I just replaced 2 bad LP converted gas valves today and two more last week, 🤷♂️ but it’s the dead gas valve season! I love working on gas furnaces so much more than boilers but I digress I do it all, oil, gas, boiler, furnace, heat pumps, mini splits…the list goes on and on! Nice job Mikey!
4 flashes was actually an open limit switch Mike. It is an open limit on Carrier and ICP as well. Replacing the valve was the right call, if the opening solenoid is sticking closed it may well stick open when it is time to close. For a couple hundred bucks it’s money well spent.👍👍🇨🇦
not looking good for Ohio, there's been multiple home explosions this year and I think all involved propane. it still amazes me people cannot smell that foul stench of an odor, even with stuffed and plugged nose, I can smell a tiny leak far away! neighbors just down the road went boom one night a handful of years ago, natural gas leak.(yes, In Ohio also)
Great job, but did you address the inducer motor? I feel like you will be back out there by Christmas. Also what was the water in the bottom on the furnace?
Great job 👏. You should give them to me because of my ohhh face. All jokes aside. I have been a long time subscriber. Back before the Steve lav stuff lol. I’m a service tech of 13 yrs. I pranked grubby when he left you the voice mails.
I live north of Minneapolis so cold climate, in the country so we do not have natural gas. It coming time to replace our electric hot water heater. Do you have any thoughts on the electric heat pump hot water heaters? Or should I just stick with the tried and true pure resistive tank?
Mikey I could really use that Testo wireless kit. 6 weeks ago was let go from the contractor I worked for 28 years. Had to leave behind my Sman manifold that was supplied by said contractor. Got a new gig 2 weeks ago and new contactor gave me a set of beat to hell 3 port JB analog guages. I've been drooling over the wirelss probes/temp setups but dont have the $ to throw down on some. I asked about wireless at my new place and they said cost was to much and they don't trust the new wireless probes. Help a guy out brother. Pick me !
hey mikey pipes i had the same situation today and we ended deeming the new gas valve bad, what ended up happening was that another company ended replacing the board. i mostly had worked in nyc and never had that situation happen as in voltage to the gas valve and it didnt work,we replaced 2 valves and it worked and died 8 hours later. is there anything i missed while checking. we even used a contactor to verify the load would pull the magnet. we ohm the wires and still missed it.
Just started doing hvac in January you should send me the probes because Im a patriot that grew up on Long Island, Massapequa and ronkonkoma to be exact. I live in charlotte nc now. Oh and my name is Mike too lol God bless you mikey pipes
Hey Mike. I can definitely used those smart probes. Will make work easy via the Bluetooth since I’m a one person operation. This is Dev. I can pick it up locally.
I would love to have the testo. I am just out of trade school and I am still building up my tools. And that would be a great set to own. As I can't afford anything right now.
The Contactor trick for the win… been burned by seeing the voltage when it was not connected to the load… felt dumb when after I went through the trouble of replacing the valve and it still did not light.. back to get a board I went head hung low …
Love me some percussive maintenance 8:59 as can tell ya lots, but is it “good” to keep there & not replace….. If was my unit, I’d say NOPE, but what do I know 😅
I’m a HVAC and refrigeration tech. I’ve been saving up my tool allowance to buy a set of probes. I would love to try out the testos and then I could use my tool allowance to buy the digital testo gauges instead. I have a set of the original fieldpiece SMANs but they crapped out on me when i was on a roof, a pop up rain shower formed, and some idiot closed and locked the ladder cage of a commercial building while I was up there. I tried to get my digital manifold tucked up inside of a unit, but apparently not fast enough.
@@PipeDoctor Yeah I saw that right after I posted. It’s no problem. I was just getting caught up on my Mikey pipes videos, didn’t realize I was so behind. Keep up the great work!
Mikey 6 yr hvac tech from Philly would love to give those testos a spin, and a couple of those pipe doctor chasity cages you got, thanks; me personally choose not to wear when working but I do wear my Beckett underwear because bring oil back 2024 believe 🙏🏻😢.
I'd really love to get a set of those become I'm starting my own ac business on the side and I am needing a professional set like those. I don't have the money for those bad boys and it would be a blessing to own a set.
Code sta 18 “ electrical failure” on a New Yorker, any ideas for me? 1st time home owner. Heat is working but turning on and off. Thermostat says heat on
I think STA 18 is waiting for flue damper, maybe stuck damper or bad wire connection from damper to control. but the control could also be failing at the damper connector/other.
in the past I have torn down random gas valves and the later model failures are many times a bad full wave rectifier with a dead diode or two. those are the ones with solenoid coils, so they rectify the AC to DC for the coil, while I didn't dive much deeper into the electronics/electrical design, I assume it's that way to A. not make a buzzing sound and B. not cause coil heating. some were failures by debris and somehow getting stick goo inside hanging the physical plunger(s) or the diaphragm/control passage ports. "NEVER, try to repair or modify a gas valve", too much liability and lives at stake!
By the way, Mikey you know that furnace should up at lease 1 inch from that bare concrete floor. Again was in the international building code book at one time.
Mickey.. Why did you not clean out the inside of the gas pipe of that glob of pipe dope, you dope You know that has the potential to clog the gas valve. Shame on you Bro!
Rolling on the floor laughing!!! Any one else?? I would question if you put the roll out heat plate back in place . But pipe dr? Nope never had a doubt about proper re- install.. An gee you gave that gas valve such a love tap 😂😂 don’t watch me 😂😂😂 But seriously that unit is short short life glad it’s you all an not us having to replace it 👍 I absolutely hate tight quarters.
You should send me the testo gen two because I'm just a badass guager. I'm confident, not arrogant. I don't think I qualify though because I'm a lic electrician and hvac tech😂
Hey Mike Daiack, of Mikey Pipes Plumbing not easy being cheesy. You know that the natural gas isn't 100% moisture free. Honeywell and white roger at one time had a ceramic or foam filter inside its gas valve. I did not you clean the flame sensor? Come on Mikey, no little PM again. If were living and working in russian, you be taking a bucket also into the house.lol. Love you buddy, you be safe out there.
You should send me the testo gen two because I'm just a badass guager. I'm confident, not arrogant. I don't think I qualify though because I'm a lic electrician and hvac tech😂
Mike what is the name of the tool bag you use. Thank You Joe H Navy Seabee
Veto amzn.to/3NzkwpA
I just replaced 2 bad LP converted gas valves today and two more last week, 🤷♂️ but it’s the dead gas valve season! I love working on gas furnaces so much more than boilers but I digress I do it all, oil, gas, boiler, furnace, heat pumps, mini splits…the list goes on and on! Nice job Mikey!
4 flashes was actually an open limit switch Mike. It is an open limit on Carrier and ICP as well. Replacing the valve was the right call, if the opening solenoid is sticking closed it may well stick open when it is time to close. For a couple hundred bucks it’s money well spent.👍👍🇨🇦
Great advice. There was a house just north of Dayton Ohio that blew up. The debris field is a 200 yard radius. Two people and two dogs are deceased 😢😢
not looking good for Ohio, there's been multiple home explosions this year and I think all involved propane. it still amazes me people cannot smell that foul stench of an odor, even with stuffed and plugged nose, I can smell a tiny leak far away!
neighbors just down the road went boom one night a handful of years ago, natural gas leak.(yes, In Ohio also)
Great job, but did you address the inducer motor? I feel like you will be back out there by Christmas. Also what was the water in the bottom on the furnace?
I didn’t see a manometer used to test the gas valve?
SO AWESOME!! WOULD LOVE TO SCHEDULE A MAINTENANCE VISIT!
Great job 👏. You should give them to me because of my ohhh face.
All jokes aside. I have been a long time subscriber. Back before the Steve lav stuff lol. I’m a service tech of 13 yrs. I pranked grubby when he left you the voice mails.
I live north of Minneapolis so cold climate, in the country so we do not have natural gas. It coming time to replace our electric hot water heater. Do you have any thoughts on the electric heat pump hot water heaters? Or should I just stick with the tried and true pure resistive tank?
That’s island park , my cousin lives there by one of the house you just passed
Mikey I could really use that Testo wireless kit. 6 weeks ago was let go from the contractor I worked for 28 years. Had to leave behind my Sman manifold that was supplied by said contractor. Got a new gig 2 weeks ago and new contactor gave me a set of beat to hell 3 port JB analog guages. I've been drooling over the wirelss probes/temp setups but dont have the $ to throw down on some. I asked about wireless at my new place and they said cost was to much and they don't trust the new wireless probes. Help a guy out brother. Pick me !
hey mikey pipes i had the same situation today and we ended deeming the new gas valve bad, what ended up happening was that another company ended replacing the board. i mostly had worked in nyc and never had that situation happen as in voltage to the gas valve and it didnt work,we replaced 2 valves and it worked and died 8 hours later. is there anything i missed while checking. we even used a contactor to verify the load would pull the magnet. we ohm the wires and still missed it.
Just started doing hvac in January you should send me the probes because Im a patriot that grew up on Long Island, Massapequa and ronkonkoma to be exact. I live in charlotte nc now. Oh and my name is Mike too lol God bless you mikey pipes
Hey Mike. I can definitely used those smart probes. Will make work easy via the Bluetooth since I’m a one person operation. This is Dev. I can pick it up locally.
You are the best…. Lol and I was whiting for the click of installing the heat shield metal back… 😜
Love everything you are the best.You are very smart, very brilliant.Love your videos my friend😅
I would love to have the testo. I am just out of trade school and I am still building up my tools. And that would be a great set to own. As I can't afford anything right now.
It was already given away
What’s your jurisdiction Mike? NYC? I’m pretty sure tape is aloud.
I always confirm voltage and then i take a contactor and wire it see if pulls it in if it does then i got enough to open the valve
The Contactor trick for the win… been burned by seeing the voltage when it was not connected to the load… felt dumb when after I went through the trouble of replacing the valve and it still did not light.. back to get a board I went head hung low …
Great video. Thank you for sharing
Here in the Midwest, we’re both Natural Gas and Areas Outside St. Louis are ALL Electric Homes which is Expensive for Furnaces, Water Heaters, etc.
Love me some percussive maintenance 8:59 as can tell ya lots, but is it “good” to keep there & not replace…..
If was my unit, I’d say NOPE, but what do I know 😅
Making the Trades Great Again Mikey Pipes. #LoveBosch Keep Smashing that Like Button folks. SMASH IT!!!!
I’m screaming thru the phone you got leverage on the opposite side with your drip leg and union ahhhhh! Which ever way works man
I know but then the other joints could open up
@@PipeDoctor true but that’s why we soap bubbles things
I’ll glady take the Testo gauges Mikey… cuz if you ain’t testin your guessin right? Never hurts to have a few sets in que…
I’m a HVAC and refrigeration tech. I’ve been saving up my tool allowance to buy a set of probes. I would love to try out the testos and then I could use my tool allowance to buy the digital testo gauges instead. I have a set of the original fieldpiece SMANs but they crapped out on me when i was on a roof, a pop up rain shower formed, and some idiot closed and locked the ladder cage of a commercial building while I was up there. I tried to get my digital manifold tucked up inside of a unit, but apparently not fast enough.
Sorry you are like a week too late
@@PipeDoctor Yeah I saw that right after I posted. It’s no problem. I was just getting caught up on my Mikey pipes videos, didn’t realize I was so behind. Keep up the great work!
Mikey 6 yr hvac tech from Philly would love to give those testos a spin, and a couple of those pipe doctor chasity cages you got, thanks; me personally choose not to wear when working but I do wear my Beckett underwear because bring oil back 2024 believe 🙏🏻😢.
FROM CHICAGO EXELENT VIDEO THANK YOU SO MUCH
Mikey, why not replace the inducermotor also? Kind regards
Cause it ain’t in the wallet
Wondering why the inducer motor was making that noise at startup?
noise was normal sounding
I'd really love to get a set of those become I'm starting my own ac business on the side and I am needing a professional set like those. I don't have the money for those bad boys and it would be a blessing to own a set.
Is that blue sealant rated for gas ?
Yes
Code sta 18 “ electrical failure” on a New Yorker, any ideas for me? 1st time home owner. Heat is working but turning on and off. Thermostat says heat on
Control
@@PipeDoctor strange because the whole unit was replaced last year! Thank you
I think STA 18 is waiting for flue damper, maybe stuck damper or bad wire connection from damper to control. but the control could also be failing at the damper connector/other.
in the past I have torn down random gas valves and the later model failures are many times a bad full wave rectifier with a dead diode or two. those are the ones with solenoid coils, so they rectify the AC to DC for the coil, while I didn't dive much deeper into the electronics/electrical design, I assume it's that way to A. not make a buzzing sound and B. not cause coil heating.
some were failures by debris and somehow getting stick goo inside hanging the physical plunger(s) or the diaphragm/control passage ports.
"NEVER, try to repair or modify a gas valve", too much liability and lives at stake!
By the way, Mikey you know that furnace should up at lease 1 inch from that bare concrete floor. Again was in the international building code book at one time.
Lol, I know a couple of homeowners that will sit in the basement and tap that gas valve every time 😂
😂😂😂😂 “oh yeah oh yeah baby oh yeah “ 😂😂😂😂😂
lol
Mickey..
Why did you not clean out the inside of the gas pipe of that glob of pipe dope, you dope
You know that has the potential to clog the gas valve.
Shame on you Bro!
Rolling on the floor laughing!!! Any one else?? I would question if you put the roll out heat plate back in place . But pipe dr? Nope never had a doubt about proper re- install.. An gee you gave that gas valve such a love tap 😂😂 don’t watch me 😂😂😂 But seriously that unit is short short life glad it’s you all an not us having to replace it 👍 I absolutely hate tight quarters.
I’m glad I made this video a little interesting a little different than the others. I typically post.
Nooo, Mikey you should’ve replaced that galvanized nipple. That’s Mikey mouse.
those american standard furnaces have heat exchangers made of paper
Tape on the gas line 😭
Some Jurisdictions it’s required
Did you see the glob of pipe dope he left in the pipe..lol
You should send me the testo gen two because I'm just a badass guager. I'm confident, not arrogant. I don't think I qualify though because I'm a lic electrician and hvac tech😂
Ty
Never ever hit a gas valve. Diagnose it. Also I would replace inducer motor
Use the Smurf jizzem 😂
Tell me about it. Until then, I got Smurf jizz removal wipes. Aka your sisters panties
@@PipeDoctor 😂
😂
nice job as always......
Thanks again!
🙂
umm, 4 blinks is "limit switch open". Mikey needs glasses 🤓🤓 join the crowd!
#1😂
Congratulations 🎊
Car starter
Thanks for sharing your feedback
Apollo 13 flight control, do we have a go or no go. Mikey are we still on VOX or Baby VOX again copy.
134 Thumbs up
They are called face bushings (FYI ) & you know better (putting too much pipe dope on & inside the pipe 🤷🏻♂️), slow down a little bit.
Hey Mike Daiack, of Mikey Pipes Plumbing not easy being cheesy. You know that the natural gas isn't 100% moisture free. Honeywell and white roger at one time had a ceramic or foam filter inside its gas valve. I did not you clean the flame sensor? Come on Mikey, no little PM again. If were living and working in russian, you be taking a bucket also into the house.lol. Love you buddy, you be safe out there.
you would be taking a bucket of coal into the house too, unquote.
Good work pipes!!
I would recommend the customer to replace that vent motor as well. Sounds bad. Peace from 🇨🇦
Yeah, well you could bring a camel to water can’t make a drink
You should send me the testo gen two because I'm just a badass guager. I'm confident, not arrogant. I don't think I qualify though because I'm a lic electrician and hvac tech😂