Transformer Differential Relay testing | and | how to create slope on Omicron kit | RET ABB RELAY

Поділитися
Вставка
  • Опубліковано 23 січ 2025

КОМЕНТАРІ • 104

  • @colinteoh3230
    @colinteoh3230 Рік тому +3

    Dear sir, thank you for sharing your knowledge, I think the world would be a better place with people like you.

  • @mohgahfer5619
    @mohgahfer5619 3 роки тому +2

    Excellent, I searched for those videos alot but not found by this details way, Thanks alot

  • @owinookello9358
    @owinookello9358 6 місяців тому +2

    One of my best teachers ,sir kindly those videos in hindi please translate in english and also put all your videos in one playlist for easy assess

  • @jejkosuru801
    @jejkosuru801 4 роки тому +4

    Best video on Trafo differential bias scheme . nice explanation . i hope you will post similar type of videos in future also.

  • @bharatlalmali8695
    @bharatlalmali8695 2 роки тому +2

    I have become fan of your knowledge and fundamentals. Great job sir....you are a guide of millions of protection engineers...thanks..May you prepare a video on 2nd harmonics testing of restricted earth fault protection and it's requirements...

  • @napolionituinabua8183
    @napolionituinabua8183 4 роки тому +3

    Great Video bro.... shows your in-depth knowledge on the subject... hope for more great videos...

  • @ND-ub6kz
    @ND-ub6kz 2 місяці тому +1

    Bravo bro... massive work

    • @baranitech
      @baranitech  2 місяці тому

      thank and most welcome

  • @RahulKumar-sw2hk
    @RahulKumar-sw2hk Рік тому +2

    Please Sir explain Generator Protection like Differential, Reverse Power, Stator Fault, Overexcitation etc.

    • @baranitech
      @baranitech  Рік тому

      ua-cam.com/video/wiVBvZ1U8rU/v-deo.html

  • @suremanverma8308
    @suremanverma8308 4 роки тому +4

    Great video upon RET670 testing through Omicron test kit (Diff Characteristic). Here some parameters missing to set in relay test kit viz. Idiff >>, Idiff>. If pick up value less than .3,then you have to set accordingly. Also after drawing curve in characteristics, it is not reflecting same as in test module. Here some video skipped. However it has given good reference for testing. If this clarity is given in upcoming videos, it will really help working engineer like me.
    Thanks for reading my feedback.

    • @baranitech
      @baranitech  4 роки тому +2

      This parameter 100 % will match for RET 620 series. i will try to make more clear and without skipping on next time and thank for your feed back .

  • @muthamilselvan5410
    @muthamilselvan5410 5 років тому +4

    Thank you for your valuable upload .it's very useful for me.kindly upload harmonics test and REF test .as well as RED670 all test

    • @muthamilselvan5410
      @muthamilselvan5410 4 роки тому +1

      @@baranitech i am waiting for your next upload for RED670 relay testing

  • @7783786
    @7783786 5 років тому +1

    Very useful video, Thanks from your efforts

  • @Naveenkumar-qb9xb
    @Naveenkumar-qb9xb 3 роки тому +1

    Excellent Sir..

  • @mix98100
    @mix98100 3 роки тому +1

    Nice video, good to value addition

  • @neeleshwaran5330
    @neeleshwaran5330 3 роки тому +1

    Very useful brother...,

  • @suremanverma8308
    @suremanverma8308 2 роки тому +1

    Thanks for step by step guide to RET 670 Diff testing through Omicron Test kit specially shot test and search test. Kindly review Bias formulae of ABB RET 670. As per manual, it is mentioned maximum of individual current referred to Primary. please share other make relays Bias formula for preparing exact slope characteristic.

  • @mkhoirun918
    @mkhoirun918 Рік тому +1

    Do you have any video for step by step Low Impedance REF Transformer Protection Setting Calculation include?

    • @baranitech
      @baranitech  Рік тому

      ua-cam.com/video/P4pi64W6oAg/v-deo.html

  • @MaheshBaburajapalayam
    @MaheshBaburajapalayam 2 роки тому +1

    Really thanks for knowledge

  • @shehab1798
    @shehab1798 4 роки тому +2

    really awesome content bro.. can't thank you enough!

  • @ajmalmuhammed3605
    @ajmalmuhammed3605 Рік тому +1

    You are great sir❤

  • @sohailjanjua123
    @sohailjanjua123 Рік тому +1

    Hi, I like your video. Thanks

  • @sureshpadhy2243
    @sureshpadhy2243 4 роки тому +1

    How to test differential protection of a three winding transformer.... Please explain

  • @balajiradhakrishnan2365
    @balajiradhakrishnan2365 5 років тому

    Simply Superb. Well done.

  • @aftabraj1865
    @aftabraj1865 5 років тому +1

    Great lecture... sir please make video on LINE DISTANCE PROTECTION with zone calculation.

  • @3rdtesla
    @3rdtesla 5 років тому

    Awesome explanation...if possible request you to pl. Add link in description every other video you'd mentioned in narration next time.

  • @pradipgajbhiye6910
    @pradipgajbhiye6910 Рік тому

    Sir, sir we replaced the 2 phase old CT of 20MVA PTR with new ones and during the stability test we observe double(0.4+0.4=0.8)current in 1phase,, and all the CT secondary polarity is ok, and then we review the relay setting vector group is Dyn5 instead of Dyn11 please explain how vector group of PTR will be affected CT secondary current

    • @baranitech
      @baranitech  Рік тому

      i will make one video related to your questions.

  • @kelvincollins1591
    @kelvincollins1591 4 роки тому +3

    Great Video Sir!!! How can one test line differential relay using the differential operating characteristic module. I have checked and have seen on the protected object that the protected equipment options are only transformer, Generator, Motor and Busbar.

    • @baranitech
      @baranitech  4 роки тому

      for line differential we do end to end test on quick CMC . if you want to do on differential char. then you can select generator for line

  • @surendrakverma555
    @surendrakverma555 2 роки тому

    Very good. Thanks 🙏🙏🙏🙏🙏🙏

  • @ganesh2241987
    @ganesh2241987 4 роки тому +1

    could you please also provide the testing of siemens 7UT trafo Diff relays

  • @ISLAMASIF56
    @ISLAMASIF56 11 місяців тому +1

    bias current formula for RET670?

  • @tushigenkh166
    @tushigenkh166 3 роки тому +1

    Hello, how can I get the bias calculation? Can you please share any link or manual about it?

    • @baranitech
      @baranitech  3 роки тому

      www.siemens.com/download?DLA06_1288

  • @sathiyaseelan5109
    @sathiyaseelan5109 Рік тому +1

    how to find es3 and y3 values ?

    • @baranitech
      @baranitech  9 місяців тому

      ua-cam.com/video/585TDCgAki4/v-deo.html

  • @ullasan1905
    @ullasan1905 Рік тому

    Usefull

  • @ByunJungSicidsky
    @ByunJungSicidsky 2 роки тому

    Dear Barani
    During the Omicron slope test, I have a question.
    For example, to test idff(0.3In) Ibias(0.5In) value, P-L1/L2/L3 and S-L1/L2/L3 current and angle are displayed automatically.
    Can you please tell me the formula to manually calculate idff(0.3In) Ibias(0.5In) values for P-L1/L2/L3 and S-L1/L2/L3 current values?

    • @baranitech
      @baranitech  Рік тому

      ua-cam.com/video/585TDCgAki4/v-deo.html

  • @allishere547
    @allishere547 5 років тому

    Please give video for phrase angle compensation video related to vector grp.

  • @haiderzafar6200
    @haiderzafar6200 4 роки тому

    For RET615, where are the details entered regarding trafo MVA, hv and Lv voltage rating, vector group etc. I can't seem to find those details in relay.

    • @vinayks3131
      @vinayks3131 3 роки тому

      For RET615 there is no option to enter Trafo MVA. We use the above showing calcalations. However for 670 series, we don't need correction factor.

  • @king-pirates_coc8364
    @king-pirates_coc8364 4 роки тому +1

    good video. can you teach us about abb pcm / siemens digsi software configuration along with required driver ?

    • @king-pirates_coc8364
      @king-pirates_coc8364 4 роки тому

      @@baranitech thanks bro ... good work ... you know ssooo many things :)

  • @adityatiwari8044
    @adityatiwari8044 4 роки тому

    Can you tell me the topic name for cal the slope

  • @surya-pc7nx
    @surya-pc7nx 5 років тому

    Dear Dharani can you take this exemple for satisfying matching FACTOR For differential protection.
    S=25MVA
    Hv=22kV
    Lv=6.9kV
    Hv CT=1600/1
    Lv CT=2500/1.

  • @F13TUN
    @F13TUN 4 роки тому

    AT 13min :00 why didi you choose 0 degree for Ip and 210 degree for Is .As i understood we should have opposite angle ie 0 for primary and 180 for secondary to get the sum of vectors =0 .

  • @mr.biplob3795
    @mr.biplob3795 4 роки тому +2

    I think RET670 match factor not available in parameter

    • @baranitech
      @baranitech  4 роки тому

      yes

    • @mr.biplob3795
      @mr.biplob3795 4 роки тому

      @@baranitech but how to relay matching that much of current

  • @santoshsalade8941
    @santoshsalade8941 3 роки тому

    Sir I don't find your vector group and differential slope value calculateion video

    • @baranitech
      @baranitech  3 роки тому

      ua-cam.com/video/-7BkRGIsc6w/v-deo.html for vector group

    • @baranitech
      @baranitech  3 роки тому

      ua-cam.com/video/qU-0eJWYUrg/v-deo.html slope calculation

  • @BMKinfinity32
    @BMKinfinity32 Рік тому

    Sir how to change vector grup in product object dyn11 not changing

    • @baranitech
      @baranitech  Рік тому

      please follow video step by step it will change.

  • @ranjeetsaroj90
    @ranjeetsaroj90 3 роки тому +1

    Very nice video.. But 1 confusion about CT matching factor, if HV CT Ratio 200/5A and HV FL current 175A. Then matching factor 1÷4.37 or 5÷4.37? Please confirm.

  • @المسلم-ب9ل
    @المسلم-ب9ل 2 роки тому

    Thanks you
    Very good

  • @mr.biplob3795
    @mr.biplob3795 4 роки тому

    Omicron differential protection parameter Primary current you to us Transformer FLA but if i will put CT current i will happen.pls tell me

    • @mr.biplob3795
      @mr.biplob3795 4 роки тому

      @@baranitech maximum site i have finish by CT ratio that time i am not getting any problem

  • @vinayks3131
    @vinayks3131 3 роки тому +1

    Here RET615 is taken as relay. For 670 series, correction factor is not required and all values we can change.

    • @baranitech
      @baranitech  3 роки тому

      yes it for RET615 and RET620 for calculation part

  • @thanhnghean90
    @thanhnghean90 3 роки тому

    good

  • @BMKinfinity32
    @BMKinfinity32 2 роки тому +1

    Sir how to get value for Id and Ib value at stabilty and unstable condition

    • @baranitech
      @baranitech  2 роки тому

      I1-I2 is Id and IB = I1+I2 /2 is for all condition

    • @BMKinfinity32
      @BMKinfinity32 2 роки тому

      Thank you sir!!!

  • @ibnelkhan
    @ibnelkhan 5 років тому +2

    Dear Sir,
    You have calculated matching factor, but in testing where have you used matching factor in testing?
    plz could you explain this, as you have used full load current every time.
    thanks

    • @ibnelkhan
      @ibnelkhan 5 років тому

      ​@@baranitech I am little bit confused here, sorry for this,
      But during testing should we inject the current after multiplying it by matching factor?
      Cz you have only injected calculated full load current, not the one with matching factor.

    • @ibnelkhan
      @ibnelkhan 5 років тому

      Understood thanks

  • @EBNRENGANATHAN
    @EBNRENGANATHAN 5 років тому

    Hi sir
    really super
    i have doubt about HOW to find out single phase pick up?
    Dyn11 for HV and LV

  • @mr.biplob3795
    @mr.biplob3795 5 років тому

    Details of this vector when we are getting boss,

  • @tufailalam6438
    @tufailalam6438 5 років тому +3

    Sir please don't add music in your video it disturbs...

  • @AliAkbarEE
    @AliAkbarEE 4 роки тому +1

    the idea of putting music in between is worst..... this is such a comprehensive topic and one cannot be short of words to put music instead. plus it shatter the tempo and focus...... it's just irritating and please try to clear your accent and pronunciation wofsome words......

    • @AliAkbarEE
      @AliAkbarEE 4 роки тому

      @@baranitech I'm also in relay testing and came across your channel and thought to watch it.

  • @mohankumarkothala7278
    @mohankumarkothala7278 2 роки тому +1

    Music between class was so annoying

    • @baranitech
      @baranitech  2 роки тому

      i have stop mixing music but sorry for this video

  • @sumitmondal548
    @sumitmondal548 4 роки тому +2

    Music sounds are irritating, please filter it out, no one prefers to listen music while understanding differential protection.

    • @baranitech
      @baranitech  4 роки тому

      my new video i am not merging sound. sorry for this.

  • @jaydevnandanfamily
    @jaydevnandanfamily Рік тому +1

    Music idea is very worst. For excellent topic

    • @baranitech
      @baranitech  Рік тому

      sorry it was avoided in future.