and or neutral and could be independent of the energy that originated from the panel (think as a drastic case, lightening strike). The sources of electricity could be multiple, hard to track down and possibly impossible to completely eliminate. That is why the system is there, to allow for a method to drain this induced electricity that some equipment can store up a charge as a capacitor would. The bonding and grounding systems provides a low resistance pathway. That said, to the best of one's ability, those stray sources should be identified and eliminated where possible.

  • @seditiouslibel
    @seditiouslibel Рік тому +1

    First & foremost, thank you. I have been in the electrical industry since 1978. Master electrician since 1990. This is clear and well explained as it relates to isolating these conductors. Secondly, the load center is tied in nicely. A true craftsman. Not sure who tied it in, but coffee is on me. Stay safe!

  • @JarredSutherland
    @JarredSutherland 2 роки тому +15

    I really appreciate videos like this. I am not an electrician but I do work on my home from time to time (including working on installing solar right now) and I really love to learn as much as possible. The fact it was passing to ground via the gas line .. freaks me out a bit.

    • @jaywalsh31
      @jaywalsh31 Рік тому

      no need there is no risk. i have disconnected a gas line and lit it up with my torch it wont combust it just puffs and puts itself out. gas is only a danger when it is allowed to fill an empty space slowly from the ground up like a basement. the gas is more dense than oxygen so it immediately falls to the ground in an enclosed area. if you ever open your basement door and smell gas there is a very good chance the entire basement is full of gas. my 0.02$

  • @bryanburgess6396
    @bryanburgess6396 4 роки тому +152

    Ben: You asked why you still had some current leakage on your EGC without the bonding jumper connected between the neutral and the EGC in the subpanel. There are two scenarios where this will take place. The first and most likely scenario is there is some current leakage in the connected load served by your subpanel; dimmers, pilot lights, surge protectors, transformers and old worn lamp holders are the usual suspects (could be in the control voltage of your furnace). The good news is the current wants to travel back to the source, and installing a dielectric union on that gas connection will make the ground wire of the supply circuit to the furnace a higher potential than the gas line. The second least likely scenario is that there could be a potential difference between the grounding electrode system of your main panel and that of your subpanel, and you could have some neutral current from your main panel finding its way to the GES of the subpanel. By the way, your video is the best explanation for the existence of Article 250.24 (A)(5) that I have seen so far. Good job!

    • @MichaelDillin
      @MichaelDillin 4 роки тому +4

      That was nice thanks for the explanation. I was thinking cheap China wifi switches 😂

    • @Noldy2009
      @Noldy2009 4 роки тому

      Hello, So that I understand. Your saying that the Dielectric union will fix that low current leak because it isolates at the union? Thanks for the explanation. I initially figured that may be the issue but not sure

    • @NoOne-xp1pe
      @NoOne-xp1pe 4 роки тому

      @@MichaelDillin I think it is BigClive that has a video of a european USB charger that has a USB shield connected to hot (220VAC!!!) through poor design and careless construction!

    • @dickbuttz7428
      @dickbuttz7428 4 роки тому

      Serious knowledge there!

    • @gregwarner3753
      @gregwarner3753 4 роки тому +4

      This is why for jobs more complex than installing a light or outlet I just pay the electrician.

  • @oilman614
    @oilman614 4 роки тому +7

    As an older electrician, a lot of this is a great refresher and some is stuff I never knew. I am not 100% in the electrical field because I ventured over into the HVAC&R career

  • @rhoward6094
    @rhoward6094 Рік тому +2

    I been doing electrical wiring for years ( Elevator electrician) your review and code applications is excellent, easy to follow and understand, keep up the videos

  • @Craig1967
    @Craig1967 4 роки тому +9

    Wow, finally on UA-cam I can watch a video by someone that knows what they are talking about! Good job and explanation!

  • @marcsanchez324
    @marcsanchez324 4 роки тому +7

    I’ve been watching a video a night for the past week. This one has probably been my favorite as it explains what is happening to current flow and not to mention something every electrician ought to understand! The wiring diagram brought it all together for me. I’m a first year wireman apprentice and watching your videos have been helpful to my education. Keep em comin!

  • @paulseminara2483
    @paulseminara2483 3 роки тому +10

    Very good explanation. I installed a subpanel on my house years ago, I followed instructions and did it correctly for the exact reasons you describe. In fact all should be aware of any situation that could have return current on ground line(s). You used the word "power" interchangeably with current. The potential (voltage) will always be there, but you won't have power without current in a circuit. Thanks and subscribed!

    • @chrisowen2925
      @chrisowen2925 3 роки тому

      It is interesting how many sub-panels have been installed years ago and WORK on the old standard but no one goes around checking them and requiring the changes.
      I went over to a friend's house and he has a sub-panel that a break was broken, worn out ...
      So I pulled the old one out replaced it and saw that that panel the GREEN and WHITE were bonded to the same ground bar.
      I might need to make a visit to change that someday.
      Also, his Dryer and Ranger use a 3 prong heavy amp plug that the NEC has not sent him a notice to update from several years ago when it was originally installed.
      Could be other items as the house was built in the '40s and updated as needed over the years.
      I should add that in the early 80s his insurance company paid for these LICENSED electricians (he check the licenses they had) to change his 2 slot outlets to 3 prong ones, I checked recently, and not one of those outlets are grounded. The original order charged the insurance to ADD a ground wire at each electrical box, not one of them was grounded. Explains why anything 3 prong with a circuit protection circuit shows a wire failure.
      The Electricians did ground the 3rd prong to the Neutral wire.
      Now he wants me to come in and rewire his home, not sure if I want that task, I do Low Voltage, but anything I do is better than what an ELECTRICIAN did.

  • @OldSneelock
    @OldSneelock Рік тому +1

    Great explanation.
    I am installing a sub panel in a new construction detached metal building that I am putting my workshop in.
    As I was checking the NEC for updates since that last time I installed a sub panel I found the ground rod requirement. That led me down the bonding rabbit hole and yours is the best explanation as to why it is done.
    Makes perfect sense.
    Now I am wondering how many sub panels are leaking to alternative grounds.
    Your comment on the gas line sparking is a concern. How many times have I unknowingly broken a loaded circuit by opening a gas line?

  • @justink7269
    @justink7269 4 роки тому +12

    You really nailed it. This video could be part of an electrical training curriculum. Great work

  • @lespaul36
    @lespaul36 4 роки тому +10

    Learned a lot from this. I was an electrician's helper for a couple of years, but I never really got an explanation on the loads for panels and balancing since it was pre designed I just followed the blue print. Now it makes a lot of sense, thanks.

    • @Lost1inDetroit
      @Lost1inDetroit 3 роки тому +6

      You did not get an explanation probably because of the person training you did not understand the theory.

    • @lespaul36
      @lespaul36 2 роки тому

      @@Lost1inDetroit Most of the companies I went to we were basically cable pullers. The journeyman that got me in to electrical taught me basics of 3 phase, length, gauge, and doing a legal install. But, theory was not taught to us low level workers since we were considered labor. I was pretty excited just to learn conduit bending from journeymen when they were up to it. Then went about the time I started apprenticeship school the recession hit and the company folded. Hell we had a lot of temp guys that didn't even own a drill.

  • @gabedodson6378
    @gabedodson6378 4 роки тому +8

    As a fellow Minnesotan, I really appreciate the information you share! Keep the great videos coming!!!

  • @REEFTANKGENIUS
    @REEFTANKGENIUS 2 роки тому +1

    Thank you so much. After watching like 10 videos of how to troubleshoot a water heater. Yours is the only one that actually thoroughly explained everything enough for me to fix the water heater myself. God bless you sir

  • @Artisan.HVACR1
    @Artisan.HVACR1 3 роки тому +3

    Good video! I'm a fellow HVAC/R skilled tradesman. I saw on your "About" page that you've ventured into the plumbing and electrical trades as well. That makes sense, since the HVAC/R trade requires that we know both of those trades as well.

  • @timdonley9324
    @timdonley9324 3 роки тому +6

    Great explanation that brings to bear why on yachts (or any boat with shore power) the neutral conductor floats on the electrical panel, NEVER jump the nuetral and grounding conductor together on a boat. This happens back on shore at the source.
    We test for potential on boats because the water around the boat can be energized with AC current....FATAL mistake if you fall into the water.
    When we find low current such as you find on the gas line we shut off all breakers and energize one at a time until we find potential. When we find voltage to ground we turn off or isolate items in that circuit until the leak stops.
    A number of times it is an appliance or piece of equipment that has a ground fault of some type will be discovered.
    Energized grounding conductor will then create electrolysis with interaction of dissimilar metals underwater the water becomes an electrolyte to carry current potential between the disimilar metals. Boats have sunk, metal appendages have wasted away and has proven fatal to swimmers as a result.
    This can cause electrolysis with neighboring boats as they share the common grounding conductor through the power pedestal on the dock.
    My boat has an isolation transformer to disconnect me from the potential stray current from other boats while grounding my system.
    Marine electrical systems are specialized systems with potential to mortally

  • @DoctorSparta
    @DoctorSparta 3 роки тому +5

    No one else has been able to explain this well enough for me to understand the full concept. Thanks for putting in the effort man, seriously.

  • @StonyAcresEstate
    @StonyAcresEstate 3 роки тому +1

    Thank-you so much! After watching your video, I realized that I never removed the neutral crossbar in a sub panel that I installed in my basement (next to the main service panel). I removed it, and the grounds and neutrals are now separated. It 'looked' correct with all the grounds installed on one side and the neutrals installed on the other, but both bars were tied together with the crossbar!

  • @sunshine7453
    @sunshine7453 4 роки тому +11

    This is the best explanation I heard. You did it with examples when they are connected and when they are not. Thank you!

  • @kevrobster
    @kevrobster 4 роки тому +11

    Best explanation I've seen of this. I did a lot of googling and read a lot of useless information on this before it finally made sense, and you just explained it in a completely logical way in a matter of minutes. Great stuff! Subscribed

  • @glennmaccrimmon2375
    @glennmaccrimmon2375 2 роки тому +4

    A couple of years later, still really good stuff. Thanks, Benjamin.

  • @DRW922
    @DRW922 2 роки тому

    My daughter told me her rose bush shocked her. I went over and stuck a long screwdriver into the dirt and connected my volt meter to said screwdriver and her mobile home. l got 90 volts. We turned off one breaker at a time until the voltage went away. It was the kitchen stove. Pulling a new 8 gauge wire to the stove fixed the problem. This is a great article! Thank you Benjamin.

  • @ronniekennedy9897
    @ronniekennedy9897 4 роки тому +32

    Thank you for demonstrating a concept that Nobody could explain to me.

    • @shawnh8498
      @shawnh8498 4 роки тому +3

      I think it's because he assumes nothing and does this as if the person is intelligent but has never done this before and he lays it all out so nicely with details that others just forget to add for the layman that doesn't know that little tidbit of information the normal worker doesn't think twice about but is essential for true understanding of the topic. I personally knew 3 phase at the outlet wiring and thought the neutral was another word for ground but now like youself know what that wire does. What amazes me is the gas line does not explode with electricity running on the copper since copper is conductive I'd think the gas would just explode but that was an incorrect assumption on my part but that scares the hell out of me gas and current together just makes my old fashioned mind twitch with anxiety of gas explosion without warning.

    • @ronniekennedy9897
      @ronniekennedy9897 4 роки тому

      @@shawnh8498
      Yes. I have never gone to school for it, but I have been wiring for 40 some years. I knew not to do it,but never knew exactly why. I guess the demonstration clicked in my head.
      And yes, I agree that gas and electricity don't go together!

    • @NoorRefrigerationsystem
      @NoorRefrigerationsystem 4 роки тому

      Right sir

    • @fredhof8326
      @fredhof8326 4 роки тому

      @@shawnh8498 An explosion is a chemical action. That action requires a fuel, oxygen, and an ignitor - all present together. For an explosion to occur, the fuel (gas) must be in the presence of oxygen and a heat source (like a spark) to cause the fuel and the oxygen to combine.

  • @fredthompson5785
    @fredthompson5785 4 роки тому +113

    Remaining voltage on the ground is probably induced into the frames of motors, transformers, and the wires themselves. Bundling wires looks pretty but traps heat and promotes induction.

    • @markgigiel2722
      @markgigiel2722 4 роки тому +2

      Winner! 🏆

    • @dougthornton151
      @dougthornton151 4 роки тому +3

      I agree in a commercial scenario. Not so much in residential ...minimal loads on branch circuits. Besides, the conductor lengths in the load center are negligible......

    • @KurtisSaiyo
      @KurtisSaiyo 4 роки тому +9

      @@dougthornton151 my grandfather (an EE) had a breaker not connected to his AC circuit trip every time his AC kicked on. He figured out that circuit was run right beside the AC circuit and current draw on the starting compressor was enough to induce a current that would trip this breaker. I could imagine a bit of current being induced by other circuits run next to each other, especially in the same conduit.

    • @miguelac6872
      @miguelac6872 4 роки тому +4

      What would happen if the neutral wire that is in the sup panel gets cut and there is a unbalanced load between the two phases, in this case we do have neither neutral nor ground wires to send back to the source the unbalanced portion of the load. What would happen? do our appliances get burned up due to both either high or low voltage in one of the two phases?

    • @rogerf7229
      @rogerf7229 4 роки тому +4

      About bundled (includes shared conduit) wires unwantedly conducting... SparkPlugWires in a car do that, causing a misfire! 🎶 Gotta Keep 'em Separated 🎶AutomotiveGearHeads say that " the Plug Wires are Communicating "
      Or, (Hi how ya doing KA POW ) for short, "communication".

  • @williampommeranz6821
    @williampommeranz6821 4 роки тому +9

    One of the branch circuit neutral conductor is grounded at the load. Start with the electric oven, dryer, air cond. Great video

  • @Mjake7015
    @Mjake7015 3 роки тому +13

    Great video. I suspect that current back to ground could be caused by a motor driven appliance. Sometimes a non insulated electric motor will cause small leakage back to ground. Just a thought. Im a licensed electrical contractor but I do make mistakes and always like to learn new ways to troubleshoot.

    • @MrWatlow
      @MrWatlow Рік тому

      You’re correct. Typically loads that are inductive like motors will “leak” some current back on the ground wire. I have seen that many, many times over the years.

  • @dantigley677
    @dantigley677 3 роки тому +4

    Hey Ben, I'm a newly certified Electrician here in Canada, Alberta and am having a hard time finding work at the moment so I've been self studying to keep myself knowledgeable about our trade. I really appreciate the in depth explanations you have and showing real world examples, I typically have a harder time understanding these concepts out of a book. Keep up the good work and you've definitely earned my subscription!

    • @JamesBrown-fd1nv
      @JamesBrown-fd1nv 2 роки тому

      Same here for other stuff. The best simple practice I learned when studying beam loading for stress prediction was to draw a stick figure, also called a free body diagram (FBD). Very much like how this video showed.

  • @robertbush7290
    @robertbush7290 3 роки тому +96

    That little bit of current you are seeing on the ground wire and the gas line are simply caused by induction. Hot wires with current flowing through them are inducing a current into the ground wire and gas line through the process of "Electro Magnetic Induction".

    • @dereknewton4247
      @dereknewton4247 3 роки тому +13

      you got it! see in the panel also the neutral are even parallel beside the ground wires. see How Transformers work. If the white returns were twisted with bare ground wire then that helps reduce this electrical noise. ie. the wire conductor criss cross each other induced current cancelling each others out. TADAH :)

    • @marvtomson574
      @marvtomson574 3 роки тому +2

      LOL Damn! I was going to write that down, but see someone already beat me to it. I somewhat had a similar issue several years ago, except with junk noise somehow getting on a LAN network wiring. It was parallelly induced.

    • @JohnDoe-le8fy
      @JohnDoe-le8fy 3 роки тому +3

      "Eddy Currents"

    • @solomondg1
      @solomondg1 3 роки тому +6

      I think it may also be current coming from the main panel's ground. Since the sub panel ground, gas lines, and grounding rods are all connected to the main panel via the EGC everything becomes a ground return path from the perspective of the main panel. I wonder if you disconnect the EGC will there be current in the gas line and ground rod.

    • @mdwynia
      @mdwynia 3 роки тому

      @@JohnDoe-le8fy q2

  • @stevem1081
    @stevem1081 2 роки тому +10

    As others have stated, you could be getting that current from things like stove/dryer plugs that only used 3 prongs. And you have separate ground rods at the panel and the house. Years ago, the cell sites installed massive ground rings around the buildings, at each corner, a ground wire was run to the ring. Every time lightning was near, they lost a lot of equipment. They found out by only using 1 ground coming out of the building instead of 4, the voltage would rise evenly on the equipment and not be destroyed! As the separate grounds created a ground loop, which created a difference in potential. So, is having the ground rods at the house a good move since it is a sub-panel?

    • @cumminspower
      @cumminspower 2 роки тому

      Cell sites and central offices still do install ground rings

    • @chrisdurkin7
      @chrisdurkin7 Рік тому +1

      @@cumminspower They may still install ground rings, but they are only connected to the electrical system at 1 point. (In the example in another comment, initially they would connect the ground rings, to the system, at each corner of the building. This would create 4 different ground loops. This would create different "ground" potential on equipment in different areas of the building. Of course all that equipment has signal wires, antenna cables, etc. interconnecting everything, and the difference between one equipment ground and another equipment ground, would cause those two pieces of equipment to be fighting each other, electrically, and it would eventually feed through equipment interconnections (data cables, antenna cables, feed signals, distribution signals, etc.) and fry the electronics. Once they only connected to the Rings at 1 location, then all of the equipment grounds were the same, thus no ground loops, thus none of the equipment fighting each other, and none of them would be damaged.

  • @fitnessmag9186
    @fitnessmag9186 Рік тому +1

    Thanks for this video, I have explained this many times but your delivery makes it much easier to follow. Not just claiming the path of least resistance. Thanks .👍

  • @vincentcorrao7094
    @vincentcorrao7094 4 роки тому +101

    Not Only Does Ben know his....Stuff! He is an Excellent Teacher...Codous and THUMBS-UP...Thx. Vince

    • @lordmerren9094
      @lordmerren9094 4 роки тому +5

      Spelled "kudos"

    • @michaeljorgensen790
      @michaeljorgensen790 4 роки тому +4

      NO. NO he is NOT and excellent teacher. He is obviously not a Master Electrician let alone an Electrical Engineer. He should not be teaching as he is learning and "discovering" things that he did not know before. This is pure lunacy. Countless times he said "Power" when "Current" was the proper term.

    • @maxclark11
      @maxclark11 4 роки тому +3

      Check your refrigerator. Fan motors operate in a damp environment and leak current into the ground system. Refrigerators often will trip a GFCI.

    • @DigitalImageStudio
      @DigitalImageStudio 4 роки тому +3

      @@michaeljorgensen790 makes me cringe a bit, "amp meter" rather than ammeter too, 0.9A rather than 900mA , basic terminology should be fluent for anyone with reasonable experience.

    • @miguelac6872
      @miguelac6872 3 роки тому

      Guys suppose that we have unbalance phases in our electrical system, as a result our neutral wire carries certain amount of current back to the source let's say 20 A with 5 V to the transformer. Why do engineers say that connecting that neutral wire to a ground rod on the transformer will cause the neutral to be 0 V? Isn't voltage suppose to be energy per charged particle? If so, then how come those 20 A can make it to the transformer? Like with what energy per charged particle can those electrons get to the transformer if their potencial energy was taken ? I hope you can undestand my point and help me out with this question that nobody in colombia knows how respond to.

  • @WordofAdviceTV
    @WordofAdviceTV 4 роки тому +191

    Loved the explanation! Good job :) My sister is adding on a bathroom to a guest house and will be doing some electrical work so I am back watching this again as a refresher. You're the man Ben! 💪💪💪

    • @gracebonez
      @gracebonez 4 роки тому +2

      I’m pretty sure you don’t need more ground rods at your sub panel.

    • @dennisbielinski3611
      @dennisbielinski3611 4 роки тому +1

      Maybe a little more on why the scenario you explained is dangerous,

    • @tomhath8413
      @tomhath8413 4 роки тому +3

      @@dennisbielinski3611 Voltage on the furnace, gas line or whatever is looking for a path to ground. It doesn't care if that path happens to go through your heart.

    • @situbes.972
      @situbes.972 4 роки тому +5

      Since grounding is grounded (aka 0 volts) it carrying a current. Lets say for some reason he had to disconnect his gas line. Now there is potential (aka voltage between to separate pieces). Which contacted together can gas a spark.
      2. Suppose the he cut himself working with that seperate pipe. He could get shocked if rest of him is well gounded. (Your skin is somewhat insulator until voltage overcomes it. But your blood has a much lower breakdown voltage).

    • @timkarcher6724
      @timkarcher6724 4 роки тому +2

      So is the equip ground bar in the sub completely isolated from the metal sub box? If a sub is right next to main and connected to main with a metal conduit wouldn’t the sub effectively be part of the main box?

  • @mattfowler9304
    @mattfowler9304 2 роки тому +4

    As a 3rd generation carpenter ive spent a whole lot of time talking to electricians, i cant say ive ever enjoyed it. That being said, i just subscribed to your channel and clicked the bell so i can be notified of any new videos you share with us. Thank you for not being a condescending jackass and giving us a very thorough explanation WITHOUT the ever present patronizing delivery that ive come to expect from a Sparky lol. Great video, and thank you for sharing it. Stay Safe.

  • @whysguy3
    @whysguy3 2 роки тому

    I just got turned onto your channel so far I’m enjoying it. If I might be so bold to make a recommendation about the subtitles I would suggest that you leave them up for more than one or two seconds so slow readers like myself don’t have to go back and pause the video.

  • @beotheguitarist
    @beotheguitarist 4 роки тому +35

    Thank you, thank you, and thank you for making this detailed video. Finally someone who explains it in detail why you separate the neutral and ground!

    • @BenjaminSahlstrom
      @BenjaminSahlstrom  4 роки тому +6

      I'm sure there are even more reasons than what I explained here but this is a good start. Thanks for watching and for subscribing!

    • @flagmichael
      @flagmichael 4 роки тому +1

      @@BenjaminSahlstrom See my comment for the lightning protection aspects.

    • @08c6vette
      @08c6vette 4 роки тому

      @@BenjaminSahlstrom The most important reason for not bonding them is for lighting protection. If you have the neutral and ground buses bonded and theres a lightning strike and you don't have a good enough earth bond with your grounding grid you could potentially fry everything in your house, not to mention someone possibly getting a nasty shock. It's the same reason Utilities are required to drive two grounds at the pole on Delta systems, (where theres no system neutral), to separate the transformers lightning protection from the customers service, hoping to avoid sending a lightning shot into the customers home if the transformer takes a shot. This is also a possible reason for the remaining stray amps on your sub panel ground. If your sub panel's grounds have a better earth bond than your main panel's, you could be getting back feed from your main panel's neutral bus, back through the ground wire into your sub panel's ground bus. It can be a needle in a haystack though, as we get this call a couple times a week, where a telephone or a cabe tech won't hook up someones service because of stray amps on the customers ground.

  • @joncasamento5978
    @joncasamento5978 3 роки тому +5

    Unwanted ground current is probably shared ground current from the main panel due to a better/good ground in the subpanel. Think of a parallel path to ground.
    Good video, thanks for the well articulated description of the panel grounding issue.

    • @RZ-xl8un
      @RZ-xl8un 9 місяців тому

      agree, in other words, the N is not zero volt at main panel.

  • @sean8889
    @sean8889 4 роки тому +5

    great vid, watching in quarantine. We have a house energy monitor already (Efergy, it works ok) or I would buy the sense right away. Everybody reading, support Benjamin and buy a sense with his link. It's very cool to see when you turn on the heat, microwave, lights to see the power usage for the house. It helps you track down silly power losses and do things like upgrade to LEDs for frequently used lights and think about how power is used in your house. In our house we have a heating system that uses electric resistance heat (! so expensive) when the thermostat is more than 2 degree difference from target, so we learned to only bump up thermostat 1 degree at a time to prioritize heat pump use which is 3-4 times as efficient.

  • @need2zipit
    @need2zipit 2 роки тому +1

    I am not an electrician, but I had a 200 foot tower on the property with a sub panel. With every lightning event current from static electricity or lightning would travel back to the main panel through the neutral. After loosing thousands of dollars of equipment they isolated the ground all the way back to the service feed. Ensured no bonding between the 200 foot tower and out building 10 feet away that housed the sub panel. There ended up being no bonding between the service feed on the pole and all grounds had been Isolated all the way back to the service utility ground. That cured the problem but I never seen the licensed electrician test for amps like you demonstrated. Great informative content, thank you for sharing.

  • @randr10
    @randr10 4 роки тому +15

    It's possible that there is a bond between ground and neutral out at one of the boxes or in an appliance itself that's causing that current to leak through like that.

    • @edwinsGT8866
      @edwinsGT8866 4 роки тому +2

      Like a dryer with a 3 wire cord?

    • @daviskyl
      @daviskyl 4 роки тому

      Or at the furnace, if the ground and neutral connect somewhere...

    • @alanbenell2943
      @alanbenell2943 4 роки тому

      Or where the Neutral and EGC is still (properly) bonded back at your service panel beside the meter.

  • @michaelfakhraee6335
    @michaelfakhraee6335 4 роки тому +19

    Your test shows that in one of the equipment in the house there is a connection between neutral and ground wire, may be through the housing.

  • @curtislake753
    @curtislake753 4 роки тому +5

    Years ago I had to separate all my neutrals from my grounds and add another ground rod because I was getting a 5VAC shock when I touched a faucet or a ductwork while lying on the ground under the house. Came to find out that the NEC allows households to use 2 conductor with ground to 120/240 VAC appliances which is stupid. Consider this: as long as you're using 240 volts, there is no imbalance, such as dryers, ovens, etc. But as soon as you use the 120v portion of any multivolt device, you're using the bare ground as a conductor. Had to rewire those appliances with 3 conductor w/ ground in order to eliminate the stray voltage.

    • @ironman6944
      @ironman6944 4 роки тому

      I just recently and a discussion with my state inspector on this issue. I installed a new 200A MB panel and bonded. Then subfed the existing panel at 60 amps to feed 6 120v circuits and the range.. it was to save time and $ for my client because #1 they were to short to extend to new panel. #2 none of them had a grounding conductor. They will be replaced in future remodeling with 12/2 wg at that time. The range is a 8/2 wg...the first thing out of his mouth " you need to separate grounds from neutrals". But there are no grounds.."the range one". But it is a 4 wire range with neutral to ground wire

    • @ironman6944
      @ironman6944 4 роки тому +1

      Don't know what the f just happened, I cut my self short. I degress.. my point is if you bond the ground and neutral at the range that makes that wire a "neutral" with potential current. I lost the discussion, shut up and did what I was told

  • @tombaker2523
    @tombaker2523 2 роки тому +1

    Remember the ABC 123 rule what a bonding ground is for neutral imbalances and over voltages like Jim said start popping breakers till the bug shows itself . Don't forget a lot of companies wire their appliances and motors this way still old school fire and electricution, lightning protections. Great video keep doin a good job and keep reminding people no substitute for a professional electrician.

  • @IceHawk0000
    @IceHawk0000 3 роки тому +5

    If I had to venture a guess, I would say that you're probably picking up some small current from low-voltage transformers which are typically grounded to the cabinets that they're mounted in on their secondary common.
    Could also be induction from other devices drawing current

  • @junkmail4613
    @junkmail4613 4 роки тому +95

    12:27 first suggestion: Turn off all breakers except main, and look at "Ground current"
    If still ground current, turn off main. look for ground current.(could be source from other external source(adjacent system or other panel)) if no ground current, go back, turn on main, clamp on ground line, turn on each breaker, one at a time and watch for current, then turn back off and test next breaker until you find ground current source. troubleshoot breaker circuit with ground current source. Q.E.D. GoodLuck 20200319

    • @stoppernz229
      @stoppernz229 4 роки тому

      Current is returning to main panel via neutral wire, then back along earthwire to sub panel again then down gas line...If you're confused ask a drywaller hehehe.

  • @oscarhh359
    @oscarhh359 4 роки тому +15

    This current in the grounding inside of your house, is perhaps that your ground inside is better than in your neighborhood. So, perhaps one of your neighbors has his neutral broken, and your ground is improving or serving as his neutral.
    So, you could disconnect your ground, and one of your neighbors will probably notice voltage variations in his inner installations (the mess will be when his voltage in one leg increases too much)
    I follow you in El Salvador, Central America

  • @stringlarson1247
    @stringlarson1247 Рік тому

    I do a lot of 'side-work' on really old homes in Chicago. Everytime I open a main panel, it's a rats nest of wire - ground wires everywhere, whites hooked up to breakers, blacks to neutral bus, and green, red, blue wherever.
    I so appreciate seeing a panel that looks like the one you are working on here. I get a little choked up at the beauty.

  • @cdb830
    @cdb830 3 роки тому +5

    Good job! Note; there can also be leakage to ground finding a path through appliances or any connected equipment, i.e. the appliance grounding is doing it's job.

  • @charlesgardner7399
    @charlesgardner7399 4 роки тому +6

    Benjamin, very well done explanation. I've spent 30 years onbaord Army ships and familiar with home and shipboard circuits. Looking forward to more of your discoveries.

  • @mikesheehan474
    @mikesheehan474 2 роки тому +5

    Great video, great job explaining why to separate and what happens if they aren’t totally separate. Not sure what you have for other utilities in the house, but I have seen where you also get amperage on the neutral and ground from phone and cable aswell. About 10 years ago all the utilities started bonding everything together so if the electric company has an issue like a bad insulator for example it will bleed into phone and cable aswell and in some cases onto customer grounds depending on if customer ground is better than their system and cause issues. I have had to install neutral isolation boxes at some houses due to amperage on the ground about 4 amps even when power is completely shut off to the house all coming in on the cable.

  • @bravo3541
    @bravo3541 2 роки тому +1

    Finally understand the "why" to this bonding situation. Great job.

  • @sonyyoung1036
    @sonyyoung1036 4 роки тому +4

    Great videos. Can you explain why ground is bonded in main panel? That would create 2 paths for electricity to return in a circuit depending on which has least resistance. Either return through neutral or ground line.

    • @BenjaminSahlstrom
      @BenjaminSahlstrom  4 роки тому +1

      I have a video in the works on this topic actually!

    • @alexbabcha
      @alexbabcha 3 роки тому

      I feel like bonding jumper should be inside the meter box not in main panel. Logically it all makes that way.

  • @derekolson4168
    @derekolson4168 4 роки тому +7

    You're house has the nicest looking mechanical systems I have personally ever seen. Excellent craftsmanship.

  • @frankie21963
    @frankie21963 3 роки тому +28

    Dear Ben, love your explanation here! You do a wonderful job representing our great trade. I would say that the difference in potential between the ground and neutral would represent induction in appliances and harmonic distortion from the use of fluorescent lighting and certainly LED lighting. I am retired from working in the field, however, harmonic distortion should be on our radar as we see the use of electronics in the home. The sub-panel grounding is in my view very interesting. I have always understood that the NEC requires a separate ground not connected to the neutral bar simply because we need the main breaker feeding the subpanel to open as quickly as possible if there is a fault. Multiple paths to ground would provide a pathway for current to circulate through the house and injure people and potentially prevent the main breaker from opening.

    • @miguelac6872
      @miguelac6872 3 роки тому +3

      Question 1. Is there a dedicated, unique and special Grounding for Sensitive Electronic Equipment?
      2 Question.
      In the event of a lightning strike near my property is it recommended to unplug my electronic devices?
      3 Question. Why is there always a little (0.3 Amps) current flowing from the neutral bus bar (on the main panel) to the ground rod ?
      Does it mean that some of that current could leak out
      through the equipment grounding conductor form the main panel to the sup panel energizing the equipments conected to the EGC?
      I would appreciate it so much if you help me answering those 3 questions.

    • @amberjoynt7012
      @amberjoynt7012 3 роки тому +2

      correct, each builing /subpannel requires its own grounding rod(s)

    • @frankie21963
      @frankie21963 3 роки тому +1

      @@miguelac6872 Hi Miguel, I will try my best to answer your questions as I understand theory and interpret the NEC rules.
      #1. Isolated ground devices and wiring is used in commercial installations and healthcare facilities where critical equipment is in use.
      #2. Grounding electrode wiring is meant to help with transient voltage from lightning. That said, there are several devices available to help protect sensitive equipment from a surge of voltage. Stil, if you have something particularly sensitive and valuable, it's a good idea to unplug it.
      #3. Some current on the neutral bar can be seen in a normal circumstance. Electronic loads cause harmonic distortion and as a result causes a non-linear load in which the current and voltage becomes out of sync with the rate of hertz. The resulting out of sync value of voltage and current goes to the neutral and then back to the source of generation. If the neutral conductor remains intact all of the way to the source, all is good. We have to be aware of the amount "unbalanced" load on the neutral conductor and size it appropriately. With regard to your question about leaking current? Everything in an electrical service and panel is designed to be bonded and grounded to ensure that there is a effective ground fault current path to the source so that the over current device can open and prevent electrocution. Current takes the least path of resistance to the source. Please be sure to correct me if I am wrong about this, it's been a number of years since I thought about this information. I always found that mikeholt.com is a wonderful source of current NEC and theory information. Best

    • @CaseDadToo
      @CaseDadToo 2 роки тому +3

      @@frankie21963 I have to disagree with a statement you made. “Current takes the least path of resistance.” This is incorrect. Current takes all the paths, but will be highest on the path of the least resistance. That is the point of this discussion in the first place, and the thing that many seem to not be understanding. If there is a path available, even if that path is not the best/designed path, electric current will take it also, not instead of the designed path.

    • @frankie21963
      @frankie21963 2 роки тому +1

      @@CaseDadToo, I believe you're correct. However, the context of the NEC and protecting life and property, the goal is to avoid multiple pathways so that the main breaker has enough current to open.

  • @brettchatz2378
    @brettchatz2378 Рік тому

    Truly excellent! Well done. This was as clear as an instructional video from the Home Inspector coursework. Superb work. You have a natural talent.

  • @gnrfan713
    @gnrfan713 3 роки тому +3

    Just wondering what happens at the main panel. does some of the neutral load get carried by the ground? Or does it all go back on the neutral? Thanks for the video

  • @rforster76
    @rforster76 4 роки тому +5

    Some of the old Dryers and Ranges had a bonding jumper in them for the 3 to 4 wire change in plugs back in the 90's

  • @jrb_sland5066
    @jrb_sland5066 4 роки тому +6

    The water line to my house is 50 feet of 3/4" copper, and it makes a really good ground connection. My two 6 foot steel ground rods are installed to meet code, but I'll bet most ground currents use the water pipe when I have "events"....Maybe I'll try your measurement test someday. Thanks for the idea!

    • @beardedgaming1337
      @beardedgaming1337 3 роки тому

      my house grounds are on the black gas pipe, the galvanized water pipe and there are 7 or 8 different grounding points along the way.

    • @beardedgaming1337
      @beardedgaming1337 3 роки тому

      @jkforever10 there's a ground coming from the dryer as well to the waterline by the sink basin. I was testing power wiring the other day and found about 60 V on the bathroom Plumbing pipes, I haven't checked in the basement yet.
      My garage also didn't have a neutral, it had a hot and a very small grounding wire

  • @soundman1402
    @soundman1402 3 роки тому +1

    Can I just say, the wiring in your house panel is beautiful!

  • @melmaddawgduran3419
    @melmaddawgduran3419 3 роки тому +3

    Plain and simple to the point. This makes it easy to explain to homeowners. Great video.
    THANKS!

  • @johnbarham7718
    @johnbarham7718 4 роки тому +5

    A high resistant connection on one of the steel /copper items in the system. As stated below, isolate each circuit in turn, when the current falls to 0A or very nearly, bearing in mind repeatabilty, that is likely to be the culprit circuit.

  • @johnhaller5851
    @johnhaller5851 4 роки тому +7

    One other problem is a ground loop. Your house has a ground loop since your gas line provides another ground. What this does is make a large loop antenna converting magnetic fields into electrical current. This will make your ground noisy, with varying voltage. Back in the day, when computers are big enough to require multiple racks, and when signal ground was tied to earth ground, these grounds loops could cause enough voltage on signal ground to make the signal unreliable. Now, we use Ethernet for this, and it has differential signals and isolation transformers, so it's no longer a problem. Back in the '80s, we had lots of problems with this, and had to use isolated ground outlets (orange) to avoid the ground loops caused by extra ground paths through conduit and metal raceways.

    • @coypatton3160
      @coypatton3160 4 роки тому +1

      John Haller there are areas where isolated grounds are still used.
      Unfortunately, I have seen times when this isolation is compromised. One biggie is extremely wet conditions.

    • @flagmichael
      @flagmichael 4 роки тому +2

      The modern mantra is "single point ground." Ground loops are hunted down and exterminated. One of the mountaintop microwave sites I had to "de-lightning" had aluminum cable tray that was suspended from the metal ceiling by all-thread. Putting a 500 KHz signal between the tower and the service entrance ground (the main lightning path), the entire tray system was hot. Lightning strikes were inductively coupled into all the wiring in the tray. We had to insulate the hangers and provide a bond to the ground bus to prevent every lightning strike from knocking nearly the whole site out.

    • @mrmotofy
      @mrmotofy 4 роки тому

      John Haller So would there be a ground loop created with an old water supply line and ground rods connected to ground bar?

    • @johnhaller5851
      @johnhaller5851 4 роки тому

      @@mrmotofy The key is single point ground reference. If the water line ground is your second ground, and it's wired to your single point ground, it's not a loop. But, it should be as close as possible to where the copper pipe enters the ground. Copper plumbing has its own set of issues with ground loops, as generally every faucet will connect hot and cold pipes, and you don't want use the middle of one of those loops as your ground reference. Metal HVAC ducting can be another source of ground loops, as can suspended ceiling supports. In the building I first referenced, the ground point was established by welding the ground to the steel columns. There may still have been ground loops in the building, but within that particular large room, it all had one ground reference. That room had several 400A 208V 3-phase circuits feeding it.

  • @Chris-eh8mi
    @Chris-eh8mi 3 роки тому +1

    It's amazing how often I used to have to correct neutral-ground connections on sub-panel submissions from major vendors. Good vid.

  • @fllev4121
    @fllev4121 4 роки тому +82

    The "leakage" through the grounded conductors in the system is likely capacitive and inductive coupling of energy between the power conductors and the ground wire going back to the main panel; especially those housed in the same raceway or conduit.

    • @donmclean1220
      @donmclean1220 4 роки тому +6

      I agree, probably inductive coupling of long runs of parallel wires.

    • @thatclintguy
      @thatclintguy 4 роки тому +6

      easy to test - hook it up to an energy meter and measure the power factor to confirm!

    • @flagmichael
      @flagmichael 4 роки тому +3

      The induction should be equal for the neutral and phase wires. The source lies elsewhere.

    • @fllev4121
      @fllev4121 4 роки тому +3

      @@flagmichael "Should". The variations in "conductor" placement , size and lengths plus current imbalance in the split phases will always cause displacement and inductive currents to flow through the grounding conductors.

    • @ajosmer
      @ajosmer 4 роки тому +1

      @@fllev4121 1/4 amp of variation?

  • @tsadkiel2008
    @tsadkiel2008 4 роки тому +168

    BTW whom ever wired that panel; deserves a medal because that is electricity sexy at its finest!

    • @riccardoz2953
      @riccardoz2953 4 роки тому +4

      that's how is supposed to be a panel wired correctly dude ....

    • @curtisdilas1049
      @curtisdilas1049 4 роки тому +29

      I agree they did a good job visually. But those tie wraps bundling the wires are not a good idea. Bundling those wires causes heat. Any high load panel will literally cause the coating to harden. Later in it's lifetime that coating can be easily broken, flake and give spots for electricity to escape. I know some will have a difference of opinion.

    • @charliezxi
      @charliezxi 4 роки тому +5

      Unfortunately, they used pvc pipe to feed the panel, which is only allowed by the NEC if it is underground. Also, the exposed romex tacked on the wall to the right is a no-no.

    • @tsadkiel2008
      @tsadkiel2008 4 роки тому +12

      @@charliezxi "Unfortunately, they used pvc pipe to feed the panel, which is only allowed by the NEC if it is underground. " Not sure what area you live in; but pvc schedule 40 is rated for use as a conduit for electrical conductors.

    • @charliezxi
      @charliezxi 4 роки тому +2

      @@tsadkiel2008 PVC Schedule 40 is rated for use as a conduit, however "where not subject to physical damage." Running perpendicular and exposed to the backside of a door is subject to physical damage.

  • @joshuawhitney9414
    @joshuawhitney9414 3 роки тому +50

    I subscribed because of how amazing you did at explaining this.

  • @kevinhedrick6354
    @kevinhedrick6354 2 роки тому

    Excellent description, I'm learning a lot about AC electric from you. I'm an auto mechanic by trade.
    I do want to let you know, when you use your Amp clamp, try not to allow it to snap closed as you are causing damage to your tool.

  • @charliebub2627
    @charliebub2627 4 роки тому +6

    Great video!
    Regarding the source of the current in the ground line mentioned at 12:55. Power line line filters like those used on computers have a capacitor from hot line to ground. This may account for what you measure. Cheers

  • @JasonDrennen
    @JasonDrennen 4 роки тому +20

    I'm glad you're teaching people. They need to learn this stuff. I used to do rough ins in Columbus Ohio. So other words I had electrical background. Well when I had my place put in I just went ahead and let an electrician hook everything up. Everything went fine for about eight years. Then when I build a CNC machine things started acting crazy. For some reason my cable and internet line kept getting shorted out AKA cooked. Wasn't making any sense it happened like three times. So I would always go to the box test everything everything would show up good. Well where I was at they would lock the meter box. After replacing the cable lines about three times I finally called The Electric Company to come take their lock off my meter. Obviously I could have done it but you get in trouble for it where I'm at. Once they did I can find the problem very quickly. They had my neutral wire slid up in there but they never tighten the lug. So basically for years my house is running fine off just the wire pushing against the lug. When I would kick on that CNC spindle it would pull all the power through the ground. So it was using any ground it could find. Including the grounding wire for my cable TV. So yeah it's very important to separate your neutral and ground. Makes me wonder how much equipment I lost due to this.

    • @donaldshimkus539
      @donaldshimkus539 4 роки тому +1

      Wow! I recently had to change out a meter socket that had a similar problem. Whoever worked on it never tightened one of the hots coming in. It was fine for years, but when the cold hit this winter, I guess that was too much for the loose connection. Melted some stuff big time.

    • @angelmarauder5647
      @angelmarauder5647 4 роки тому

      Wow!

    • @jimdavis6833
      @jimdavis6833 4 роки тому

      Im most areas, if you call the power company and tell them you cut the lock off and why, they will just replace it next time they check it and no big deal. I've had to do that as couple of times to remove the meter so I could upgrade the primary service box to a higher capacity. No way to change it without removing the meter.

    • @jimdavis6833
      @jimdavis6833 4 роки тому

      @@donaldshimkus539 The meter "socket" as well as the meter and lines from the pole all belong to your power company. You should have just called them. With your situation, they would have expedited it.

    • @donaldshimkus539
      @donaldshimkus539 4 роки тому

      @@jimdavis6833 in N. Carolina, as in most states, the meter socket is the homeowners property. Only things the power company owns is the meter and the line to the pole.

  • @eie_for_you
    @eie_for_you 4 роки тому +6

    Leakage current through devices plugged into the system. I used to work as a biomedical technician and we had to test everything for leakage current from line to ground and then swap line and neutral and test again for leakage current. Your average consumer device has more tolerance for leakage current to ground than medical devices.

  • @MGPackers
    @MGPackers Рік тому

    You did a very thorough job explaining why the neutral and ground are separated in sub panels. Thanks!!

  • @davez4194
    @davez4194 4 роки тому +355

    When I was a youngster I would drink water from the metal bathtub faucet while sitting in the tub...yeah weird i know...but...I always felt an electrical tingling when I did that. I told my dad and he said what the hell was i drinking water out of the faucet for anyway...and he said I was imagining it....well I kept at him and finally he put a volt meter between the faucet and the drain...and guess what...it showed voltage....here our old house had the panel box grounded to the water pipe from the well...he drove a rod into the ground and grounded that way and it fixed it...but he still thought it was weird that i drank from the faucet while I soaked in the tub...hey i was 10 years old...kids do weird shit.

    • @larryreno8293
      @larryreno8293 4 роки тому +11

      Dave Z I jump into the water at a marina grabbed a pipe I thought was a water line.... it wasn’t, just a poorly grounded conduit.⚡️⚡️⚡️ it hurt

    • @johnsiders7819
      @johnsiders7819 4 роки тому +7

      If my water heater blows a element if I touch the pipe on top of it and hand on flowing water at a facet I get bit ! Discovered this past February I BTW GE water heaters are made in Mexico junk ! It eats a lower element every 2of 3 months and it’s not full of sediment! Done this since I installed it !

    • @LVL1Yo-YoGuy
      @LVL1Yo-YoGuy 4 роки тому +28

      I'm a electrician 20 years in trade and I remember 7 years old to 9 i be sticking my dad's old car and truck keys in the plugs play driving a car with my little brother sitting behind me (them two prong style) I liked the little explosion sound it made like when you start and old hot rod, anyways I always have black stuff on my hands and twice on my face and the apartment manager banging at our door saying half of the complex is out of power again I'm calling your dad now and of course he use his belt on my back but for some reason it didn't stop me.

    • @davez4194
      @davez4194 4 роки тому +16

      @@LVL1Yo-YoGuy and you lived to tell about it! Wow!

    • @jonfairbank7626
      @jonfairbank7626 4 роки тому +8

      @@johnsiders7819 Do you have a sacrificial anode screwed done in to the tank? They all have them but might need to be replaced on an older unit. (PS they are all probably made there nowadays!)

  • @AerialPhotogGuy
    @AerialPhotogGuy 2 роки тому +4

    The small amount of current flowing through the ground wire after disconnecting the jumper wire from neutral to ground is coming from a ground loop between the house and the main panel outside, if you install a ground rod at the source and a ground rod at the sub panel, you create a ground loop.
    Installing a ground rod at each location is OK if the distance between the two panels is far enough apart or if the ground itself is bad at conducting electricity. Sandrock is not a good soil for ground rods, I've had to install as many as 4 ground rods in sandrock, I had to get the power company to measure the resistance with one of their earth ground testers, I didn't want to spend $3,000.00 for an earth ground tester.
    Thanks!

    • @excalidude
      @excalidude 2 роки тому +1

      Thanks for posting that. That's what I have been told by our local building inspector. My mobile home is about 175 feet from the MDP and I am told a second ground is not only unnecessary but not to code.
      Other than that this is a great video and fills in a lot of knowledge about how a 4-wire system works.

    • @stevem1081
      @stevem1081 2 роки тому +1

      Also found out that having multiple locations of ground rods greatly increases equipment to be destroyed when lightning strikes nearby. The ground loop will create a difference in potential, whereas in a single ground point, all the voltage on the equipment rises together and survives.

    • @AerialPhotogGuy
      @AerialPhotogGuy 2 роки тому

      @@stevem1081
      Spot on!
      I've lost 2 computer's due to ground loops, both instances were from lighting strikes.

  • @mmccrack3n
    @mmccrack3n 4 роки тому +9

    It is one thing to know, and another to be able to communicate that knowledge. Thanks

  • @olson.pamela
    @olson.pamela Місяць тому

    I was wondering where you lived given the scenery I see in your videos. Minnesota! That’s where I live too! My dad told me all the kids in MN are smart so don’t think I’m special. Thanks dad. But this kid IS special. Thanks for fantastic teaching!

  • @MrSuperchargeron
    @MrSuperchargeron 4 роки тому +25

    Can you leave your meter on the ground and shut off one breaker at a time till you figure out which circuit is still going back to ground? Then examine the equipment on that circuit to figure out why you are still getting a little amperage back on the ground.. Bad neutral at the bussbar or at the equipment?

    • @textsmsmaster9884
      @textsmsmaster9884 4 роки тому +6

      @MrSuperChargeron .. You ask a great question for a could be very time consuming troubleshooting process .. your solution is at least pointed in the right direction .. Potential measured on the Neutral .. you think it would be isolated by breaking the hot thru the bus at the Breaker .. what if it's some form of feedback thru the neutral and/or ground off one or more branch circuits? .. to actually isolate that branch circuit .. Disconnect its related Neutral and Ground in the Sub-Panel .. but, before you go doing each branch circuit ..since you do have each panel with their own 5/8" Grounding Rods .. disconnect the sub panel ground at the main panel .. remember, like all bonding, there is an inherit potential from natural ground including copper and galvanized pipe picked up thru cold water and gas lines assuming you've jumped across the non dielectric gas union .. and if you have to get into the weeds .. there's always the headaches of tracing back and disconnecting joints in junction boxes or outlet boxes to fan motors, sump pumps, refrigerator compressors, electric hot water elements, even GFCI's too .. check 3 way switches .. some of these rope pullers don't understand 4 wire travelers and companions .. and even loose neutrals or uncapped taped up neutral joints .. and God forbid in line joints covered inside walls .. enjoy

    • @jamiephillips887
      @jamiephillips887 4 роки тому +2

      MrSuperchargeron there could be a motor winding going bad or, similar electronic component with a faint short. Eliminate your circuits one by one until you determine which circuit is shorting. That will get you very close to the source.

    • @SteveWhiteDallas
      @SteveWhiteDallas 4 роки тому +1

      Any circuit or all circuits are likely to result in a load on the ground wire (EGC) because when you bond a subpanel, the EGC is no longer a ground wire. Since the main panel is bonded, bonding the subpanel creates a parallel neutral (neutral & EGC.) That creates a whole new hazard since the parallel neutrals are not the same size. The smaller conductor could end up carrying too much current and grounded appliances will be connected to the neutral instead of ground. If for any reason the neutral supplying the subpanel became disconnected, the grounded appliance housings would become a hot end of an open circuit until someone touched any grounded item, thereby [inefficiently and inadequately] closing all 120 volt circuits through their body, running the current to ground with no connection back to the center tap on the transformer.

  • @macy1066
    @macy1066 4 роки тому +6

    I have no idea why UA-cam suggested this or why I'll ever use it in my life but I have to say it's fascinating. Thanks.

  • @realcoolphil
    @realcoolphil 4 роки тому +27

    The power still going back on the ground may be coming from the electric water heater if you have one. I'm glad you did not try to show us what would happen if the neutral was unhooked.

    • @Mike_5
      @Mike_5 4 роки тому +2

      Floating Neutrals are fun!

    • @jamesganglinteriorrestorat9939
      @jamesganglinteriorrestorat9939 4 роки тому +5

      I'm a retired electrcal inspector in Minesota and this the best explanations of this problem I have ever seen. If I were still working I would refer people to this video when this question comes up. It is avery common question asked of inspectos. Thank You very much.

    • @gbnomore3918
      @gbnomore3918 4 роки тому +1

      Prob'ly woulda been an Explosive Video.

    • @kidt3068
      @kidt3068 4 роки тому +2

      Maybe he should grab the open neutral to see what happens.

    • @gbnomore3918
      @gbnomore3918 4 роки тому +1

      @@kidt3068 we always want to avoid pain and/death. Nonetheless always good have the warnings out there.

  • @2016MMXVI
    @2016MMXVI 2 роки тому

    Great video. I have never seen a practical explanation so well illustrated. Many dryers or cooking units come equipped with a bonding jumper from the neutral to the ground for use with older electrical systems that didn't bring a neutral to the receptacle. The NEC allows for this in article 250.140 Exception. Many times you will find this bonding jumper not removed as it should be for newer installations which then bonds the neutral and equipment ground.

  • @terryeffinp
    @terryeffinp 4 роки тому +296

    Turn off breakers one at a time to isolate where your ground leakage is coming from.

    • @bobb7494
      @bobb7494 4 роки тому +6

      won't work that way

    • @zachdesrosiers
      @zachdesrosiers 4 роки тому +1

      @@bobb7494 Why not?

    • @hessammousavi500
      @hessammousavi500 4 роки тому +4

      yes you are right. the easiest way to test

    • @mikekokomomike
      @mikekokomomike 4 роки тому +3

      Leaking from a white wire and a ground wire making a high resistance connection in an appliance or junction bix

    • @mikekokomomike
      @mikekokomomike 4 роки тому +2

      Turning off a breaker won't identify it

  • @rodneycaupp5962
    @rodneycaupp5962 4 роки тому +33

    That's a subscribe, and a like. I once had a city inspector tell me he had never seen a prettier ground wire job. I had to do it to sell our house. Well let me tell you, I have NEVER seen a prettier power panel. I'm an old Navy electrician. Best schooling in the world. NICE WORK, and very nice video. BTW, that residual power in your ground, could be aliens. They've been sucking power from our systems since the Pyramids.

    • @daddio7249
      @daddio7249 4 роки тому +2

      I guess you never saw a panel wired by a ballistic missile technician. Not me, a guy I worked with after he got a civilian job. Picky, picky, picky.

    • @rcpmac
      @rcpmac 4 роки тому +3

      Rodney Caupp I work for a utility. The biggest conductor in a system (grid level) is earth. The biggest insulator is air. I’m not sure that tightly binding conductors together is advisable for a number of reasons. My panel was wired by a professional and looks like a 3D printed circuit board. Parallel runs, 90deg turns and space between the conductors.

    • @lawrenceflowers9499
      @lawrenceflowers9499 3 роки тому

      I, and a friend as well, have seen their crafts over the local power plant's main output towers. But once the enhanced awareness had been metabolized and the morning light and fog had taken over, they were no longer visible. And it was just another thing to speak of only to someone who might mention it first, such as yourself. Better to be silent and have them thionk you are insane, than speak and remove all doubt....,.

  • @TheRayDog
    @TheRayDog 3 роки тому +2

    Your small current on the EGC: induced as others mentioned, but also ground and neutral are still connected at the main panel. Ground from your subpanel still offers a path.

  • @jbsimmons54
    @jbsimmons54 Рік тому

    Thanks. This is a subject beyond the comprehension of most DIYs. They didn't even teach this when I was going for my EE degree back in 1972 as it wasn't an issue. Grounding was something new and not all the intricacies were known.