Gas Furnace No Heat Service Call - Step by Step Diagnosis Bad Gas Control Valve & Replacement

Поділитися
Вставка
  • Опубліковано 26 лис 2024

КОМЕНТАРІ • 85

  • @petroman-cg8tt
    @petroman-cg8tt Місяць тому +1

    Mike what is the name of the tool bag you use. Thank You Joe H Navy Seabee

  • @tphvac87
    @tphvac87 Місяць тому +7

    I just replaced 2 bad LP converted gas valves today and two more last week, 🤷‍♂️ but it’s the dead gas valve season! I love working on gas furnaces so much more than boilers but I digress I do it all, oil, gas, boiler, furnace, heat pumps, mini splits…the list goes on and on! Nice job Mikey!

  • @danobrien3109
    @danobrien3109 Місяць тому +3

    4 flashes was actually an open limit switch Mike. It is an open limit on Carrier and ICP as well. Replacing the valve was the right call, if the opening solenoid is sticking closed it may well stick open when it is time to close. For a couple hundred bucks it’s money well spent.👍👍🇨🇦

  • @Steve-bm2zm
    @Steve-bm2zm Місяць тому +2

    Great advice. There was a house just north of Dayton Ohio that blew up. The debris field is a 200 yard radius. Two people and two dogs are deceased 😢😢

    • @throttlebottle5906
      @throttlebottle5906 Місяць тому

      not looking good for Ohio, there's been multiple home explosions this year and I think all involved propane. it still amazes me people cannot smell that foul stench of an odor, even with stuffed and plugged nose, I can smell a tiny leak far away!
      neighbors just down the road went boom one night a handful of years ago, natural gas leak.(yes, In Ohio also)

  • @brucesibert6550
    @brucesibert6550 Місяць тому +2

    Great job, but did you address the inducer motor? I feel like you will be back out there by Christmas. Also what was the water in the bottom on the furnace?

  • @dkinfishing
    @dkinfishing Місяць тому +2

    I didn’t see a manometer used to test the gas valve?

  • @BronxBabyRamos
    @BronxBabyRamos Місяць тому

    SO AWESOME!! WOULD LOVE TO SCHEDULE A MAINTENANCE VISIT!

  • @North_Coast_Hvac
    @North_Coast_Hvac Місяць тому +1

    Great job 👏. You should give them to me because of my ohhh face.
    All jokes aside. I have been a long time subscriber. Back before the Steve lav stuff lol. I’m a service tech of 13 yrs. I pranked grubby when he left you the voice mails.

  • @realrigel
    @realrigel 18 днів тому

    I live north of Minneapolis so cold climate, in the country so we do not have natural gas. It coming time to replace our electric hot water heater. Do you have any thoughts on the electric heat pump hot water heaters? Or should I just stick with the tried and true pure resistive tank?

  • @oscarreyes3175
    @oscarreyes3175 Місяць тому

    That’s island park , my cousin lives there by one of the house you just passed

  • @filthyphil8208
    @filthyphil8208 Місяць тому +1

    Mikey I could really use that Testo wireless kit. 6 weeks ago was let go from the contractor I worked for 28 years. Had to leave behind my Sman manifold that was supplied by said contractor. Got a new gig 2 weeks ago and new contactor gave me a set of beat to hell 3 port JB analog guages. I've been drooling over the wirelss probes/temp setups but dont have the $ to throw down on some. I asked about wireless at my new place and they said cost was to much and they don't trust the new wireless probes. Help a guy out brother. Pick me !

  • @jaredreynolds4935
    @jaredreynolds4935 5 днів тому

    hey mikey pipes i had the same situation today and we ended deeming the new gas valve bad, what ended up happening was that another company ended replacing the board. i mostly had worked in nyc and never had that situation happen as in voltage to the gas valve and it didnt work,we replaced 2 valves and it worked and died 8 hours later. is there anything i missed while checking. we even used a contactor to verify the load would pull the magnet. we ohm the wires and still missed it.

  • @machete18
    @machete18 Місяць тому

    Just started doing hvac in January you should send me the probes because Im a patriot that grew up on Long Island, Massapequa and ronkonkoma to be exact. I live in charlotte nc now. Oh and my name is Mike too lol God bless you mikey pipes

  • @DevinHVACInc
    @DevinHVACInc Місяць тому

    Hey Mike. I can definitely used those smart probes. Will make work easy via the Bluetooth since I’m a one person operation. This is Dev. I can pick it up locally.

  • @macogarage6428
    @macogarage6428 Місяць тому +1

    You are the best…. Lol and I was whiting for the click of installing the heat shield metal back… 😜

  • @kirkhemmings8234
    @kirkhemmings8234 Місяць тому

    Love everything you are the best.You are very smart, very brilliant.Love your videos my friend😅

  • @amandagrace6984
    @amandagrace6984 Місяць тому

    I would love to have the testo. I am just out of trade school and I am still building up my tools. And that would be a great set to own. As I can't afford anything right now.

    • @PipeDoctor
      @PipeDoctor  Місяць тому

      It was already given away

  • @drodriguez394
    @drodriguez394 Місяць тому

    What’s your jurisdiction Mike? NYC? I’m pretty sure tape is aloud.

  • @josephbermudez8073
    @josephbermudez8073 Місяць тому +1

    I always confirm voltage and then i take a contactor and wire it see if pulls it in if it does then i got enough to open the valve

    • @tc7922
      @tc7922 Місяць тому

      The Contactor trick for the win… been burned by seeing the voltage when it was not connected to the load… felt dumb when after I went through the trouble of replacing the valve and it still did not light.. back to get a board I went head hung low …

  • @zekenzy6486
    @zekenzy6486 Місяць тому

    Great video. Thank you for sharing

  • @kens.3729
    @kens.3729 Місяць тому

    Here in the Midwest, we’re both Natural Gas and Areas Outside St. Louis are ALL Electric Homes which is Expensive for Furnaces, Water Heaters, etc.

  • @Aepek
    @Aepek Місяць тому

    Love me some percussive maintenance 8:59 as can tell ya lots, but is it “good” to keep there & not replace…..
    If was my unit, I’d say NOPE, but what do I know 😅

  • @scottvolage1752
    @scottvolage1752 Місяць тому

    Making the Trades Great Again Mikey Pipes. #LoveBosch Keep Smashing that Like Button folks. SMASH IT!!!!

  • @tphvac87
    @tphvac87 Місяць тому +5

    I’m screaming thru the phone you got leverage on the opposite side with your drip leg and union ahhhhh! Which ever way works man

    • @PipeDoctor
      @PipeDoctor  Місяць тому +1

      I know but then the other joints could open up

    • @tphvac87
      @tphvac87 Місяць тому +1

      @@PipeDoctor true but that’s why we soap bubbles things

  • @tc7922
    @tc7922 Місяць тому

    I’ll glady take the Testo gauges Mikey… cuz if you ain’t testin your guessin right? Never hurts to have a few sets in que…

  • @jamess2953
    @jamess2953 Місяць тому

    I’m a HVAC and refrigeration tech. I’ve been saving up my tool allowance to buy a set of probes. I would love to try out the testos and then I could use my tool allowance to buy the digital testo gauges instead. I have a set of the original fieldpiece SMANs but they crapped out on me when i was on a roof, a pop up rain shower formed, and some idiot closed and locked the ladder cage of a commercial building while I was up there. I tried to get my digital manifold tucked up inside of a unit, but apparently not fast enough.

    • @PipeDoctor
      @PipeDoctor  Місяць тому

      Sorry you are like a week too late

    • @jamess2953
      @jamess2953 Місяць тому

      @@PipeDoctor Yeah I saw that right after I posted. It’s no problem. I was just getting caught up on my Mikey pipes videos, didn’t realize I was so behind. Keep up the great work!

  • @Solothekid
    @Solothekid Місяць тому

    Mikey 6 yr hvac tech from Philly would love to give those testos a spin, and a couple of those pipe doctor chasity cages you got, thanks; me personally choose not to wear when working but I do wear my Beckett underwear because bring oil back 2024 believe 🙏🏻😢.

  • @andresbarragan8595
    @andresbarragan8595 Місяць тому

    FROM CHICAGO EXELENT VIDEO THANK YOU SO MUCH

  • @Ikke-wi2xy
    @Ikke-wi2xy Місяць тому

    Mikey, why not replace the inducermotor also? Kind regards

    • @PipeDoctor
      @PipeDoctor  Місяць тому +2

      Cause it ain’t in the wallet

  • @nickmrt2670
    @nickmrt2670 4 дні тому

    Wondering why the inducer motor was making that noise at startup?

  • @garypitts4139
    @garypitts4139 Місяць тому

    I'd really love to get a set of those become I'm starting my own ac business on the side and I am needing a professional set like those. I don't have the money for those bad boys and it would be a blessing to own a set.

  • @goofybeer1
    @goofybeer1 Місяць тому +1

    Is that blue sealant rated for gas ?

  • @jacobpasake8802
    @jacobpasake8802 Місяць тому +1

    Code sta 18 “ electrical failure” on a New Yorker, any ideas for me? 1st time home owner. Heat is working but turning on and off. Thermostat says heat on

    • @PipeDoctor
      @PipeDoctor  Місяць тому +3

      Control

    • @jacobpasake8802
      @jacobpasake8802 Місяць тому

      @@PipeDoctor strange because the whole unit was replaced last year! Thank you

    • @throttlebottle5906
      @throttlebottle5906 Місяць тому

      I think STA 18 is waiting for flue damper, maybe stuck damper or bad wire connection from damper to control. but the control could also be failing at the damper connector/other.

  • @throttlebottle5906
    @throttlebottle5906 Місяць тому

    in the past I have torn down random gas valves and the later model failures are many times a bad full wave rectifier with a dead diode or two. those are the ones with solenoid coils, so they rectify the AC to DC for the coil, while I didn't dive much deeper into the electronics/electrical design, I assume it's that way to A. not make a buzzing sound and B. not cause coil heating.
    some were failures by debris and somehow getting stick goo inside hanging the physical plunger(s) or the diaphragm/control passage ports.
    "NEVER, try to repair or modify a gas valve", too much liability and lives at stake!

  • @everettstevenson2111
    @everettstevenson2111 Місяць тому

    By the way, Mikey you know that furnace should up at lease 1 inch from that bare concrete floor. Again was in the international building code book at one time.

  • @DanielMalkokian
    @DanielMalkokian Місяць тому

    Lol, I know a couple of homeowners that will sit in the basement and tap that gas valve every time 😂

  • @JoeJoe-gg9uc
    @JoeJoe-gg9uc Місяць тому +1

    😂😂😂😂 “oh yeah oh yeah baby oh yeah “ 😂😂😂😂😂

  • @MedinaCliff
    @MedinaCliff Місяць тому +7

    Mickey..
    Why did you not clean out the inside of the gas pipe of that glob of pipe dope, you dope
    You know that has the potential to clog the gas valve.
    Shame on you Bro!

  • @kat2641
    @kat2641 Місяць тому +2

    Rolling on the floor laughing!!! Any one else?? I would question if you put the roll out heat plate back in place . But pipe dr? Nope never had a doubt about proper re- install.. An gee you gave that gas valve such a love tap 😂😂 don’t watch me 😂😂😂 But seriously that unit is short short life glad it’s you all an not us having to replace it 👍 I absolutely hate tight quarters.

    • @PipeDoctor
      @PipeDoctor  Місяць тому +1

      I’m glad I made this video a little interesting a little different than the others. I typically post.

  • @catchingdreams600
    @catchingdreams600 Місяць тому

    Nooo, Mikey you should’ve replaced that galvanized nipple. That’s Mikey mouse.

  • @DiogoDC123
    @DiogoDC123 Місяць тому

    those american standard furnaces have heat exchangers made of paper

  • @PJam2019
    @PJam2019 Місяць тому +3

    Tape on the gas line 😭

    • @PipeDoctor
      @PipeDoctor  Місяць тому +2

      Some Jurisdictions it’s required

    • @MedinaCliff
      @MedinaCliff Місяць тому +3

      Did you see the glob of pipe dope he left in the pipe..lol

  • @merllhagard6799
    @merllhagard6799 Місяць тому

    You should send me the testo gen two because I'm just a badass guager. I'm confident, not arrogant. I don't think I qualify though because I'm a lic electrician and hvac tech😂

  • @ThumperKJFK
    @ThumperKJFK Місяць тому +1

  • @jameshill1281
    @jameshill1281 16 днів тому

    Never ever hit a gas valve. Diagnose it. Also I would replace inducer motor

  • @tphvac87
    @tphvac87 Місяць тому +3

    Use the Smurf jizzem 😂

    • @PipeDoctor
      @PipeDoctor  Місяць тому +2

      Tell me about it. Until then, I got Smurf jizz removal wipes. Aka your sisters panties

    • @tphvac87
      @tphvac87 Місяць тому +2

      @@PipeDoctor 😂

    • @DanielMalkokian
      @DanielMalkokian Місяць тому

      😂

  • @MrMjn5000
    @MrMjn5000 Місяць тому +1

    nice job as always......

  • @dennisgallear409
    @dennisgallear409 Місяць тому

    🙂

  • @throttlebottle5906
    @throttlebottle5906 Місяць тому

    umm, 4 blinks is "limit switch open". Mikey needs glasses 🤓🤓 join the crowd!

  • @scottmaz4063
    @scottmaz4063 Місяць тому +3

    #1😂

  • @avinashdesai0206
    @avinashdesai0206 Місяць тому +1

    Car starter

    • @PipeDoctor
      @PipeDoctor  Місяць тому

      Thanks for sharing your feedback

  • @everettstevenson2111
    @everettstevenson2111 Місяць тому +1

    Apollo 13 flight control, do we have a go or no go. Mikey are we still on VOX or Baby VOX again copy.

  • @steveblake8766
    @steveblake8766 Місяць тому

    134 Thumbs up

  • @boby115
    @boby115 Місяць тому

    They are called face bushings (FYI ) & you know better (putting too much pipe dope on & inside the pipe 🤷🏻‍♂️), slow down a little bit.

  • @everettstevenson2111
    @everettstevenson2111 Місяць тому

    Hey Mike Daiack, of Mikey Pipes Plumbing not easy being cheesy. You know that the natural gas isn't 100% moisture free. Honeywell and white roger at one time had a ceramic or foam filter inside its gas valve. I did not you clean the flame sensor? Come on Mikey, no little PM again. If were living and working in russian, you be taking a bucket also into the house.lol. Love you buddy, you be safe out there.

    • @everettstevenson2111
      @everettstevenson2111 Місяць тому

      you would be taking a bucket of coal into the house too, unquote.

  • @harryschrysan3183
    @harryschrysan3183 Місяць тому

    Good work pipes!!
    I would recommend the customer to replace that vent motor as well. Sounds bad. Peace from 🇨🇦

    • @PipeDoctor
      @PipeDoctor  Місяць тому +1

      Yeah, well you could bring a camel to water can’t make a drink

  • @merllhagard6799
    @merllhagard6799 Місяць тому

    You should send me the testo gen two because I'm just a badass guager. I'm confident, not arrogant. I don't think I qualify though because I'm a lic electrician and hvac tech😂