Previously MISDIAGNOSED | HVAC | Replacing a leaking CARRIER coil and TXV
In today’s video, I went out to a job that the customer was told that the Schraders were leaking, but previously called the company back to let them know still was not working. Then the customer was told that the line set was leaking. So they called us out for a second opinion, and I was able to locate the leak at the evaporator coil.
While ordering the coil, I was looking to have a preassembled TXV and drain pan but apparently carrier doesn’t do things that way. So I returned for the system that was under warranty to replace the evaporator coil as well as the TXV.
 Hope y’all enjoyed the video if you could smash that 👍 button and SUBSCRIBE!! Appreciate yall 🫡
#bluecollar #hvac #skilledtrades #hvactech #hvactechnician #acreapir #hvacvlog #tools #dayinthelife #hardwork #workhard #tradelife
SUPPORT THE CHANNEL 👇👇👇
PAYPAL : @hvacwithkrauss
AMAZON LINK 👇👇👇
HVAC KNIGHTS LIVE PODCAT | SUBSCRIBE
youtube.com/@HVACKnights?si=bq2zy572xw5EprIf
SOCKS I ROCK
Code : KRAUSS
www.camelcitymill.com/KRAUSS
Questions or business inquiries:
hvacwithkrauss@gmail.com
Переглядів: 2 187

Відео

How to find Refrigerant leaks | HVAC | If it’s LENNOX it LEAKS
Переглядів 1,3 тис.21 день тому
And today’s video I filmed this back in beginning of August during peak season. Customer had notated that the system was not cooling off during the peak of the afternoon and would start to get warm. Found out right away that it was a Lennox unit, which was a direct Indicator that there was a leak in the refrigerant system. Because Lennox is known for their shitty coils. So I started by checking...
Drain line causes ISSUES | HVAC | water leaking onto ceiling
Переглядів 2,2 тис.Місяць тому
In today’s video, I go out to a call in which the customer noted. There was water leaking through the attic ceiling. Thought it was just that there was a backed up drain line, which is what it was. But due to the neglect of the system and the installation The drain line was not sloped properly and all the bacteria was building up inside of the drain pan not allowing the drain primary float swit...
I JUST GUESSED | HVAC | small van upgrade | Lennox blower motor
Переглядів 1,8 тис.2 місяці тому
In this video, I go on a service call where the customer noticed that the upstairs unit was running hot. Want arrival found that the suction side was freezing over. Suspected either a refrigerant leak being that it was a Lennox system or a bad ECM motor. Once upstairs found that the blower motor was not running. It did appear to be receiving the call. Although I wasn’t able to determine if it w...
MAJOR ISSUE found on MAINTENANCE | HVAC | Carrier evaporator coil replacement
Переглядів 3,1 тис.2 місяці тому
In today’s video, I returned to a call in which I went out to do a maintenance. During the maintenance, I asked my general questions about the systems performance, and the homeowner indicated that it wasn’t keeping up to temp during the afternoons systems pressures and them to be lower than normal for the ambient temperature. Performed a leak directly at the evaporator coil as that’s where I te...
I Blew THE POWER to the building | HVAC | Reviving 23 year old neglected system
Переглядів 2,2 тис.2 місяці тому
In today’s video, I go to a commercial space where the temperature inside was reading 84. The customer would reset the breakers and the system would tend to work. The initial inspection of the unit found that the coil was dirty and the head pressure was extremely high. Needed water access, but there was none on the premises so had to run home and pick up my portable M2 sprayer. Once I return to...
CONDENSER WONT START | HVAC | Carrier unit DOA due to REPTILE DAMAGE
Переглядів 1,6 тис.2 місяці тому
In today’s video, I go out to a call where the customer is letting us know that the condenser won’t start. Upon initial inspection, checked all the typical fail points, such as float, switch, and capacitor. Check the voltage coming into the board, but no voltage was present leaving the board and sending voltage back to the Condenser contactor. Was rained out and couldn’t finish the video and sh...
IT COULD BE WORSE| HVAC | blower motor PULL and CLEAN
Переглядів 1,5 тис.2 місяці тому
In today’s video, I returned to a call that I was previously on where I replaced the capacitor. Upon check in the capacitor I checked over the rest of the system to see if there’s any more issues to keep the unit running as long as possible. Came across the blower wheel, which was extremely dirty. By cleaning the blower wheel it frees up the weight that’s running on the motor. Also helps the ai...
CUSTOMER told PART NO LONGER MADE | HVAC | 2nd opinion to the “LARGE COMPANY”
Переглядів 3,3 тис.2 місяці тому
In today’s video I returned back to a job from a previous video in which I went out for a second opinion. The customer was told that the part is no longer made, it’s very expensive, and the unit was out of warranty. Needless to say, none of those issues were true and they make aftermarket components for this system if that was the case and just about any other system out there aside from commun...
MASSIVE BUSINESS ISSUE | HVAC | Day In The Life | maintenance, ECM failure, drain line
Переглядів 2,3 тис.2 місяці тому
And today’s video I discussed the issues we’ve been having with our tracking numbers, which has hindered the business quite a bit. Also perform a maintenance, nothing crazy. I go to a service call in which I don’t show anything in terms of what was happening, but I did film a video so stay tuned for that. And went to a clogged drain line with a failed float switch that was causing her Florida b...
AC won’t SHUT OFF | HVAC | Failed Module carrier x-13 | motor replacement
Переглядів 1,7 тис.3 місяці тому
In today’s video, customer had called and let us know that the system would nonstop run so inside and initially just checked the condenser found all the operations on the carrier system to be normal. Went back inside disconnected to 24 V from the ECM X 13 blower module. And the motor would continue to run. Ran to the nearest supply house system was under warranty returned and replace the motor ...
WRONG DIAGNOSTIC causes BIG problems | HVAC | failed Rheem control board
Переглядів 4 тис.3 місяці тому
In today’s video, we have ourselves a no cool call. No matter what the customer did with the thermostat the system would not operate. My initial thoughts were right to the thermostat, that it was the issue because once I jumped it out from the control board in the air handler (instead of jumping it out at the thermostat), I would’ve known that. It was not my initial thought. So after diagnosing...
Just make it WORK | HVAC | Rain, HAWKS and a capacitor
Переглядів 2,6 тис.4 місяці тому
In today’s video, I was running the last call of the day. On arrival it was pouring down rain. Unable to check the size of the capacitor for the unit. Quickly crossed referenced the data plate after taking a screenshot from the video. Found the unit was the 45 micro capacitor. Scramble to find one inside the truck. By the time I was able to locate one the rain it stopped, swapped the capacitor ...
This was NASTY | HVAC | BACKED up drain line, and BYPASSED disconnect
Переглядів 2,1 тис.4 місяці тому
In today’s video, there is a property management company that had called about in water issue that was around the air handler. Pretty common thought was that it would be the drain line which it was. The float switch, but not engaging properly to turn off the system. Cleared the drain line using the gall gun with back pressure. And the amount of bacteria that came out was disgusting. Trying to i...
It DOESNT always go as planned | HVAC | repairs, estimates and follow ups
Переглядів 4,1 тис.4 місяці тому
In today’s video, you’ll find a repair that went wrong on something pretty simple. Just part of the game we play when we go to work every day. If I would’ve just taken the proper precautions, would’ve been good. Ended up trying to replace the low pressure switched, ended up just bypassing it for now to get the system running. After that call went to an estimate. Customer noted. They really didn...
There just ain’t NO WAY | HVAC | Amana heat pump low on refrigerant
Переглядів 7 тис.4 місяці тому
There just ain’t NO WAY | HVAC | Amana heat pump low on refrigerant
What would YOU DO | HVAC | Vanity VS Sanity, capacitor swap
Переглядів 3,2 тис.5 місяців тому
What would YOU DO | HVAC | Vanity VS Sanity, capacitor swap
Tree trimmer BLEW UP the AC | HVAC | inspection turns to change out
Переглядів 2,6 тис.5 місяців тому
Tree trimmer BLEW UP the AC | HVAC | inspection turns to change out
REPAIR or REPLACE aging system| HVAC | Parallel Wiring Capacitors
Переглядів 2,4 тис.5 місяців тому
REPAIR or REPLACE aging system| HVAC | Parallel Wiring Capacitors
MY MOST common HVAC service call | evap swap and DRAINS
Переглядів 3,7 тис.5 місяців тому
MY MOST common HVAC service call | evap swap and DRAINS
Running out of GAS | HVAC | 2 stage seer2 heat pump “COMPLETE” install
Переглядів 2,3 тис.6 місяців тому
Running out of GAS | HVAC | 2 stage seer2 heat pump “COMPLETE” install
Low Voltage Short | HVAC | the NEW (mini)van
Переглядів 8 тис.6 місяців тому
Low Voltage Short | HVAC | the NEW (mini)van
NEW Klein METRIC & SAE RATCHETING combo wrench set | 69408MG and 69408G
Переглядів 13 тис.6 місяців тому
NEW Klein METRIC & SAE RATCHETING combo wrench set | 69408MG and 69408G
Failure to COMMUNICATE | HVAC | Ruud 20 seer communicating heat pump blower motor replacement
Переглядів 2,2 тис.7 місяців тому
Failure to COMMUNICATE | HVAC | Ruud 20 seer communicating heat pump blower motor replacement
The CUSTOMER made the RIGHT choice | HVAC | OEM carrier condenser motor and fan blade replacement
Переглядів 8 тис.7 місяців тому
The CUSTOMER made the RIGHT choice | HVAC | OEM carrier condenser motor and fan blade replacement
Customer LOST FAITH | HVAC | Failed Ruud variable speed Compressor
Переглядів 11 тис.7 місяців тому
Customer LOST FAITH | HVAC | Failed Ruud variable speed Compressor
FAILED ZoomLock PUSH FITTING | the Risk WAS NOT worth it | HVAC Tech
Переглядів 6 тис.8 місяців тому
FAILED ZoomLock PUSH FITTING | the Risk WAS NOT worth it | HVAC Tech
NOW it Begins | HVAC | Getting the van wrapped and leaking Goodman evap
Переглядів 4,4 тис.8 місяців тому
NOW it Begins | HVAC | Getting the van wrapped and leaking Goodman evap
FREE Veto Pro Pac SB-LD | SPRING PROMO | Loadout
Переглядів 18 тис.8 місяців тому
FREE Veto Pro Pac SB-LD | SPRING PROMO | Loadout
Running an HVAC Business | HVAC | Big things are Coming
Переглядів 9 тис.9 місяців тому
Running an HVAC Business | HVAC | Big things are Coming

КОМЕНТАРІ

  • @AIRCONDITIONINGSCHOOLING
    @AIRCONDITIONINGSCHOOLING День тому

    Great video

  • @DavidRichardson-k9h
    @DavidRichardson-k9h 3 дні тому

    how long to these dampers usually last????

    • @KoolinwithKrauss
      @KoolinwithKrauss 2 дні тому

      I’ve seen them last multiple years no issues and I’ve seen them fail within a year on new construction homes

  • @Ronnie-f1v
    @Ronnie-f1v 9 днів тому

    Yada yada dude

  • @ibsanverde2243
    @ibsanverde2243 13 днів тому

    Lmao 😂

  • @biggysmallz5644
    @biggysmallz5644 13 днів тому

    What part of Florida do you live in? I’m currently doing hvac in Ohio and thinking about moving to Naples Florida to continue doing it but I need to know how bearable the heat is during the summer.

    • @KoolinwithKrauss
      @KoolinwithKrauss 13 днів тому

      I’m in central, west of orlando about 75 miles in from the gulf. The summers suck for sure. Just expect 90+ degrees and probably 100% humidity morning-day-night. I’m originally from Maryland and the summers were about the same, only difference is when the sun goes down there’s a break up there. But it can be brutal but it’s great. Depends how well you are with the heat now.

  • @Dustin2112
    @Dustin2112 16 днів тому

    Impact rated steel is SOFTER than chrome vanadium steel. Everybody thinks its the other way around but the forces at play with impact guns tend to break harder steels. They make them more pliable in order to resist breaking. There is an old saying, "which is stronger the oak or bamboo?".

  • @Sunrise_HVAC
    @Sunrise_HVAC 17 днів тому

    That’s why there are a lot of pistons in some of the older units. People get lazy and don’t install them and leave piston in place.

    • @KoolinwithKrauss
      @KoolinwithKrauss 16 днів тому

      Very true! I’ve seen a lot of techs just remove the txv all together

  • @cjfisher9572
    @cjfisher9572 17 днів тому

    Which should i buy old version or new blackout version because theres about £60 difference. Is it worth the extra £60 for blackout ?

    • @KoolinwithKrauss
      @KoolinwithKrauss 17 днів тому

      I love the blackout more then the OG, the pivoting handle and the VSwap is a game changer imo 👍

    • @cjfisher9572
      @cjfisher9572 16 днів тому

      ​@@KoolinwithKrauss if you dint use vswap would you still get black out or og ?

  • @Rhodesrepairllc
    @Rhodesrepairllc 17 днів тому

    250 to 350. I try not to get close to the 450 because it will mess up the plug and leak eventually the weakest point of the whole system.

    • @KoolinwithKrauss
      @KoolinwithKrauss 17 днів тому

      Solid point!! I don’t want to risk that either that’s why I like to keep it low, unless you just can’t find that bastard 😆

  • @HvacHack90
    @HvacHack90 18 днів тому

    I pressure test both at 250

  • @DanO181919
    @DanO181919 18 днів тому

    Krauss in the house!! Love the videos. Low side pressure is what I go with.

  • @helmsajr
    @helmsajr 18 днів тому

    Hey Jake between Lennox and Carrier Evp. coils they are keeping you busy. lol Great video.

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      You ain’t lying 😅 but I will say the majority of new build within the past 5-10 years is Lennox and carrier so I’ll give them … SOME benefit of the doubt, but damn 🤣 😆

  • @Eddy63
    @Eddy63 18 днів тому

    Nice job ... Thx

  • @JakePorterHVAC
    @JakePorterHVAC 18 днів тому

    Good to see a bulkhead in the van protecting the headski. Thanks for the video. Get healthy and stay safe out there.

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      Plans to seal it more, that’s just some scrap wood, I’ll get a nice partition eventually 😆 thanks brother good to hear from ya!!

    • @JakePorterHVAC
      @JakePorterHVAC 17 днів тому

      @@KoolinwithKrauss Scrap wood does the job. Do what you can when you can.

  • @HVACGUY
    @HVACGUY 18 днів тому

    Love taking the service valve caps off and finding leak lock

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      @@HVACGUY see that shit?! 🤣 after I freed it up tried to use my hands to get it undone, but NOPE 🤦‍♂️

  • @AaronPowellvox
    @AaronPowellvox 18 днів тому

    I usually go on the low side of the pressure to test it. I have had situation where the original installer burned the valves and nitrogen leaked back into the system. That was a rough one to figure out. I had to recover everything and then pressure test with the valves open.

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      Whoaaaa that’s a good point, especially when you encounter something like that, and then it’s always in the back of your mind!! Good call

    • @topher8634
      @topher8634 17 днів тому

      I ruined the charge in a new Goodman system like that once. Nitrogen pressure kept dropping, turned out the low side king valve wasn't completely closed from the factory, allowing the pressure to overcome the factory holding charge. Had to recover and recharge. Ever since then, I will just pressurize to 150 on a system with a refrigerant holding charge. And I make sure I can't close the valve any.

  • @AaronPowellvox
    @AaronPowellvox 18 днів тому

    That is so stupid that they wouldn’t just either braze that in or make it a 1/4” port connection with a flare.

  • @OnusBones
    @OnusBones 18 днів тому

    Would you ever replace a coil and not replace the TXV, if only due to possible contamination? You'd think Carrier would already have it nicely attached...

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      It would be fantastic if it was preassembled. But only way would be in it’s out of warranty and the cost maybe, can always just build it into the cost. But sometimes it’s that hundred or so that makes a difference

  • @nhfdtb
    @nhfdtb 18 днів тому

    Talk junk about Lennox, but it comes with the TXV and drain pan attached. Unlike Trane and Carrier.

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      Yup but hell Lennox has to provide all that as often as they leak 🤣 their only saving grace is

    • @dumptrks
      @dumptrks 18 днів тому

      @@nhfdtb Lennox is way superior to Carrier

    • @madeinusa1576
      @madeinusa1576 18 днів тому

      @@dumptrksyour high

    • @Kilcrops1985
      @Kilcrops1985 18 днів тому

      Trane also comes with pre installed txv and pan, it's been like that for the past year or so. At least on the TEM6 air handlers

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      @@dumptrks boooooo 😆

  • @noahbaggett9037
    @noahbaggett9037 18 днів тому

    Oh and I hate those carrier coils it seems like they leak and then are way more difficult to swap . Love seeing the good ol DA sticker in the beginning of the vid 😂

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      Bro it’s a pain a the arse!!! And you have to buy each piece individually if you want it nice and easy 🤦‍♂️ That’s up there in Heathrow my guy 🫡 yall all up in there, right down the road from Mr del airs estate

    • @noahbaggett9037
      @noahbaggett9037 18 днів тому

      @@KoolinwithKrauss that house is unbelievable. His wife still lives there after bob died . I’m one of the only techs allowed to maintain those systems at his house .

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      @@noahbaggett9037 it looks like it for sure, that’s pretty awesome man, shows the type of guy and tech you are 🫡

  • @Qualityservicesbcs
    @Qualityservicesbcs 18 днів тому

    I go around 200 to 300 usually let it sit for 15 to 20 minutes then vacuum and let it sit 10 no drop and good

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      That’s a good procedure!! You find that you pull it down to fast but there’s still some moisture in the line?

    • @Qualityservicesbcs
      @Qualityservicesbcs 18 днів тому

      @ yeah I always let it sit if it goes up I let it sit a bit more . But I always pull way below 500 usually around 200

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      @@Qualityservicesbcs hell ya

  • @pnajera3938
    @pnajera3938 18 днів тому

    Sup Krause. Saw you on the road the other day near sanford. Crazy guy waiving you down in the black explorer. Keep them videos coming brotha!

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      YOOOOO 💪 🫡 My man!!! Appreciate the support bro!!

  • @noahbaggett9037
    @noahbaggett9037 18 днів тому

    That damn check in kiosk 😂 Out here running calls on a Sunday sitting in the truck watch this 😂

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      Dude that shit is so annoying 🤣 brother be safe out there and crush it make that money!!!

    • @noahbaggett9037
      @noahbaggett9037 18 днів тому

      @@KoolinwithKrauss yes sir ! I deleted my Facebook and instagram . You should have my number if you need anything sir .

  • @Ronnie-f1v
    @Ronnie-f1v 18 днів тому

    Good job son

  • @hvactechpr7872
    @hvactechpr7872 18 днів тому

    I remember when I did the vrf they made us pressure test at 800 there was leaks that didn't pop up at 400...

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      Man 😳 hell of a lot of pressure, but makes sense!!

  • @Ronnie-f1v
    @Ronnie-f1v 18 днів тому

    Have to go by the max pressure on that aluminum coil

  • @ReliableHVACR
    @ReliableHVACR 18 днів тому

    maxing out that van, and putting that Inficon to work

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      Bro, I’ve gotten more shit in here now since then 🤦‍♂️ but it is coming up clutch

  • @dumptrks
    @dumptrks 18 днів тому

    Low side always especially if you have transducer bruh...U KNOW

  • @Ronnie-f1v
    @Ronnie-f1v 18 днів тому

    That's why I use my welding gloves

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      I heard that!! I need to start wearing mine 🤦‍♂️

  • @twharton3611
    @twharton3611 18 днів тому

    Why you looking away holding the pop fuse in your hand haha

  • @Boushhhhh
    @Boushhhhh 19 днів тому

    What is the difference between the 32500hdrt vs 32500hdrtg? One is 10 bucks more but I can’t find a difference.

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      Not sure what the hdrtg is can’t find anything on it, only thing is there’s a ratcheting version and non ratcheting

  • @robquin2460
    @robquin2460 21 день тому

    didn't flow nitro?!

  • @98593le
    @98593le 22 дні тому

    Boycott made in Israel. End apartheid

  • @TropicaljeremiahBiz
    @TropicaljeremiahBiz 23 дні тому

    The “what’s starting to leak” cracked me up 😂😂

  • @brooksmax00
    @brooksmax00 23 дні тому

    What valve is that your using with your probe. The one you purged with

    • @KoolinwithKrauss
      @KoolinwithKrauss 23 дні тому

      Yellow jacket valve core tool

    • @Ronnie-f1v
      @Ronnie-f1v 22 дні тому

      He'll yeah son it rose this morning with a Trump gift

  • @randyshope4744
    @randyshope4744 23 дні тому

    CX34 coil leaking

  • @jasonjohnsonHVAC
    @jasonjohnsonHVAC 23 дні тому

    A leaking Lennox evap coil......nooooooo....lol....they always leak

  • @stevensko9153
    @stevensko9153 24 дні тому

    Also find it an inconvenience. It would have been much better to be able to pull the sockets through.

  • @woodystokes1543
    @woodystokes1543 24 дні тому

    Nice work man really don’t waste your battery on a Lennox you already know 😊

  • @jes6885
    @jes6885 24 дні тому

    From my experience i feel like carrier residential evap coils are the most reliable coils besides their txv’s lol i don’t remember the last time i went to carrier to pick up a evap coil.

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      Stay tuned, carrier coil coming in hot!! But I do find carrier coils to be on the upper end of reliability compared to other manufacturers and especially at the rate I encounter their equipment

  • @JesseDoesHVAC
    @JesseDoesHVAC 25 днів тому

    Lennox pulled outta Australia 🇦🇺 a few years ago Used to install heaps of their single speed ac (add on) units typically the tsa outdoor condensers and ch33 c and d coils onto gas furnaces down here Used to be fairly reliable but before they pulled out of aus we were getting so many evap coils leaking out of the box and condensers with low/no base charges…shameful

    • @KoolinwithKrauss
      @KoolinwithKrauss 18 днів тому

      That’s wiiiild!!! Was it Lennox decision on government to kick their 🫏 outta there?! I recall when I started they were definitely very reliable and a top manufacturer

  • @AaronPowellvox
    @AaronPowellvox 25 днів тому

    I still like my cheaper version of that inficon leak detector. I’ve never not found the leak with it.

    • @KoolinwithKrauss
      @KoolinwithKrauss 23 дні тому

      Solid!! Gotta having something reliable, definitely enjoying the inficon lineup

  • @Qualityservicesbcs
    @Qualityservicesbcs 25 днів тому

    I won’t tell anybody shhhh mums the word Haha

  • @JonBoy-HVAC
    @JonBoy-HVAC 25 днів тому

    Leaky Lennox

  • @38mullet
    @38mullet 25 днів тому

    lennox sucks replaced so many coils every no cool low on charge come on

  • @venvnco6259
    @venvnco6259 25 днів тому

    Leaky Azz lennox.

  • @victorhugorengifomera6517
    @victorhugorengifomera6517 25 днів тому

    Great job Krauss How much for replace a compressor of 5.tones

  • @Eddy63
    @Eddy63 25 днів тому

    Nice job & vid Jake ... Thx

  • @helmsajr
    @helmsajr 25 днів тому

    Great job Jake. Not a fan with Lennox.

    • @KoolinwithKrauss
      @KoolinwithKrauss 25 днів тому

      Appreciate it man, sadly neither am I at this point!

  • @harbosonius
    @harbosonius 25 днів тому

    If Dave Lennox was alive today he would be absolutely disgusted at what they’ve done to his legacy… Absolute shit boxes…Lennox units from the 80s through late 90s were absolutely bulletproof other than the occasional evap leak or outdoor run cap or fan motor.

    • @KoolinwithKrauss
      @KoolinwithKrauss 25 днів тому

      That is the absolute truth sadly!! I feel if you’re a contractor willingly and knowingly selling that shit, your scum! Only if your the owner because they must be giving them some bad ass rebate incentive and labor warranty knowing the high failure rate In my option of course 😆

    • @harbosonius
      @harbosonius 25 днів тому

      @@KoolinwithKrauss “ Allegedly”😀😀😀😀