How to Perform an Electrical Inspection According to the InterNACHI® SOP

Поділитися
Вставка
  • Опубліковано 19 гру 2019
  • Subscribe to our UA-cam Channel: ua-cam.com/users/internachi?... In this part of the nine-part video series on home inspections, follow along with Certified Professional Inspector® Jim Krumm and Mike Krumm as they inspect the electrical system of a home according to InterNACHI's Home Inspection Standards of Practice.
    =========================================================================
    Subscribe to our UA-cam Channel: ua-cam.com/users/internachi?...
    ==========================================================================
    Share this video! • How to Perform an Elec...
    ==========================================================================
    Follow us on Facebook and Instagram!
    / internachi
    / internachihq

КОМЕНТАРІ • 163

  • @jasonevans8680
    @jasonevans8680 Рік тому

    Very helpful! Thanks for putting so much time into these videos. The effort put into the add-in diagrams and built in videos is extra helpful. Keep up the great work! Thanks again.

    • @internachi
      @internachi  10 місяців тому

      Awesome. Thanks for watching the video and for replying. For more home inspection videos, please visit www.nachi.org/webinars

  • @garygech
    @garygech 3 роки тому +5

    This was really good, and the emphasis on safety was terrific. I am very thankful. I learned a great deal.

    • @internachi
      @internachi  3 роки тому

      Glad it helped! Anything else you're looking for?

  • @farmerdave7965
    @farmerdave7965 3 роки тому

    As a Colorado electrician, I appreciate your work. Looks to be pretty thorough.

    • @internachi
      @internachi  3 роки тому

      I appreciate that! Thank you.

  • @ThreeMinuteHistory
    @ThreeMinuteHistory 3 роки тому +2

    Some very good tips and information. Carrying extra screws in case you drop and lose some: nice touch!

  • @kevinrobins5805
    @kevinrobins5805 3 роки тому

    He's a Legend. Great video and thank you.

    • @internachi
      @internachi  3 роки тому

      Glad you enjoyed it. I recommend Check out my free, online class "How to Become a Successful Home Inspector" at www.nachi.org/webinars/2020/how-to-become-a-successful-home-inspector-1
      Another good inspection video is at ua-cam.com/play/PLKPEi6DdHVZyHK4tkfQuDKRPkBE5oWtuA.html

  • @hozelaud1667
    @hozelaud1667 2 роки тому +1

    Thank you very much for sharing all this to me you are top the best to hear and learn ,my whole respect and admire your knowelege,i want to become like you

  • @SwingTrading
    @SwingTrading 4 роки тому +5

    I'm just getting started doing home inspections, great video.

    • @internachi
      @internachi  4 роки тому +1

      Thank you, Swing Trader. Glad to hear you enjoy watching the videos. Be sure to subscribe to our channel.

    • @chadsadventures
      @chadsadventures 2 роки тому +1

      How is it going did u continue with it

  • @jpurvis1
    @jpurvis1 4 роки тому +15

    Great content, and as Always, Jim is a very good mentor, Inspector and coach.

    • @internachi
      @internachi  4 роки тому +1

      Jim is one of the best CPIs.

    • @ChakasCave
      @ChakasCave 3 роки тому

      Lon is my favorite. I’m just glad Jim got rid of his early 2000s hairstyle😂😂

    • @joeshmoe5935
      @joeshmoe5935 2 роки тому

      @@internachi Hands Down

    • @glennferris5056
      @glennferris5056 2 роки тому

      Home inspector is a scam , they don't warrenty thier work? They take your money and run, just call your local electrical company to do this.

  • @AfGG
    @AfGG 3 роки тому +3

    Nicely explained thank you great sir! I got a midterm popping up for my electrical inspection course and this helps generalize everything 💯

  • @vince6829
    @vince6829 Рік тому +5

    Very comprehensive inspection.
    I am a recently-retired professor of biology. One thing that I had access to back when I was still teaching was a lab safety inspection checklist. I used the checklist in preparing for scheduled lab inspections. I am wondering if electricians and homeowners would benefit from a home electrical inspection checklist. Just a thought. It would be fairly easy to generate from what you addressed in your video.
    Thanks for sharing your knowledge.

  • @leotexas3485
    @leotexas3485 3 роки тому +1

    Thank you for this! I’m an Apprentice, for my side job, and this helps me understand what Inspectors look for during inspections!

    • @internachi
      @internachi  3 роки тому +1

      Glad it was helpful! I invite you to take the Master Class for Home Inspectors at www.nachi.org/masterclass.htm.

    • @waynedickens4031
      @waynedickens4031 3 роки тому +1

      Hey as a apprentice . If you copy this guy . You wont live long . Were ppe .
      Then no one will call your old lady . And tell her you burned your eyes. From a electrician .

    • @whith5184
      @whith5184 3 роки тому +1

      @@waynedickens4031 he explained why he wasn't wearing any

    • @fatherelijah1763
      @fatherelijah1763 3 роки тому

      @@whith5184 still

    • @paulb9156
      @paulb9156 Місяць тому

      What type of apprentice? Electrician or home inspector?

  • @OthmanAlikhan
    @OthmanAlikhan 7 місяців тому

    Thanks for the video =)

    • @internachi
      @internachi  7 місяців тому

      Thanks for watching.

  • @tytravelbee9030
    @tytravelbee9030 3 роки тому

    Great information

  • @Danny-fs1hk
    @Danny-fs1hk 3 роки тому

    An excellent video

  • @izabari
    @izabari 2 роки тому +1

    As a newbie I'm wondering if there is a list of correct gauge wires to size of breaker. Would be handy. Great video!!!

    • @internachi
      @internachi  2 роки тому

      That's in our free, online electrical course at www.nachi.org/education.

  • @vonkanon3091
    @vonkanon3091 Рік тому

    Can't give this video enough thumbs up

    • @internachi
      @internachi  Рік тому

      Thanks for watching and commenting.

  • @jamescourtney130
    @jamescourtney130 3 роки тому

    I noticed that there is dryer duct hose running right next to the distribution panel, which normally we are not supposed to have any plumbing or duct work either directly above or below. Would you call that out as a defect or simply note its existence in this particular case?

    • @internachi
      @internachi  3 роки тому

      Great catch, James. Spot on. Defect.

  • @AnAZPatriot
    @AnAZPatriot Рік тому

    All the new construction at least post 2015 the main panels are outside also in Texas.

  • @joeshmoe5935
    @joeshmoe5935 2 роки тому

    Ideal circuit analyzer? In my mind last 2 weeks have been fighting over Amprobe INSP III or Ideal. Folks say Ideal take too long for start and load drop screen.

  • @mehmetferhat1986
    @mehmetferhat1986 Рік тому

    Thanks

  • @justinbailey7281
    @justinbailey7281 2 роки тому

    Would this be a good guidelines to how electrical inspectors for the city do inspections

  • @BillC-64
    @BillC-64 2 роки тому

    I was told to not use the tester to test the GFI but to use the built in tester of the outlet.If the circuit is ungrounded but is GFI protected, then the circuit tester will still report as not working.

  • @telosfd
    @telosfd 3 роки тому

    In a newly built house that needs to be connected to the electric network for the first time, what documents are necessary to do this?

    • @internachi
      @internachi  3 роки тому

      Not sure. Thanks for watching and commenting.

  • @davekauffman8727
    @davekauffman8727 3 роки тому

    The placement of the carbon monoxide detector would be lethal to the occupants if a CO emission began accumulating the deadly gas in the home, CO is heavier than air and will not be detected until it reaches the height that the detector is placed. Good call on using the plastic pen in the breaker box, I'm nervous when working on putting wire into a breaker and securing it with the screw., I've shorted them before. I don't care how much less aluminum wire costs, copper is the best for home use, it's all there is here in NY State.

    • @internachi
      @internachi  3 роки тому

      Great comments, Dave. Thanks for watching.

  • @paulb9156
    @paulb9156 Місяць тому

    Up in Canada I’ve never seen a distribution panel outdoors. That’s scary to me considering you could be standing in moist/wet ground.

    • @internachi
      @internachi  Місяць тому

      Common in about half of panels in U.S.

  • @a-ron9884
    @a-ron9884 3 роки тому

    How do you tell the difference between aluminum wires and tin coated copper?

    • @internachi
      @internachi  3 роки тому +1

      That's a good question. ua-cam.com/video/wQd2JJ2XA20/v-deo.html

  • @GuidedInspections
    @GuidedInspections 4 роки тому +3

    14:00 " they are both 12 amp breakers (12 gage conductors)"

    • @internachi
      @internachi  4 роки тому +1

      Yep. Good catch. I think he meant 12 gauge.

  • @streetcruise9807
    @streetcruise9807 Рік тому

    In Pennsylvania, do I need to pay $225 to the exam ? Is the exam include in the package?

    • @internachi
      @internachi  10 місяців тому

      No. www.nachi.org/licensing-and-certification/us/pennsylvania

  • @waynedickens4031
    @waynedickens4031 3 роки тому +3

    Great video. I am a electrician. I been yelled at with horror in there voices . Never take a cover off a panel with no glasses .

    • @internachi
      @internachi  3 роки тому +1

      Good point! PPE is essential. Every home inspector must protect themselves in order to come back home at the end of the day.

    • @TheBooze13
      @TheBooze13 3 роки тому +2

      Lol cmon Wayne real electricians never wear glasses!

    • @waynedickens4031
      @waynedickens4031 3 роки тому +1

      @@TheBooze13 real men dont eat quiche. But were glasses . Haha

    • @whith5184
      @whith5184 3 роки тому +1

      he explained why he wasn't wearing any PPE

    • @robblochinger986
      @robblochinger986 9 місяців тому +1

      35 years of taking of panel covers with no giant arcs, you tend to get complacent.
      I just thought he was gettin danger close to the lugs when he was poking around with the pen.

  • @johnherlache9415
    @johnherlache9415 Рік тому

    NEC table250.122 number 10 equipment grounding conductor is allowed on a 60 amp circuit

  • @blade7029
    @blade7029 3 роки тому +1

    interesting how in the US the panels are on the exterior of the home.

    • @internachi
      @internachi  3 роки тому +1

      Not all homes, but many. It really depends on location.

  • @darylsavage119
    @darylsavage119 2 роки тому +1

    As a uk electrician am I missing part of the testing? Here we have to much more testing, testing that earths (grounds) have a complete path with resistance readings to make sure the breaker will trip off in correct timings. We also have to test insulation resistance of cable to make sure the pvc hasnt broken down?

    • @internachi
      @internachi  2 роки тому

      Hm. We don't test over here.

    • @darylsavage119
      @darylsavage119 2 роки тому

      @@internachi as in ever? Or just during inspections?
      Over here it's called, periodic testing and inspection,and should be carried out at no more than 5yr intervals

    • @kevinwalker4623
      @kevinwalker4623 2 роки тому

      I'm from the US and watching CJR do y'alls inspections is interesting and confusing. I think where the major difference is we are mostly 120vac where I understand yall are 240vac. The consequences of a short in 240 is worlds different. Still trying to figure out rings, spurs, mcd's and rcd's. I finally figured out the testing gizmo is just a meggar, a fancy expensive one. Here in my home, I have a 200amp "consumer unit". I want a bigger one so I can have more 240 outlets in the garage for a welder and an air compressor. No testing is required by the NEC in residential that I've ever read.

    • @darylsavage119
      @darylsavage119 2 роки тому

      @@kevinwalker4623 forget about rings, only dinosaurs are still installing them in new builds, and in exsisting dwellings they're a constant source of headache.
      RCBO is a GFCI from what I understand, difference is we do it at the DB so we can protect the entirety of the cable as well as outlets.
      RCD is an older version of GFCI that covered a couple of circuits, problem was a fault in any of the circuits resulted in a loss of alot of your circuits until it was reset, and if the issue is bad enough it wouldn't reset until you found a fault

    • @darylsavage119
      @darylsavage119 2 роки тому

      @@kevinwalker4623 also our testing is to determine a multitude of things, earth fault loop impedance (make sure our ground is actually connected right the way through and it adequate to actually carry the fault current sufficiently to 1. trip breaker within a given time and 2.carry the fault current without also causing fire.
      While megger is the brand CJR uses there is others, but his tester same as mine will carry out the 4 main tests we care about, earth fault loop impedance, ring continuity, RCD/RCBO tripping times, insulation resistance

  • @MasterTheNEC
    @MasterTheNEC 2 роки тому +1

    Ummmm....The reference made at 5:06 is incorrect, that is a violation of multiple grounded (neutral) conductors under a single lug but its not a "fused" neutral as stated.

  • @thoner93
    @thoner93 4 роки тому +1

    All those branch circuits wiring coming thru looks like a 2" opening, would that be considered bundling ...

    • @internachi
      @internachi  4 роки тому

      Good catch.

    • @lloydmills9619
      @lloydmills9619 3 роки тому

      No, but it is a violation.

    • @jjoejones1
      @jjoejones1 3 роки тому

      From the video, it’s hard to discern if multiple cables are entering the cabinet through a connector or a raceway. If it’s a nonmetallic sheathed cable (Romex) connector, some jurisdictions would consider the installation an NEC violation because the connector is not listed for multiple cables. ‘Bundling’, as you refer to it, describes a failure to maintain separation of cables, but it’s only an NEC violation if the length of the ‘bundled’ cables exceeds 24-inches.

  • @saundersryan20
    @saundersryan20 Рік тому

    Interesting that you have to bond to the water system! I have not ever done that! I bond to the slab, gas but never the water

  • @Gunny_101st
    @Gunny_101st 4 роки тому +1

    23:12 i always mention when a smoke detector is located near a return, register or WH fan with the possibility of smoke being drawn away from it.

    • @internachi
      @internachi  4 роки тому

      Nice. Good feedback. Thanks, Stephen, for watching.

  • @andolik
    @andolik 3 роки тому +1

    The CO alarm is suppose to be few inches off the floor not that high. By the time CO alarm goes off, the occupants Let's say sleeping on the bed would be dead. The CO gas is much heavier than other gases or air and starts to sink on the floor and built up. The CO alarm, I recommend to be installed no more than 24 inches off the ground on the wall. I don't understand why he didn't call that as a defect.

  • @wildwoodtop
    @wildwoodtop 2 роки тому

    8:37 Just what you do in a situation whereas you remove a pointy screw, Would you go to your bag and get a flat screw to replace the pointy one 🤔9:18 😋

    • @internachi
      @internachi  2 роки тому

      Yes. That's why we bring extra panel screws for replacements.

  • @thoner93
    @thoner93 4 роки тому

    Only counter top receptacles in the kitchen require GFCI.

    • @internachi
      @internachi  4 роки тому +2

      Yep, but also other kitchen receptacles or circuits, such as the dishwasher. It requires GFCI protection. 2018 IRC E3902 codes.iccsafe.org/content/IRC2018P3/chapter-39-power-and-lighting-distribution

  • @zman3754
    @zman3754 4 роки тому

    Is this called sub panel or distribution panel?

  • @davidedgren8306
    @davidedgren8306 4 роки тому +1

    At 5:10 You use the term "fused Neutrals" This is not the correct term. A fused neutral is a dangerous condition, typically found in knob and tube wiring sections. You are referring to multiple neutrals under one lug. I am not being critical, but using the wrong terms can be confusing for all involved.

    • @internachi
      @internachi  4 роки тому +1

      Correct, David. Thank you for watching our videos. I'll forward your comment to the inspector in the video.

  • @rayjackson4547
    @rayjackson4547 Рік тому

    Nice Job Jim, but never stick anything inside a live electric panel even if it is a nonconductive plastic pen.

    • @internachi
      @internachi  Рік тому

      He uses a plastic pen with no metal parts or guts. Good point.

  • @ronperez4243
    @ronperez4243 3 роки тому

    Miss your fro Jim

  • @BearStar1
    @BearStar1 2 роки тому

    Wearing Gloves and a Protective Shield is only required in a Industrial Complex !! NOT in a Residential or Commercial !!

    • @internachi
      @internachi  2 роки тому

      Nope. It's ultimately up to the home inspector and what PPE she feels is needed.

  • @marsupialsrock010
    @marsupialsrock010 8 місяців тому +1

    When you said you saw an indication of someone who is not an electrician was in the electrical panel, all I could think was "like the inspector?"

  • @vanillarain711
    @vanillarain711 2 роки тому

    I have spilled those plug in air fresheners!! It was horrible!

  • @MasterTheNEC
    @MasterTheNEC 2 роки тому

    FYI- That's sheathing and not insulation on that NM Cable....Big Difference.

  • @waynedickens4031
    @waynedickens4031 3 роки тому

    A friend of mine . worikg on electrical panel no gloves . He is a serious electrician . Explosion. Burnt his hand so bad he suffered for 6 months . Then got a good job . Cause they wee afraid of a lawsuit .

    • @internachi
      @internachi  3 роки тому

      Thank you for the feedback.

  • @michaeleverest3487
    @michaeleverest3487 3 роки тому

    Those are some sad looking panels, whoever wired them needs to make their work a lot cleaner and organized

    • @internachi
      @internachi  3 роки тому

      Hm. Thanks for watching and commenting.

  • @kevinstenger4334
    @kevinstenger4334 2 роки тому

    Nice job but OSHA doesn’t care if you’re making a video, proper PPE is always required inside the arc flash boundary. I’m a retired electrician and we all had to learn how to do a lot of things we didn’t think were realistic when all of the arc flash regulations came out. I thought they were nuts in the beginning but when I moved over into power distribution, substation, and breaker maintenance I got to work with really good electrical engineers doing arc flash studies and trip device settings I got to see clearly how it all works. And yes, even the little 120/240 breaker panel can be extremely dangerous depending on the coordination of the over current devices and the power source. We found some panels that beyond class 4, they were prohibited for energized work under any condition.

    • @internachi
      @internachi  2 роки тому

      Great comment. Safety first.

  • @chadgerman8173
    @chadgerman8173 2 роки тому

    ha ha ha ha

  • @bdubs8620
    @bdubs8620 Місяць тому

    I don’t believe you wear PPE.
    Pair glasses/hardhat/gloves/ steel toe boots wouldn’t affect video quality
    If you regularly wear PPE one would have expected them to be with all your other tools that are used on a daily basis.
    Is what it is, I don’t either

    • @internachi
      @internachi  19 днів тому

      Thank you for watching and commenting. Good point.

  • @mr.spacely6503
    @mr.spacely6503 4 роки тому

    Internachi sop says not to insert any items in electrical panel lol

  • @allanguindon2156
    @allanguindon2156 3 роки тому

    As a licensed Master electrician, NEVER use a pen to touch LIVE electrical parts. Some screw drivers and tools are rated for high voltage for a reason. The last time I checked pens are not rated for electricity.

    • @internachi
      @internachi  3 роки тому +1

      The home inspector removes all metal parts from the pen including the inner components and the outside pocket hook and button.

    • @allanguindon2156
      @allanguindon2156 3 роки тому +2

      @@internachi 1)Do honestly believe that guy took the time to remove all metal parts from the pen?? Its a pen!.. No one wastes their time disassembling a pen.
      2) Was that pen rated for Voltage? Was that pen tested by U.L. or by a federal safety agency? Look at screwdrivers. Some are plain old screwdrivers and some are rated for voltage. Why would screwdrivers need that voltage rating?

    • @waynedickens4031
      @waynedickens4031 3 роки тому

      Pens are not ul rated . Is right .

    • @kentdavis4446
      @kentdavis4446 3 роки тому

      I took a screenshot and zoomed in. Its a click style pen and he does not have tip out, however I cannot be sure all of the internal components have been removed.

    • @farmerdave7965
      @farmerdave7965 3 роки тому

      I use a long soda straw.

  • @LuisGomez-le4vk
    @LuisGomez-le4vk 3 роки тому

    This is a payaso

    • @internachi
      @internachi  3 роки тому

      No. Es un profesional inteligente que gana mucho dinero en su negocio.

  • @waynedickens4031
    @waynedickens4031 3 роки тому

    People will watch this and get hurt . No glasses no gloves
    I am trained to say something if I see a hazard.

    • @internachi
      @internachi  3 роки тому +1

      Home inspectors should wear PPE, and it's up to them to choose which equipment. InterNACHI takes safety seriously and that's why we provide a free, online course about home inspector safety at www.nachi.org/safety_course.htm. This course is free, online, and open to everyone. Everyone. Go ahead and take it. No credit card required.

    • @whith5184
      @whith5184 3 роки тому +1

      he explained why he wasn't wearing any

    • @bradleywilliams229
      @bradleywilliams229 3 роки тому +2

      are you also trained to pay attention?

  • @lloydmills9619
    @lloydmills9619 3 роки тому

    Off gasses? WTF are you talking about?

  • @MovingToMnPro
    @MovingToMnPro 2 роки тому +1

    @4:00 Good idea not to be standing in a puddle.

  • @kiefmanning7394
    @kiefmanning7394 Рік тому +1

    That is a ten cent pen. Not what I usually like to trust my life to. Seems unnecessary to touch and drag things over live circuits for zero reason

    • @Thebeardedangler785
      @Thebeardedangler785 11 місяців тому

      My thoughts exactly

    • @internachi
      @internachi  10 місяців тому

      The metal components of the pen have been removed for safety.

  • @joeymcpeek5120
    @joeymcpeek5120 3 роки тому +1

    For the love of God, please quit saying “pitcher” instead of “picture”.

    • @internachi
      @internachi  3 роки тому +1

      Ha. Or roof instead of ruff.

  • @5400bowen
    @5400bowen 2 роки тому

    Anyone who takes the top screws out first on the cover needs to reevaluate their profession. I've looked at hundreds of breaker boxes, I've never seen a burnt wire. And his tone of voice is angry. He sounds like an angry father berating his teenager for putting s dent in the car fender.

    • @internachi
      @internachi  2 роки тому

      Glad you enjoyed watching the video.

  • @waynedickens4031
    @waynedickens4031 3 роки тому

    Only electricians should take panel covers off . Obviously the guy has no clue . Sorry that's from a electrician

    • @internachi
      @internachi  3 роки тому +1

      Hi, Wayne. I hear what you're saying. I've found that I do a better home inspection for my client when I can remove the dead front safely. Home inspectors are not required to remove them. But some/many do. And when I do, I often find defects, and that's when I recommend that a licensed electrician come and further evaluate and make necessary corrections. My report summary is essential a lead-generation for licensed professionals like yourself. Thanks for watching.

  • @waynedickens4031
    @waynedickens4031 3 роки тому

    Were safety glasses and gloves not like this guy . He is unsafe . Non electrician should not open electrical panel. Even electrician. Dont open panel without a safe work plan . Super dangerous .
    If I did this when I was working at some large corporation. They would kick me and my company off site . Cause they would seem us incompetent.

    • @internachi
      @internachi  3 роки тому

      PPE is critical. You're correct. We agree.

  • @ara5823
    @ara5823 5 місяців тому

    he is doing an electrician job by opening the dead front cover. SOP SOP

    • @internachi
      @internachi  4 місяці тому

      Home inspectors are permitted by the InterNACHI Standards of Practice to remove the dead front cover.

    • @ara5823
      @ara5823 4 місяці тому

      @@internachi what's the point of the SOP?

  • @ara5823
    @ara5823 5 місяців тому

    its not required to open dead front cover then don't do it. period

    • @internachi
      @internachi  4 місяці тому

      Thank you for watching and commenting.

  • @ara5823
    @ara5823 5 місяців тому

    you are inter-nachi people operating outside the SOP. so I take inter nachi course told to follow SOP and now you are showing other wise. contradiction. hypocritical

    • @internachi
      @internachi  4 місяці тому

      Nope. Home inspectors are permitted to exceed the minimum standards. Read www.nachi.org/exceed-or-not-exceed.htm